| Parameter | Value |
|---|---|
| GTIN | 4046356288781 |
| Orderkey | 2865751 |
| (EMC data) | IIB |
| Catalog page | Page 150 (C-5-2017) |
| Depth (Note) | 114.5 mm |
| Packing unit | 1 pc |
| Width (Note) | 35 mm |
| (Input data) | 2 A (28 V DC) |
| Height (Note) | 99 mm |
| ATEX (EMC data) | II (1) G [Ex ia Ga] IIC |
| Group (General) | IIB |
| Group (EMC data) | IIC |
| IECEx (EMC data) | [Ex ia Ga] IIC |
| Shock (EMC data) | 15g, according to IEC 60068-2-27 |
| Country of origin | DE (Germany) |
| (Connection data) | Ex nA nC ic IIC T4 Gc X |
| Shock (Dimensions) | 15g, according to IEC 60068-2-27 |
| Custom tariff number | 85437090 |
| DNV GL-EMC (EMC data) | A |
| SIL (Connection data) | 2 |
| ATEX (Connection data) | II (1) G [Ex ia Ga] IIC |
| Conformance (EMC data) | CE-compliant |
| Designation (EMC data) | Conducted interferences |
| Color (Connection data) | gray |
| IECEx (Connection data) | [Ex ia Ga] IIC |
| Output name (Input data) | Relay output |
| Contact type (Input data) | 3 PDTs |
| Designation (Safety data) | Conducted interferences |
| UL, USA/Canada (EMC data) | UL 508 Listed |
| DNV GL-Humidity (EMC data) | B |
| DNV GL-Enclosure (EMC data) | Required protection according to the Rules shall be provided upon installation on board |
| DNV GL-Vibration (EMC data) | A |
| Noise immunity (Dimensions) | EN 61000-6-2 When being exposed to interference, there may be minimal deviations. |
| Screw thread (Power supply) | M3 |
| (Standards and Regulations) | For details about hazardous substances go to tab “Downloads”, Category “Manufacturer's declaration” |
| Conformance (Connection data) | CE-compliant |
| Contact material (Input data) | AgSnO2, hard gold-plated |
| DNV GL-Temperature (EMC data) | B |
| Designation (Connection data) | Output/supply |
| Maximum altitude (Dimensions) | ≤ 2000 m |
| Max. output power Po (General) | 11 mW |
| Electrical isolation (EMC data) | 4-way, between input/output/power supply/switching output |
| Power consumption (Output data) | < 2.4 W |
| Stripping length (Power supply) | 7 mm |
| Connection method (Power supply) | Screw connection |
| Max. output current Io (General) | 7.4 mA |
| Max. output voltage Uo (General) | 6 V |
| Standards/regulations (EMC data) | EN 61000-4-6 |
| Status display (Connection data) | Green LED (supply voltage, PWR) |
| UL, USA/Canada (Connection data) | UL 508 Listed |
| Vibration (operation) (EMC data) | 5g, accordance to IEC 60068-2-6 |
| Current output signal (Input data) | 4 mA ... 20 mA (in the case of SIL; further free configuration without SIL) |
| Housing material (Connection data) | PA 6.6-FR |
| Supply voltage range (Output data) | 24 V ... 230 V AC/DC (-20 %/+10 %, 50/60 Hz) |
| Vibration (operation) (Dimensions) | 5g, accordance to IEC 60068-2-6 |
| Max. external capacity Co (General) | 15 µF |
| Maximum inrush current (Input data) | 2 A (250 V AC) |
| Standards/regulations (Safety data) | EN 61000-4-6 |
| Mechanical service life (Input data) | 1x 105cycles |
| Tightening torque max (Power supply) | 0.6 Nm |
| Weight per Piece (excluding packing) | 200.000 g |
| Degree of pollution (Connection data) | 2 |
| Max. internal inductance Li (General) | negligible |
| Tightening torque, min (Power supply) | 0.5 Nm |
| China RoHS (Standards and Regulations) | Environmentally Friendly Use Period = 50 |
| Configurable/programmable (Input data) | Yes |
| Electrical isolation (Connection data) | 300 Vrms(Rated insulation voltage (overvoltage category II; degree of pollution 2, safe isolation as per EN 61010-1)) |
| Max. external inductivity Lo (General) | 1 mH |
| Max. internal capacitance Ci (General) | 44 nF |
| Maximum switching voltage (Input data) | 250 V AC (250 V DC) |
| Overvoltage category (Connection data) | II |
| Input signal range (Ambient conditions) | -1000 mV ... 1000 mV |
| Max. current output signal (Input data) | 22 mA |
| Max. voltage output signal (Input data) | ± 11 V |
| Electromagnetic compatibility (EMC data) | Conformance with EMC directive |
| Step response (0–99%) (Connection data) | typ. 1000 ms (With SIL) |
| Typical current consumption (Output data) | < 100 mA (24 V DC) |
| Safety-related maximum voltage Um (General) | 253 V AC/DC |
| Ambient temperature (operation) (Dimensions) | -20 °C ... 65 °C |
| Load/output load current output (Input data) | ≤ 600 Ω (20 mA) |
| Load/output load voltage output (Input data) | ≥ 10 kΩ |
| Maximum transmission error (Connection data) | 0.1 % (e.g. for Pt 100, 300 K span, 4 ... 20 mA) |
| Permissible humidity (operation) (Dimensions) | typ. 5 % ... 95 % (non-condensing) |
| Utilization restriction (Key Commercial Data) | 1 |
| Conductor cross section AWG max. (Power supply) | 14 |
| Conductor cross section AWG min. (Power supply) | 24 |
| Electromagnetic compatibility (Connection data) | Conformance with EMC directive |
| Temperature measuring range (Ambient conditions) | -250 °C ... 2500 °C (Range depending on the sensor type) |
| Conductor cross section solid max. (Power supply) | 2.5 mm² |
| Conductor cross section solid min. (Power supply) | 0.2 mm² |
| Flammability rating according to UL 94 (EMC data) | V0 |
| Maximum temperature coefficient (Connection data) | 0.01 %/K |
| Potentiometer resistance range (Ambient conditions) | 0 Ω ... 50 kΩ |
| Ambient temperature (storage/transport) (Dimensions) | -40 °C ... 85 °C |
| Behavior in the event of a sensor error (Input data) | according to NE 43 or freely configurable |
| Conductor cross section flexible max. (Power supply) | 2.5 mm² |
| Conductor cross section flexible min. (Power supply) | 0.2 mm² |
| Sensor types that can be used (TC) (Ambient conditions) | B, E, J, K, N, R, S, T, L, U, CA, DA, A1G, A2G, A3G, MG, LG |
| Flammability rating according to UL 94 (Connection data) | V0 |
| Sensor types (RTD) that can be used (Ambient conditions) | Pt, Ni, Cu sensors: 2, 3, 4-wire |
| Typical deviation from the measuring range final value (Safety data) | 2 % |
Technical specifications and performance data