MACX MCR-EX-AP-2SD-25-35-LP-SP - MACX MCR-EX-AP-2SD-25-35-LP-SP 1291186 PHOENIX CONTACT Ex i-Valve control block to activate Ex i magnetic va..
In Stock Hot Product

MACX MCR-EX-AP-2SD-25-35-LP-SP

MACX MCR-EX-AP-2SD-25-35-LP-SP 1291186 PHOENIX CONTACT Ex i-Valve control block to activate Ex i magnetic va..

$386.66USD
57 in stock
Key Specifications
:Da
Depth:113.7 mm
Width:17.5 mm
Height:107.8 mm
Supplier Information
Products: 0
Usually ships within 2-3 business days
Quality Guaranteed
Fast Shipping
Technical Support

Technical Specifications

ParameterValue
Da
Depth113.7 mm
Width17.5 mm
Height107.8 mm
GeneralInstallation conditions influence the ambient temperature.Please refer to the “Control cabinet installation instructions”.
Altitude≤ 2000 m
Product typeSolenoid driver
Test voltage500 V (50 Hz, 60 s)
Mounting typeNS 35/15, NS 35/7,5
Identification II (1) G [Ex ia Ga] IIC
Product familyMACX Analog
Status displayYellow LED/per channel
No. of channels2
Depth NS 35/7,5114.5 mm (Snapped onto DIN rail NS 35/7,5 in accordance with EN 60715)
Housing materialPolyamide (PA 6.6)
Stripping length8 mm
Connection methodPush-in connection
Cross section AWG(converted acc. to IEC)
Mounting positionvertical, horizontal
Power consumption0.5 W (+ (lAx 37 mW/mA))
Output descriptionintrinsically safe
Dimensional drawing
Ex i circuits (EPL)Ga
Switching frequency≤ 10 Hz
Degree of protectionIP20 (Terminal blocks)
Electrical isolation4-way isolation
Max. output power Po760 mW
Supply voltage rangeloop-powered, no external supply necessary
Ex installation (EPL)Gc
Standards/regulationsIEC/EN 60079-11
Typical response time≤ 18 ms
Typical turn-off time≤ 50 ms
Max. output current Io110 mA (Ex ia)
Max. output voltage Uo27.6 V
Rated insulation voltage375 VPP
Switching level "0" signal0 V ... 5 V
Switching level "1" signal18 V ... 31.2 V
Conductor cross section AWG24 ... 16
Max. internal inductance Linegligible
Reverse polarity protectionyes
Max. internal capacitance Ci1.1 nF
Conductor cross section rigid0.2 mm² ... 1.5 mm²
Electromagnetic compatibilityTested in accordance with the following standards and regulations: EN 61326-1 For industrial use, NAMUR NE 21
Ambient temperature (operation)-20 °C ... 70 °C (Stand-alone device: any mounting position)
Conductor cross section flexible0.2 mm² ... 1.5 mm²
Permissible humidity (operation)≤ 95 % (non-condensing)
Safety-related maximum voltage Um253 V AC
Flammability rating according to UL 94V0
Ambient temperature (storage/transport)-40 °C ... 80 °C
I (simple circuit): Max. external inductivity Lo/ Max. external capacitance Co100 mH / 3.5 µF
IIA (simple circuit): Max. external inductivity Lo/ Max. external capacitance Co100 mH / 2.22 µF
IIB (simple circuit): Max. external inductivity Lo/ Max. external capacitance Co9 mH / 667 nF
IIC (simple circuit): Max. external inductivity Lo/ Max. external capacitance Co1.2 mH / 85 nF
IIB/IIIC (simple circuit): Max. external inductivity Lo/ Max. external capacitance Co1.8 mH / 665 nF

Product Description