| Parameter | Value |
|---|---|
| 4 mA ... 20 mA (with HART) | |
| Load | 0 Ω ... 600 Ω |
| Note | With connection of power sources |
| Depth | 113.7 mm |
| Width | 17.5 mm |
| Height | 112.5 mm |
| General | Accuracy, typically specified as a percentage of the measuring span (20 mA) at UN, 23°C |
| Altitude | ≤ 2000 m |
| Input signal | Current |
| Product type | Repeater power supplies |
| Screw thread | M3 |
| Test voltage | 350 V (50 Hz, 60 s) |
| Input current | ≤ 50 mA (for mA sources) |
| Mounting type | NS 35/15, NS 35/7,5 |
| Identification | II (1) G [Ex ia Ga] IIC |
| Input power Pi | limited internally |
| Product family | MACX Analog |
| Status display | Green LED (supply voltage) |
| No. of channels | 1 |
| Depth NS 35/7,5 | 114.5 mm (Snapped onto DIN rail NS 35/7,5 in accordance with EN 60715) |
| Housing material | Polyamide (PA 6.6) |
| Input current Ii | 100 mA |
| Input voltage Ui | 30 V |
| Non-load voltage | ≤ 26 V |
| Stripping length | 7 mm |
| Connection method | Screw connection |
| Cross section AWG | (converted acc. to IEC) |
| Mounting position | vertical, horizontal |
| Power consumption | 2.7 W (20 mA) |
| Power dissipation | 2.2 W (RL250 Ω) |
| Output description | Current output (active) |
| Dimensional drawing | |
| Ex i circuits (EPL) | Ga |
| Protocols supported | HART-transparent |
| Current input signal | 0 mA ... 20 mA |
| Degree of protection | IP20 (Terminal blocks) |
| Electrical isolation | 3-way isolation |
| Line fault detection | < 3.6 mA (Line break) |
| Max. output power Po | 576 mW |
| Supply voltage range | 18 V ... 31.2 V |
| Current output signal | 0 mA ... 20 mA |
| Ex installation (EPL) | Gc |
| Short-circuit current | ≤ 35 mA |
| Standards/regulations | IEC/EN 60079-11 |
| Max. output current Io | 88 mA |
| Max. output voltage Uo | 27 V |
| Max. switching current | 100 mA |
| Nominal supply voltage | 24 V DC |
| Output ripple (current) | ≤ 40 µA (effective) |
| Description of the input | active and passive current input, intrinsically safe |
| Rated insulation voltage | 375 VPP |
| Frequency measuring range | 0.5 kHz ... 10 kHz (bidirectional HART transmission) |
| Maximum switching voltage | 30 V |
| Conductor cross section AWG | 24 ... 14 |
| Max. internal inductance Li | negligible |
| Reverse polarity protection | yes |
| Max. internal capacitance Ci | negligible |
| Signal transmission behavior | In = Out |
| Conductor cross section rigid | 0.2 mm² ... 2.5 mm² |
| Electromagnetic compatibility | Tested in accordance with the following standards and regulations: EN 61326-1 For industrial use, NAMUR NE 21 |
| Input resistance current input | ≤ 100 Ω (for mA sources) |
| Ambient temperature (operation) | -20 °C ... 70 °C (Stand-alone device: any mounting position) |
| Conductor cross section flexible | 0.2 mm² ... 2.5 mm² |
| Permissible humidity (operation) | ≤ 95 % (non-condensing) |
| Temperature coefficient, typical | ≤ 0.05 % (10 K) |
| Safety-related maximum voltage Um | 253 V AC |
| Flammability rating according to UL 94 | V0 |
| Ambient temperature (storage/transport) | -40 °C ... 80 °C |
| I (mixed circuit): Max. external inductivity Lo/ Max. external capacitance Co | 40 mH / 480 nF, 20 mH / 660 nF, 0.5 mH / 810 nF, 0.1 mH / 1200 nF |
| I (simple circuit): Max. external inductivity Lo/ Max. external capacitance Co | 40 mH / 3750 nF |
| IIA (mixed circuit): Max. external inductivity Lo/ Max. external capacitance Co | 28 mH / 410 nF, 2 mH / 480 nF, 1 mH / 540 nF, 0.2 mH / 820 nF |
| IIC (mixed circuit): Max. external inductivity Lo/ Max. external capacitance Co | 2 mH / 42 nF, 1 mH / 56 nF, 0.5 mH / 72 nF, 0.2 mH / 90 nF |
| IIA (simple circuit): Max. external inductivity Lo/ Max. external capacitance Co | 28 mH / 2330 nF |
| IIC (simple circuit): Max. external inductivity Lo/ Max. external capacitance Co | 2.3 mH / 90 nF |
| IIB/IIIC (mixed circuit): Max. external inductivity Lo/ Max. external capacitance Co | 17 mH / 290 nF, 2 mH / 320 nF, 0.5 mH / 460 nF, 0.2 mH / 600 nF |
| IIB/IIIC (simple circuit): Max. external inductivity Lo/ Max. external capacitance Co | 17 mH / 705 nF |
Technical specifications and performance data