| Parameter | Value |
|---|---|
| 4 mA ... 20 mA | |
| EMC | B |
| Note | and EN 61326 |
| Type | Ex i signal conditioners with SIL functional safety |
| Color | gray (RAL 7042) |
| Depth | 114.5 mm |
| Width | 12.5 mm |
| Height | 116 mm |
| Altitude | ≤ 2000 m |
| Humidity | B |
| Enclosure | Required protection according to the Rules shall be provided upon installation on board |
| Vibration | A |
| Application | Analog OUT |
| Certificate | CE-compliant |
| Designation | Electromagnetic RF field |
| Temperature | B |
| Product type | Output signal conditioner |
| Test voltage | 1.5 kV AC (50 Hz, 60 s) |
| Voltage drop | 5.4 V (20 mA) |
| HART function | Yes |
| Mounting type | DIN rail mounting |
| Output ripple | < 20 mVrms |
| Identification | II (1) G [Ex ia Ga] IIC/IIB |
| Noise emission | EN 61000-6-4 |
| Noise immunity | EN 61000-6-2 |
| Status display | Green LED (supply voltage) |
| Input impedance | > 100 kΩ (If there is a line fault) |
| No. of channels | 1 |
| Article revision | 09 |
| Housing material | PA 6.6-FR |
| Number of inputs | 1 |
| Pollution degree | 2 |
| Stripping length | 8 mm |
| Connection method | Push-in connection |
| Number of outputs | 1 |
| Power dissipation | < 1.1 W (24 V DC / 20 mA) |
| Output description | Current output |
| Dimensional drawing | |
| Protocols supported | HART |
| Current input signal | 0 mA ... 20 mA |
| Degree of protection | IP20 (not assessed by UL) |
| Electrical isolation | 3-way isolation |
| Max. output power Po | 633 mW |
| Overvoltage category | II |
| Supply voltage range | 19.2 V DC ... 30 V DC (24 V DC, -20 % ... +25 %) |
| Current output signal | 0 mA ... 20 mA (intrinsically safe) |
| Standards/regulations | EN 61000-4-3 |
| Max. output current Io | 92 mA |
| Max. output voltage Uo | 27.7 V |
| Nominal supply voltage | 24 V DC |
| Step response (10-90%) | < 140 µs (for 4 mA ... 20 mA step) |
| Max. current consumption | < 46 mA (24 V DC / 20 mA) |
| Maximum transmission error | < 0.1 % (of final value) |
| Conductor cross section AWG | 24 ... 16 |
| Safety Integrity Level (SIL) | 2 |
| Signal transmission behavior | In = Out |
| Conductor cross section rigid | 0.2 mm² ... 1.5 mm² |
| Electromagnetic compatibility | Conformance with EMC directive |
| Ambient temperature (operation) | -20 °C ... 60 °C (Any mounting position) |
| Load/output load current output | < 800 Ω (20 mA) |
| Maximum temperature coefficient | < 0.01 %/K |
| Conductor cross section flexible | 0.2 mm² ... 1.5 mm² |
| Permissible humidity (operation) | 10 % ... 95 % (non-condensing) |
| Safety-related maximum voltage Um | 253 V AC (125 V DC) |
| Flammability rating according to UL 94 | V0 (Housing) |
| Ambient temperature (storage/transport) | -40 °C ... 80 °C |
| Electrical isolation between input and output | yes |
| Typical deviation from the measuring range final value | 1 % |
| IIB: Max. external inductivity Lo/ Max. external capacitance Co | 4 mH / 663 nF |
| IIC: Max. external inductivity Lo/ Max. external capacitance Co | 2 mH / 85 nF |
Technical specifications and performance data