| Parameter | Value |
|---|---|
| GTIN | 4046356449533 |
| Note | Made to Order (non-returnable) |
| Orderkey | 2924223 |
| (EMC data) | Class I, Zone 2, Group IIC T4 |
| Catalog page | Page 126 (C-5-2017) |
| Depth (Note) | 114.5 mm |
| Packing unit | 1 pc |
| Width (Note) | 12.5 mm |
| (Input data) | < 730 Ω (22.5 mA) |
| GL (EMC data) | C, EMC1 |
| Height (Note) | 116 mm |
| ATEX (EMC data) | II 3 G Ex nA IIC T4 Gc X |
| Country of origin | DE (Germany) |
| (Connection data) | Class I, Zone 2, Group IIC T4 |
| Custom tariff number | 85437090 |
| GL (Connection data) | C, EMC1 |
| (Ambient conditions) | 4 mA ... 20 mA |
| SIL (Connection data) | 2 |
| ATEX (Connection data) | II 3 G Ex nA IIC T4 Gc X |
| Conformance (EMC data) | CE-compliant, additionally EN 61326-1 |
| Designation (EMC data) | Electromagnetic RF field |
| Color (Connection data) | gray |
| HART function (General) | Yes |
| Noise emission (EMC data) | EN 61000-6-4 |
| UL, USA/Canada (EMC data) | UL 508 Listed |
| Output ripple (Input data) | < 20 mVrms |
| Signal output (Input data) | Current output |
| Noise immunity (Dimensions) | EN 61000-6-2 |
| (Standards and Regulations) | For details about hazardous substances go to tab “Downloads”, Category “Manufacturer's declaration” |
| Conformance (Connection data) | CE-compliant, additionally EN 61326-1 |
| Designation (Connection data) | Input/output/power supply |
| Maximum altitude (Dimensions) | ≤ 2000 m |
| Protocols supported (General) | HART |
| (Data communication (bypass)) | 12.2 x 10-4(10 years) |
| Power dissipation (Output data) | < 1.1 W (24 V DC / 20 mA) |
| Stripping length (Power supply) | 8 mm |
| Connection method (Power supply) | Push-in connection |
| Standards/regulations (EMC data) | EN 61000-4-3 |
| Status display (Connection data) | Green LED (supply voltage) |
| UL, USA/Canada (Connection data) | UL 508 Listed |
| No. of channels (Connection data) | 1 |
| Current output signal (Input data) | 0 mA ... 20 mA |
| Housing material (Connection data) | PA 6.6-FR |
| Supply voltage range (Output data) | 19.2 V DC ... 30 V DC (24 V DC -20%...+25%) |
| Transmission Behavior (Input data) | 1:1 to input signal |
| λDD (Data communication (bypass)) | 0 |
| λDU (Data communication (bypass)) | 2.79 x 10-8(27.9 FIT) |
| λSD (Data communication (bypass)) | 0 |
| λSU (Data communication (bypass)) | 4.965 x 10-7(496.5 FIT) |
| Input impedance (Ambient conditions) | > 100 kΩ (If there is a line fault) |
| Nominal supply voltage (Output data) | 24 V DC |
| Weight per Piece (excluding packing) | 128.900 g |
| Degree of pollution (Connection data) | 2 |
| China RoHS (Standards and Regulations) | Environmentally Friendly Use Period = 50 |
| Electrical isolation (Connection data) | 1.5 kV (50 Hz, 1 min., test voltage) |
| Max. current consumption (Output data) | < 46 mA (24 V DC / 20 mA) |
| Overvoltage category (Connection data) | II |
| REACh SVHC (Standards and Regulations) | Lead 7439-92-1 |
| Interference emission (Connection data) | EN 61000-6-4 |
| Designation (Safety characteristic data) | Electromagnetic RF field |
| Electromagnetic compatibility (EMC data) | Conformance with EMC directive |
| Step response (10-90%) (Connection data) | < 140 µs (for 4 mA ... 20 mA step) |
| Current input signal (Ambient conditions) | 0 mA ... 20 mA |
| Ambient temperature (operation) (Dimensions) | -20 °C ... 60 °C (Any mounting position) |
| Equipment type (Data communication (bypass)) | Type A |
| Load/output load current output (Input data) | < 800 Ω (20 mA) |
| Maximum transmission error (Connection data) | < 0.1 % (of final value) |
| Input voltage limitation (Ambient conditions) | 5.4 V (at 20 mA) |
| Permissible humidity (operation) (Dimensions) | 10 % ... 95 % (non-condensing) |
| Transmission error, typical (Connection data) | < 0.05 % (of final value) |
| Utilization restriction (Key Commercial Data) | EMC: class A product, see manufacturer's declaration in the download area |
| Conductor cross section AWG max. (Power supply) | 16 |
| Conductor cross section AWG min. (Power supply) | 24 |
| Electromagnetic compatibility (Connection data) | Conformance with EMC directive |
| Conductor cross section solid max. (Power supply) | 1.5 mm² |
| Conductor cross section solid min. (Power supply) | 0.2 mm² |
| Flammability rating according to UL 94 (EMC data) | V0 |
| Maximum temperature coefficient (Connection data) | < 0.01 %/K |
| Standards/regulations (Safety characteristic data) | EN 61000-4-3 |
| Integrity requirement (Data communication (bypass)) | IEC 61508 - High demand |
| Ambient temperature (storage/transport) (Dimensions) | -40 °C ... 85 °C |
| Conductor cross section flexible max. (Power supply) | 1.5 mm² |
| Conductor cross section flexible min. (Power supply) | 0.2 mm² |
| Diagnostic coverage (DC) (Data communication (bypass)) | DCS=0 %, DCD=0 % |
| Flammability rating according to UL 94 (Connection data) | V0 |
| Safe Failure Fraction (SFF) (Data communication (bypass)) | 94.68 % |
| Safety Integrity Level (SIL) (Data communication (bypass)) | 2 |
| Probability of a hazardous failure per hour (PFHD) (Data communication (bypass)) | 2,79 x 10-8 |
| Probability of a hazardous failure on demand (PFDAVG) (Data communication (bypass)) | 1.22 x 10-4(1 year) |
Technical specifications and performance data