| Parameter | Value |
|---|---|
| 2.5 kV (50 Hz, 1 min., test voltage) | |
| Color | gray (RAL 7042) |
| Depth | 113.2 mm |
| Width | 9.8 mm |
| Height | 75.2 mm |
| Altitude | 2000 m (max. altitude above sea level) |
| Certificate | Sira 17ATEX4208X |
| Designation | Electromagnetic RF field |
| Input signal | Current |
| Product type | Repeater power supply |
| Screw thread | M3 |
| HART function | Yes |
| Inductance Li | 0 mH |
| Output ripple | < 20 mVrms(at 600 Ω) |
| Capacitance Ci | 0 nF |
| Identification | II 3G Ex ec IIC T4 Gc |
| Product family | VIP I/O-Marshalling |
| Status display | Green LED (supply voltage) |
| No. of channels | 1 |
| Residual ripple | < 20 mVrms(600 Ω) |
| Article revision | 02 |
| Input current Ii | 100 mA (Controller interface) |
| Input voltage Ui | 0 V (nA, nB) |
| Stripping length | 10 mm |
| Connection method | Screw connection |
| Mounting position | any |
| Power consumption | ≤ 1600 mW (at IOUT= 20 mA, 24 V DC, 600 Ω load) |
| Output description | Current output (active and passive) |
| Degree of pollution | 2 |
| Protocols supported | HART |
| Current input signal | 4 mA ... 20 mA (repeater power supply and isolator operation) |
| Degree of protection | IP20 |
| Electrical isolation | Reinforced insulation in accordance with IEC 61010-1 |
| Max. output power Po | 726 mW |
| Overvoltage category | II |
| Supply voltage range | 18 V DC ... 30 V DC |
| Current output signal | 0 mA ... 20 mA (isolator amplifier) |
| Standards/regulations | EN 61000-4-3 |
| Transmission Behavior | 1:1 to input signal |
| Limit frequency (3 dB) | 1.75 kHz (typ.) |
| Max. output current Io | 104 mA |
| Max. output voltage Uo | 28 V (nA, nB) |
| Nominal supply voltage | 24 V DC |
| Step response (10-90%) | < 200 µs (typ.) |
| Max. current output signal | 22.5 mA |
| Maximum transmission error | < 0.1 % (of final value) |
| Transmitter supply voltage | > 17 V (20 mA) |
| Conductor cross section AWG | 24 ... 12 (flexible) |
| Conductor cross section rigid | 0.2 mm² ... 1.5 mm² (with ferrule) |
| Electromagnetic compatibility | Conformance with EMC directive |
| Ambient temperature (operation) | -40 °C ... 70 °C |
| Load/output load current output | ≤ 600 Ω (20 mA) |
| Maximum temperature coefficient | 0.01 %/K |
| Underload/overload signal range | 0 mA ... 22.5 mA (According to NE43) |
| Conductor cross section flexible | 0.2 mm² ... 1.5 mm² |
| Permissible humidity (operation) | 5 % ... 95 % |
| Temperature coefficient, typical | 0.01 %/K |
| Safety-related maximum voltage Um | 60 V AC/DC (Peak) |
| Flammability rating according to UL 94 | V0 |
| Ambient temperature (storage/transport) | -40 °C ... 85 °C |
| Output behavior in the event of an error | 0 mA (Cable break in the input) |
| Typical deviation from the measuring range final value | 1 % |
| IIA: Max. external inductivity Lo/ Max. external capacitance Co | / 6.6 µF |
| IIC: Max. external inductivity Lo/ Max. external capacitance Co | / 0.27 µF |
| IIB/IIIC/IIIB/IIIA: Max. external inductivity Lo/ Max. external capacitance Co | / 1.65 µF |
Technical specifications and performance data
Installation and operation guide