| Parameter | Value |
|---|---|
| GTIN | 4046356160407 |
| Orderkey | 2865382 |
| Catalog page | Page 142 (C-5-2017) |
| Depth (Note) | 114.5 mm |
| Packing unit | 1 pc |
| Width (Note) | 12.5 mm |
| (Input data) | > 22.5 mA (In the event of cable short circuit at the input (as per NE 43)) |
| Height (Note) | 99 mm |
| (Safety data) | IIB |
| Country of origin | DE (Germany) |
| (Connection data) | Ex nA [ia Ga] IIC T4 Gc |
| ATEX (Safety data) | II (1) G [Ex ia Ga] IIC |
| Group (Safety data) | IIC |
| IECEx (Safety data) | [Ex ia Ga] IIC |
| Custom tariff number | 85437090 |
| SIL (Connection data) | 3 |
| ATEX (Connection data) | II (1) G [Ex ia Ga] IIC |
| Color (Connection data) | green |
| HART function (General) | Yes |
| IECEx (Connection data) | [Ex ia Ga] IIC |
| DNV GL-EMC (Safety data) | A |
| Conformance (Safety data) | CE-compliant, additionally EN 61326 |
| Signal output (Input data) | Current output |
| Noise immunity (Dimensions) | EN 61000-6-2 When being exposed to interference, there may be minimal deviations. |
| Screw thread (Power supply) | M3 |
| (Standards and Regulations) | For details about hazardous substances go to tab “Downloads”, Category “Manufacturer's declaration” |
| Noise emission (Safety data) | EN 61000-6-4 |
| UL, USA/Canada (Safety data) | Class I Div 2; IS for Class I, II, III Div 1 |
| Conformance (Connection data) | CE-compliant, additionally EN 61326 |
| DNV GL-Humidity (Safety data) | B |
| Designation (Connection data) | Output 1/output 2/ power supply |
| Maximum altitude (Dimensions) | ≤ 2000 m |
| Protocols supported (General) | HART |
| DNV GL-Enclosure (Safety data) | Required protection according to the Rules shall be provided upon installation on board |
| DNV GL-Vibration (Safety data) | A |
| Power dissipation (Output data) | < 1.4 W (at 24 V DC / 20 mA) |
| Stripping length (Power supply) | 7 mm |
| Connection method (Power supply) | Screw connection |
| DNV GL-Temperature (Safety data) | B |
| Status display (Connection data) | Green LED (supply voltage) |
| UL, USA/Canada (Connection data) | Class I Div 2; IS for Class I, II, III Div 1 |
| No. of channels (Connection data) | 2 |
| Signal input (Ambient conditions) | Intrinsically safe |
| Current output signal (Input data) | 4 mA ... 20 mA (active) |
| Housing material (Connection data) | PA 6.6-FR |
| Supply voltage range (Output data) | 19.2 V DC ... 30 V DC (24 V DC -20%...+25%) |
| Transmission Behavior (Input data) | 1:1 to input signal |
| Group (Data communication (bypass)) | IIB |
| Nominal supply voltage (Output data) | 24 V DC |
| Tightening torque max (Power supply) | 0.6 Nm |
| Weight per Piece (excluding packing) | 163.800 g |
| Degree of pollution (Connection data) | 2 |
| Tightening torque, min (Power supply) | 0.5 Nm |
| China RoHS (Standards and Regulations) | Environmentally Friendly Use Period = 50 |
| Electrical isolation (Connection data) | 1.5 kV (50 Hz, 1 min., test voltage) |
| Max. current consumption (Output data) | < 100 mA (24 V / 20 mA) |
| Overvoltage category (Connection data) | II |
| Interference emission (Connection data) | EN 61000-6-4 |
| Step response (10-90%) (Connection data) | < 1.3 ms (for 4 mA ... 20 mA step) |
| Current input signal (Ambient conditions) | 4 mA ... 20 mA |
| Electromagnetic compatibility (Safety data) | Conformance with EMC directive |
| Ambient temperature (operation) (Dimensions) | -20 °C ... 60 °C (Any mounting position) |
| Load/output load current output (Input data) | ≤ 450 Ω (20 mA) |
| Maximum transmission error (Connection data) | < 0.1 % (of final value) |
| Permissible humidity (operation) (Dimensions) | 10 % ... 95 % (non-condensing) |
| Transmission error, typical (Connection data) | < 0.05 % (of final value) |
| Utilization restriction (Key Commercial Data) | EMC: class A product, see manufacturer's declaration in the download area |
| Conductor cross section AWG max. (Power supply) | 14 |
| Conductor cross section AWG min. (Power supply) | 24 |
| Electromagnetic compatibility (Connection data) | Conformance with EMC directive |
| Transmitter supply voltage (Ambient conditions) | > 16 V (20 mA) |
| Conductor cross section solid max. (Power supply) | 2.5 mm² |
| Conductor cross section solid min. (Power supply) | 0.2 mm² |
| Maximum temperature coefficient (Connection data) | < 0.01 %/K |
| Max. output power Po (Data communication (bypass)) | 587 mW |
| Ambient temperature (storage/transport) (Dimensions) | -40 °C ... 80 °C |
| Conductor cross section flexible max. (Power supply) | 2.5 mm² |
| Conductor cross section flexible min. (Power supply) | 0.2 mm² |
| Flammability rating according to UL 94 (Safety data) | V0 |
| Max. output current Io (Data communication (bypass)) | 93 mA |
| Max. output voltage Uo (Data communication (bypass)) | 25.2 V |
| Underload/overload signal range (Ambient conditions) | 0 mA ... 24 mA |
| Output behavior in the event of an error (Input data) | < 3.6 mA (In the event of cable break at the input (as per NE 43)) |
| Max. external capacity Co (Data communication (bypass)) | 820 nF |
| Flammability rating according to UL 94 (Connection data) | V0 |
| Max. external inductivity Lo (Data communication (bypass)) | 4 mH |
| Safety-related maximum voltage Um (Data communication (bypass)) | 253 V AC (125 V DC) |
Technical specifications and performance data