| Parameter | Value |
|---|---|
| GTIN | 4046356448321 |
| Orderkey | 2865968 |
| Catalog page | Page 122 (C-5-2017) |
| Depth (Note) | 114.5 mm |
| Packing unit | 1 pc |
| Width (Note) | 17.5 mm |
| (Input data) | 0 mA (Cable short-circuit in the input) |
| Height (Note) | 112.5 mm |
| Country of origin | DE (Germany) |
| (Connection data) | Class I, Zone 2, Group IIC T4 |
| Custom tariff number | 85437090 |
| (Ambient conditions) | 4 mA ... 20 mA |
| SIL (Connection data) | 2 |
| ATEX (Connection data) | II 3 G Ex nA IIC T4 Gc X |
| Color (Connection data) | gray |
| HART function (General) | Yes |
| Designation (Output data) | Signal conditioner operation |
| Output ripple (Input data) | < 20 mVrms |
| Signal output (Input data) | Signal conditioner operation |
| Noise immunity (Dimensions) | EN 61000-6-2 |
| Screw thread (Power supply) | M3 |
| (Standards and Regulations) | For details about hazardous substances go to tab “Downloads”, Category “Manufacturer's declaration” |
| Conformance (Connection data) | CE-compliant, additionally EN 61326-1 |
| Designation (Connection data) | Input/output/power supply |
| Maximum altitude (Dimensions) | ≤ 2000 m |
| Protocols supported (General) | HART |
| (Data communication (bypass)) | Class I, Zone 2, Group IIC T4 |
| Power consumption (Output data) | < 1.1 W |
| Power dissipation (Output data) | < 1.1 W (24 V DC/ 20 mA) |
| Stripping length (Power supply) | 7 mm |
| Connection method (Power supply) | Screw connection |
| Status display (Connection data) | Green LED (supply voltage) |
| UL, USA/Canada (Connection data) | UL 508 Listed |
| No. of channels (Connection data) | 1 |
| Signal input (Ambient conditions) | Signal conditioner operation |
| Voltage drop (Ambient conditions) | < 3.5 V (in input isolating amplifier operation) |
| ATEX (Data communication (bypass)) | II 3 G Ex nA IIC T4 Gc X |
| Current output signal (Input data) | 0 mA ... 20 mA (active) |
| Housing material (Connection data) | PA 6.6-FR |
| Supply voltage range (Output data) | 19.2 V AC/DC ... 253 V AC/DC (24 V AC/DC ... 230 V AC/DC (-20 % ... +10 %, 50/60 Hz)) |
| Transmission Behavior (Input data) | 1:1 to input signal |
| Voltage output signal (Input data) | 0 V ... 5 V (internal resistance, 250 Ω, 0.1%) |
| Tightening torque max (Power supply) | 0.6 Nm |
| Weight per Piece (excluding packing) | 150.500 g |
| Degree of pollution (Connection data) | 2 |
| Tightening torque, min (Power supply) | 0.5 Nm |
| China RoHS (Standards and Regulations) | Environmentally Friendly Use Period = 50 |
| Electrical isolation (Connection data) | 300 Vrms(Rated insulation voltage (overvoltage category II; degree of pollution 2, safe isolation as per EN 61010-1)) |
| Max. current consumption (Output data) | < 45 mA (24 V DC/ 20 mA) |
| Overvoltage category (Connection data) | II |
| Interference emission (Connection data) | EN 61000-6-4 |
| Step response (10-90%) (Connection data) | < 600 µs (for 4 mA ... 20 mA step) |
| Conformance (Data communication (bypass)) | CE-compliant, additionally EN 61326-1 |
| Current input signal (Ambient conditions) | 0 mA ... 20 mA |
| Nominal supply voltage range (Output data) | 24 V ... 230 V AC/DC (50/60 Hz) |
| Ambient temperature (operation) (Dimensions) | -20 °C ... 60 °C (Any mounting position) |
| Load/output load current output (Input data) | < 600 Ω (20 mA) |
| Maximum transmission error (Connection data) | < 0.1 % (of final value) |
| Noise emission (Data communication (bypass)) | EN 61000-6-4 |
| UL, USA/Canada (Data communication (bypass)) | UL 508 Listed |
| Permissible humidity (operation) (Dimensions) | 10 % ... 95 % (non-condensing) |
| Transmission error, typical (Connection data) | < 0.05 % (of final value) |
| Utilization restriction (Key Commercial Data) | 1 |
| Conductor cross section AWG max. (Power supply) | 14 |
| Conductor cross section AWG min. (Power supply) | 24 |
| Electromagnetic compatibility (Connection data) | Conformance with EMC directive |
| Transmitter supply voltage (Ambient conditions) | > 16 V (20 mA) |
| Conductor cross section solid max. (Power supply) | 2.5 mm² |
| Conductor cross section solid min. (Power supply) | 0.2 mm² |
| Maximum temperature coefficient (Connection data) | < 0.01 %/K |
| Ambient temperature (storage/transport) (Dimensions) | -40 °C ... 85 °C |
| Conductor cross section flexible max. (Power supply) | 2.5 mm² |
| Conductor cross section flexible min. (Power supply) | 0.2 mm² |
| Output behavior in the event of an error (Input data) | 0 mA (Cable break in the input) |
| Flammability rating according to UL 94 (Connection data) | V0 |
| Electromagnetic compatibility (Data communication (bypass)) | Conformance with EMC directive |
| Flammability rating according to UL 94 (Data communication (bypass)) | V0 |
Technical specifications and performance data