| Parameter | Value |
|---|---|
| GTIN | 4055626633879 |
| Orderkey | 1045379 |
| (Drawings) | |
| Catalog page | Page 213 (C-4-2019) |
| Packing unit | 1 |
| Number (General) | 1 |
| (EMC Directives) | EN 61000-6-3 |
| ETIM 6.0 (eCl@ss) | EC002300 |
| ETIM 7.0 (eCl@ss) | EC002300 |
| Interface (General) | Ethernet |
| Operation (General) | via Proficloud application and web interface |
| Custom tariff number | 85437090 |
| Pictogram (Drawings) | |
| Altitude (Dimensions) | ≤ 2000 m (amsl (above mean sea level)) |
| Sampling rate (General) | 500 kHz |
| Block diagram (Drawings) | |
| Basic functions (General) | Acquisition of sensor data |
| Type (Ambient conditions) | DIN rail module, one-piece |
| Color (Ambient conditions) | traffic grey A RAL 7042 |
| Screw thread (Connections) | M3 |
| Connection method (General) | RJ45 |
| Horizontal pitch (Drawings) | 1.3 Div. |
| Operating current (General) | ≤ 70 mA |
| Operating voltage (General) | 24 V DC (-15% ... +20% including all tolerances and ripple) |
| Transmission speed (General) | 10/100 Mbps |
| eCl@ss 9.0 (Classifications) | 27200316 |
| Connection name (Connections) | SPD remote indication contact monitoring |
| Note (Typical characteristics) | The T connector can be used to bridge the supply voltage. It can be snapped onto a 35 mm DIN rail according to EN 60715. |
| Stripping length (Connections) | 8 mm |
| Connection method (Connections) | Screw terminal block |
| Maximum measuring period (General) | 1 s |
| Mounting type (Ambient conditions) | DIN rail: 35 mm |
| Cloud platform (Ambient conditions) | Proficloud |
| Housing material (Ambient conditions) | Polyamide |
| REACh SVHC (Standards and Regulations) | Lead 7439-92-1 |
| Screw thread (Typical characteristics) | M3 |
| Note on the connection method (General) | pluggable |
| Connection name (Typical characteristics) | 24 V supply |
| Standards/specifications (EMC Directives) | EN 61000-6-2 |
| Immunity to EF (Remote indication contact) | Noise immunity test in accordance with EN 61000-6-2 Electromagnetic fields EN 61000-4-3/IEC 61000-4-3 Criterion A, Field intensity: 10 V/m |
| Stripping length (Typical characteristics) | 8 mm |
| Connection method (Typical characteristics) | Screw terminal block |
| Immunity to ESD (Remote indication contact) | Noise immunity test in accordance with EN 61000-6-2 Electrostatic discharge (ESD) EN 61000-4-2/IEC 61000-4-2 Criterion B, 6 kV contact discharge, 8 kV air discharge |
| Tightening torque (Typical characteristics) | 0.5 Nm ... 0.6 Nm |
| Ambient temperature (operation) (Dimensions) | -25 °C ... 60 °C |
| Immunity to burst (Remote indication contact) | Noise immunity test in accordance with EN 61000-6-2 Fast transients (burst) EN 61000-4-4/IEC 61000-4-4 Criterion A, 2.2 kV |
| Immunity to surge (Remote indication contact) | Noise immunity test in accordance with EN 61000-6-2 Transient overvoltage (surge) EN 61000-4-5/IEC 61000-4-5 Criterion B; DC supply lines: ±0.5 kV/±1 kV (symmetrical/asymmetrical), fieldbus cable shielding: ±1 kV |
| Permissible humidity (operation) (Dimensions) | 30 % ... 95 % (non-condensing) |
| Supports cloud computing (Ambient conditions) | yes |
| Detectable values (current strength) (General) | 100 A ... 40 kA |
| Number of connections (Typical characteristics) | 4 |
| Interference emission (Remote indication contact) | Noise immunity test in accordance with EN 61000-6-2 Noise emission EN 61000-6-3/IEC 61000-6-3 Class B |
| Ambient temperature (storage/transport) (Dimensions) | -35 °C ... 85 °C |
| Permissible humidity (storage/transport) (Dimensions) | 30 % ... 95 % (non-condensing) |
| Electromagnetic compatibility (Remote indication contact) | Conformance with EMC Directive 2014/30/EU |
| Immunity to conducted interference (Remote indication contact) | Noise immunity test in accordance with EN 61000-6-2 Conducted interference EN 61000-4-6/IEC 61000-4-6 Criterion A, Test voltage 10 V |
Technical specifications and performance data