| Parameter | Value |
|---|---|
| < 100 Ω ... 360 Ω (Short Circuit) | |
| Load | 0 Ω ... 600 Ω |
| Depth | 113.7 mm |
| Width | 17.5 mm |
| Height | 112.5 mm |
| Marked | II (1) G [Ex ia Ga] IIC |
| General | Accuracy, typical data in % of the basic measurement interval with UN, 23 °C |
| Altitude | ≤ 2000 m |
| Impulse Time | 25 μs |
| Product Type | Frequency value transformer |
| Screw thread | M3 |
| Test voltage | 350 V (50 Hz, 60 sec) |
| Configuration | Software |
| Product Family | MACX Analog |
| Shell material | Polyamide (PA 6.6) |
| Supply voltage | 18 V ... 31.2 V |
| Connection type | Screw connection |
| Depth NS 35/7.5 | 114.5 mm (fitted on DIN rail NS 35/7.5 according to EN 60715) |
| Dimension Scheme | |
| Dissipated Power | ≤ 1.5 W |
| Protection Index | IP20 (Terminals) |
| Type of mounting | NS 35/15, NS 35/7.5 |
| Power Consumption | 1.8 W |
| Status Indication | Green LED (supply voltage) |
| Number of channels | 2 |
| Ticket Description | Intrinsic safety |
| Galvanic Separation | 5-way spacing |
| Line Fault Detection | < 0.05 mA ... 0.35 mA (Cable Break) |
| Usable Input Sources | According to IEC/EN 60947-5-6 NAMUR |
| AWG Conductor Section | (Converted according to IEC) |
| Current Output Signal | 0 mA ... 20 mA (configurable) |
| Ex Installation (EPL) | Gc |
| Max. output power Por | 61.4 mW |
| Position for mounting | vertical, horizontal |
| Nominal Supply Voltage | 24 V DC |
| Max. Output Current Ior | 23.4 mA |
| Max. output voltage Uor | 10.5 V |
| Rigid conductor section | 0.2 mm² ... 2.5 mm² |
| Standards/Specifications | IEC/EN 60079-11 |
| Length to be de-insulated | 7 mm |
| Max. Internal Capacity Ci | despicable |
| Maximum Switching Voltage | 30 V |
| Maximum safety voltage Um | 253 V AC |
| Maximum switching current | 100 mA |
| Sizing Insulation Voltage | 375 VPP |
| Flexible conductor section | 0.2 mm² ... 2.5 mm² |
| Frequency measurement range | 0.001 Hz ... 20000 Hz |
| Internal inductance max. Li | despicable |
| Polarity reversal protection | Yes |
| Ambient Temperature (Service) | -40 °C ... 70 °C (Individual Equipment: Discretionary Mounting Position) |
| Electromagnetic compatibility | Testing according to the following standards and requirements: EN 61326-1 for use in the industrial field, NAMUR NE 21 |
| Typical Temperature Coefficient | ≤ 0.05% |
| Intrinsically safe circuits (EPL) | Ga |
| Permissible air humidity (service) | ≤ 95% (non-condensing) |
| Flammability class according to UL 94 | V0 |
| Ambient Temperature (Storage/Transport) | -40 °C ... 80 °C |
| Output current in case of short circuit | 3.8 mA (Original Factory Settings, Adjustable) |
| Output current in case of cable breakage | 20.5 mA (Original Factory Settings, Adjustable) |
| I (single electrical circuit): External inductance max. Lor/ Max. external capacity Cor | 600 mH / 95 μF |
| I (combined electrical circuit): External inductance max. Lor/ Max. external capacity Cor | 100 mH / 4 μF, 10 mH / 5.7 μF, 2 mH / 7.8 μF, 0.1 mH / 17 μF |
| IIA (Single Electrical Circuit): External inductance max. Lor/ Max. external capacity Cor | 450 mH / 75 μF |
| IIC (Single Electrical Circuit): External inductance max. Lor/ Max. external capacity Cor | 63 mH / 2.41 μF |
| IIA (Combined Electrical Circuit): External inductance max. Lor/ Max. external capacity Cor | 100 mH / 2.9 μF, 10 mH / 4.5 μF, 1 mH / 7.3 μF, 0.1 mH / 14 μF |
| IIC (Combined Electrical Circuit): External inductance max. Lor/ Max. external capacity Cor | 20 mH / 0.49 μF, 5 mH / 0.67 μF, 1 mH / 0.96 μF, 0.2 mH / 1.4 μF |
| IIB/IIIC (Single Electrical Circuit): External Inductance Max. Lor/ Max. external capacity Cor | 230 mH / 16.8 μF |
| IIB/IIIC (Combined Electrical Circuit): External inductance max. Lor/ Max. external capacity Cor | 100 mH / 1.9 μF, 20 mH / 2.7 μF, 2 mH / 4.5 μF, 0.5 mH / 6.4 μF |
Technical specifications and performance data