| Parameter | Value |
|---|---|
| Da | |
| Depth | 113.7 mm |
| Width | 17.5 mm |
| Height | 107.8 mm |
| General | Installation conditions influence the ambient temperature.Please refer to the “Control cabinet installation instructions”. |
| Altitude | ≤ 2000 m |
| Product type | Solenoid driver |
| Test voltage | 500 V (50 Hz, 60 s) |
| Mounting type | NS 35/15, NS 35/7,5 |
| Identification | II (1) G [Ex ia Ga] IIC |
| Product family | MACX Analog |
| Status display | Yellow LED/per channel |
| No. of channels | 2 |
| Depth NS 35/7,5 | 114.5 mm (Snapped onto DIN rail NS 35/7,5 in accordance with EN 60715) |
| Housing material | Polyamide (PA 6.6) |
| Stripping length | 8 mm |
| Connection method | Push-in connection |
| Cross section AWG | (converted acc. to IEC) |
| Mounting position | vertical, horizontal |
| Power consumption | 0.5 W (+ (lAx 37 mW/mA)) |
| Output description | intrinsically safe |
| Dimensional drawing | |
| Ex i circuits (EPL) | Ga |
| Switching frequency | ≤ 10 Hz |
| Degree of protection | IP20 (Terminal blocks) |
| Electrical isolation | 4-way isolation |
| Max. output power Po | 760 mW |
| Supply voltage range | loop-powered, no external supply necessary |
| Ex installation (EPL) | Gc |
| Standards/regulations | IEC/EN 60079-11 |
| Typical response time | ≤ 18 ms |
| Typical turn-off time | ≤ 50 ms |
| Max. output current Io | 110 mA (Ex ia) |
| Max. output voltage Uo | 27.6 V |
| Rated insulation voltage | 375 VPP |
| Switching level "0" signal | 0 V ... 5 V |
| Switching level "1" signal | 18 V ... 31.2 V |
| Conductor cross section AWG | 24 ... 16 |
| Max. internal inductance Li | negligible |
| Reverse polarity protection | yes |
| Max. internal capacitance Ci | 1.1 nF |
| Conductor cross section rigid | 0.2 mm² ... 1.5 mm² |
| Electromagnetic compatibility | Tested in accordance with the following standards and regulations: EN 61326-1 For industrial use, NAMUR NE 21 |
| Ambient temperature (operation) | -20 °C ... 70 °C (Stand-alone device: any mounting position) |
| Conductor cross section flexible | 0.2 mm² ... 1.5 mm² |
| Permissible humidity (operation) | ≤ 95 % (non-condensing) |
| Safety-related maximum voltage Um | 253 V AC |
| Flammability rating according to UL 94 | V0 |
| Ambient temperature (storage/transport) | -40 °C ... 80 °C |
| I (simple circuit): Max. external inductivity Lo/ Max. external capacitance Co | 100 mH / 3.5 µF |
| IIA (simple circuit): Max. external inductivity Lo/ Max. external capacitance Co | 100 mH / 2.22 µF |
| IIB (simple circuit): Max. external inductivity Lo/ Max. external capacitance Co | 9 mH / 667 nF |
| IIC (simple circuit): Max. external inductivity Lo/ Max. external capacitance Co | 1.2 mH / 85 nF |
| IIB/IIIC (simple circuit): Max. external inductivity Lo/ Max. external capacitance Co | 1.8 mH / 665 nF |
Technical specifications and performance data
Installation and operation guide