| Parameter | Value |
|---|---|
| > 15.3 V (22.5 mA) | |
| Note | and EN 61326-1 |
| Type | Signal conditioners with SIL functional safety |
| Color | gray (RAL 7042) |
| Depth | 113.7 mm |
| Width | 17.5 mm |
| Height | 107.9 mm |
| Altitude | ≤ 2000 m (The technical data refers to altitudes ≤2000 m above mean sea level. For altitudes >2000 m above mean sea level, refer to the data sheet.) |
| Insulation | Safe isolation |
| Application | Analog IN |
| Certificate | CE-compliant |
| Designation | Repeater power supply operation |
| Height range | > 2000 m ... 3000 m |
| Product type | Repeater power supply |
| Test voltage | 2.5 kV AC (50 Hz, 60 s) |
| Voltage drop | < 3.5 V (in input isolating amplifier operation) |
| Configuration | DIP switches |
| HART function | Yes |
| Mounting type | DIN rail mounting |
| Output ripple | < 20 mVrms |
| Identification | II 3 G Ex ec IIC T4 Gc X |
| Noise emission | EN 61000-6-4 |
| Noise immunity | EN 61000-6-2 |
| Product family | MACX Analog |
| Status display | Green LED (supply voltage) |
| No. of channels | 1 |
| Article revision | 10 |
| Depth NS 35/7,5 | 114.5 mm (Snapped onto DIN rail NS 35/7,5 in accordance with EN 60715) |
| Housing material | PA 6.6-FR |
| Number of inputs | 1 |
| Pollution degree | 2 |
| Stripping length | 10 mm |
| Connection method | Push-in connection |
| Number of outputs | 1 |
| Power consumption | < 1.9 W |
| Power dissipation | < 1.6 W (24 V DC / 20 mA) |
| Output description | Current output (active and passive) |
| Dimensional drawing | |
| Protocols supported | HART-transparent |
| Current input signal | 4 mA ... 20 mA |
| Degree of protection | IP20 (not assessed by UL) |
| Electrical isolation | 3-way isolation |
| Overvoltage category | II |
| Supply voltage range | 19.2 V AC/DC ... 253 V AC/DC (50/60 Hz) |
| Current output signal | 4 mA ... 20 mA (active) |
| Ex installation (EPL) | Gc |
| Standards/regulations | IEC/EN 61010-1 |
| Voltage output signal | 1 V ... 5 V (internal resistance, 250 Ω, 0.1%) |
| Step response (10-90%) | < 600 µs (for 4 mA ... 20 mA step) |
| Description of the input | Active current input |
| Max. current consumption | < 75 mA (24 V DC / 20 mA) |
| Rated insulation voltage | 300 Vrms |
| Maximum transmission error | < 0.1 % (of final value) |
| Transmitter supply voltage | > 16 V (20 mA) |
| Conductor cross section AWG | 24 ... 14 |
| Transmission error, typical | < 0.05 % (of final value) |
| Nominal supply voltage range | 24 V AC/DC ... 230 V AC/DC -20 % ... +10 % (50/60 Hz) |
| Signal transmission behavior | In = Out |
| Conductor cross section rigid | 0.2 mm² ... 2.5 mm² |
| Electromagnetic compatibility | Conformance with EMC directive |
| Ambient temperature (operation) | -40 °C ... 60 °C (Any mounting position) |
| Load/output load current output | < 600 Ω (20 mA) |
| Maximum temperature coefficient | < 0.01 %/K |
| Conductor cross section flexible | 0.2 mm² ... 2.5 mm² |
| Permissible humidity (operation) | 10 % ... 95 % (non-condensing) |
| Flammability rating according to UL 94 | V0 (Housing) |
| Ambient temperature (storage/transport) | -40 °C ... 80 °C |
| Output behavior in the event of an error | 0 mA (Cable break in the input) |
| Electrical isolation between input and output | yes |
| Conductor cross section flexible (2 conductors with same cross section) | 0.25 mm² ... 0.34 mm² (TWIN ferrule without plastic sleeve) |
Technical specifications and performance data
Installation and operation guide