| Parameter | Value |
|---|---|
| GTIN | 4046356160490 |
| Orderkey | 2865476 |
| (General) | 1.5 x 10-3(5 years) |
| (EMC data) | IIB/IIIC |
| Catalog page | Page 153 (C-5-2017) |
| Depth (Note) | 114.5 mm |
| Packing unit | 1 pc |
| Width (Note) | 12.5 mm |
| (Input data) | 30 V DC (2 A) |
| Height (Note) | 99 mm |
| λDD (General) | 6 x 10-9(6 FIT) |
| λDU (General) | 6.2 x 10-8(62 FIT) |
| λSD (General) | 1 x 10-9(1 FIT) |
| λSU (General) | 2.48 x 10-7(248 FIT) |
| ATEX (EMC data) | II (1) G [Ex ia Ga] IIC |
| Group (EMC data) | IIC |
| IECEx (EMC data) | [Ex ia Ga] IIC |
| Country of origin | DE (Germany) |
| (Connection data) | UL 61010 Listed |
| Custom tariff number | 85437090 |
| (Ambient conditions) | Short circuit 100 Ω < RSensor < 360 Ω |
| DNV GL-EMC (EMC data) | B |
| Designation (General) | Inverted operation |
| SIL (Connection data) | 2 |
| ATEX (Connection data) | II (1) G [Ex ia Ga] IIC |
| Conformance (EMC data) | CE-compliant, additionally EN 61326 |
| Designation (EMC data) | Conducted interferences |
| Color (Connection data) | gray |
| IECEx (Connection data) | [Ex ia Ga] IIC |
| Equipment type (General) | Type A |
| Contact type (Input data) | 1 N/O contact per channel |
| Designation (Safety data) | Conducted interferences |
| Noise emission (EMC data) | EN 61000-6-4 |
| UL, USA/Canada (EMC data) | Class I Div 2; IS for Class I, II, III Div 1 |
| DNV GL-Humidity (EMC data) | B |
| DNV GL-Enclosure (EMC data) | Required protection according to the Rules shall be provided upon installation on board |
| DNV GL-Vibration (EMC data) | A |
| Noise immunity (Dimensions) | EN 61000-6-2 EN 61326 |
| Screw thread (Power supply) | M3 |
| (Standards and Regulations) | For details about hazardous substances go to tab “Downloads”, Category “Manufacturer's declaration” |
| Conformance (Connection data) | CE-compliant, additionally EN 61326 |
| Contact material (Input data) | AgSnO2, hard gold-plated |
| DNV GL-Temperature (EMC data) | B |
| Designation (Connection data) | Output 1/output 2/input/power supply, DIN rail connector |
| Maximum altitude (Dimensions) | ≤ 2000 m |
| Switching output (Input data) | Relay output |
| Evaluation criterion (EMC data) | A |
| Integrity requirement (General) | IEC 61508 - Low demand |
| Power consumption (Output data) | 0.8 W |
| Power dissipation (Output data) | < 1 W |
| Stripping length (Power supply) | 7 mm |
| Connection method (Power supply) | Screw connection |
| Standards/regulations (EMC data) | EN 61000-4-6 |
| Status display (Connection data) | Green LED (supply voltage) |
| Switching frequency (Input data) | ≤ 20 Hz (without load) |
| UL, USA/Canada (Connection data) | Class I Div 2; IS for Class I, II, III Div 1 |
| No. of channels (Connection data) | 2 |
| Signal input (Ambient conditions) | Intrinsically safe |
| Diagnostic coverage (DC) (General) | DCS= 0.4 %, DCD= 8 % |
| Evaluation criterion (Safety data) | A |
| Group (Safety characteristic data) | IIB/IIIC |
| Housing material (Connection data) | PA 6.6-FR |
| Supply voltage range (Output data) | 19.2 V DC ... 30 V DC (24 V DC -20%...+25%) |
| Standards/regulations (Safety data) | EN 61000-4-6 |
| Mechanical service life (Input data) | 107cycles |
| Nominal supply voltage (Output data) | 24 V DC -20 % ... +25 % |
| Tightening torque max (Power supply) | 0.6 Nm |
| Weight per Piece (excluding packing) | 143.300 g |
| Degree of pollution (Connection data) | 2 |
| Non-load voltage (Ambient conditions) | ~ 8 V DC |
| Safe Failure Fraction (SFF) (General) | 78 % |
| Tightening torque, min (Power supply) | 0.5 Nm |
| China RoHS (Standards and Regulations) | Environmentally Friendly Use Period = 50 |
| Electrical isolation (Connection data) | 2.5 kV (50 Hz, 1 min., test voltage) |
| Max. current consumption (Output data) | 35 mA (24 V DC) |
| Maximum switching voltage (Input data) | 250 V AC (2 A) |
| Overvoltage category (Connection data) | III |
| Safety Integrity Level (SIL) (General) | 1 |
| Interference emission (Connection data) | EN 61000-6-4 |
| Maximum switching capacity (Input data) | 500 VA |
| Electromagnetic compatibility (EMC data) | Conformance with EMC directive |
| Line fault detection (Ambient conditions) | Break 0.05 mA < IIN < 0.35 mA |
| Switching hysteresis (Ambient conditions) | < 0.2 mA |
| Short-circuit current (Ambient conditions) | ~ 8 mA |
| Ambient temperature (operation) (Dimensions) | -20 °C ... 60 °C (Any mounting position) |
| Available input sources (Ambient conditions) | NAMUR proximity sensors (IEC/EN 60947-5-6) |
| Permissible humidity (operation) (Dimensions) | 5 % ... 95 % (non-condensing) |
| Utilization restriction (Key Commercial Data) | 1 |
| Conductor cross section AWG max. (Power supply) | 14 |
| Conductor cross section AWG min. (Power supply) | 24 |
| Electromagnetic compatibility (Connection data) | Conformance with EMC directive |
| Conductor cross section solid max. (Power supply) | 2.5 mm² |
| Conductor cross section solid min. (Power supply) | 0.2 mm² |
| Flammability rating according to UL 94 (EMC data) | V0 |
| Max. output power Po (Safety characteristic data) | 25 mW |
| Switching points (attenuated) (Ambient conditions) | < 1.2 mA (blocking) |
| Max. output current Io (Safety characteristic data) | 10 mA |
| Max. output voltage Uo (Safety characteristic data) | 9.6 V |
| Ambient temperature (storage/transport) (Dimensions) | -40 °C ... 80 °C |
| Conductor cross section flexible max. (Power supply) | 2.5 mm² |
| Conductor cross section flexible min. (Power supply) | 0.2 mm² |
| Switching points (unattenuated) (Ambient conditions) | > 2.1 mA (conductive) |
| Max. external capacity Co (Safety characteristic data) | 26 µF |
| Flammability rating according to UL 94 (Connection data) | V0 |
| Max. internal inductance Li (Safety characteristic data) | negligible |
| Max. external inductivity Lo (Safety characteristic data) | 1000 mH |
| Max. internal capacitance Ci (Safety characteristic data) | 11 nF |
| Safety-related maximum voltage Um (Safety characteristic data) | 253 V AC (125 V DC) |
| Probability of a hazardous failure on demand (PFDAVG) (General) | 3.01 x 10-4(1 year) |
Technical specifications and performance data
Installation and operation guide