| Parameter | Value |
|---|---|
| GTIN | 4055626510941 |
| Note | Made to Order (non-returnable) |
| Orderkey | 2702971 |
| Packing unit | 1 pc |
| (Power supply) | 3 A (230 V (AC15)) |
| Country of origin | DE (Germany) |
| Net weight (Times) | 51.09 g |
| Relay type (Times) | Electromechanical relay with forcibly guided contacts in accordance with IEC/EN 61810-3 (EN 50205) |
| pluggable (General) | Yes |
| Custom tariff number | 85364900 |
| (Ambient conditions) | Polarity reversal protection for rated control circuit supply voltage and diagnostic supply voltage |
| Housing color (Times) | yellow |
| Mounting type (Times) | Plug-in mounting |
| Status display (Times) | 2 x LED bi-color (green, red) |
| Housing material (Times) | PA 6.6 |
| Mounting position (Times) | vertical or horizontal |
| Category (Connection data) | 4 |
| Output fuse (Power supply) | 3 A gL/gG |
| Output name (Power supply) | Enabling current path |
| Connection method (General) | Pluggable onto VIP base module |
| Contact type (Power supply) | 1 enabling current path |
| Depth (Key Commercial Data) | 112 mm |
| Width (Key Commercial Data) | 10 mm |
| (Standards and Regulations) | For details about hazardous substances go to tab “Downloads”, Category “Manufacturer's declaration” |
| Degree of protection (Times) | IP20 |
| Height (Key Commercial Data) | 75 mm |
| Assembly instructions (Times) | See derating curve |
| Designation (Connection data) | EN 50156-2 |
| Inrush current (Power supply) | min. 3 mA |
| Maximum altitude (Dimensions) | ≤ 2000 m (Above sea level) |
| Nominal operating mode (Times) | 100% operating factor |
| Contact material (Power supply) | AgSnO2 |
| Stop category (Connection data) | 0 |
| Filter time (Ambient conditions) | max. 3 ms (at pins 05/06 in the event of voltage dips at Us) |
| Number of outputs (Power supply) | 1 (undelayed) |
| Sq. Total current (Power supply) | 9 A2(observe derating) |
| Switching voltage (Power supply) | min. 12 V AC/DC |
| Output description (Power supply) | safety-related N/O contacts |
| Switching capacity (Power supply) | min. 60 mW |
| Inrush current (Ambient conditions) | typ. 100 mA (Δt s) |
| Weight per Piece (excluding packing) | 51.090 g |
| (Safety-related characteristic data) | Safe isolation, 6 kV reinforced insulation from the control circuit (05/06) and diagnostics circuit (03/04/02) to the enabling current path (15/19) |
| China RoHS (Standards and Regulations) | Environmentally Friendly Use Period = 50 |
| Mechanical service life (Power supply) | 10x 106cycles |
| (Relay outputs: enabling current path) | max. 100 mA |
| Protective circuit (Ambient conditions) | Surge protection 35 V suppressor diode (pins 05/06)33 V suppressor diode (pins 04/03)35 V suppressor diode (pins 02/03) |
| Input current at UD (Ambient conditions) | 7 mA (at pins 04/03 for UD; + 100 mA depending on load at pin 02) |
| Performance level (PL) (Connection data) | e |
| Inrush current at UD (Ambient conditions) | typ. 200 mA (Δt D) |
| Limiting continuous current (Power supply) | 3 A (observe derating) |
| Shock (Safety-related characteristic data) | 15 g (in the event of continuous stress caused by shock, contact reactions are possible.) |
| Ambient temperature (operation) (Dimensions) | -40 °C ... 70 °C (observe derating) |
| Power consumption at US (Ambient conditions) | typ. 0.77 W |
| Safety Integrity Level (SIL) (Connection data) | 3 (Reference IEC 61508) |
| Conformance (Safety-related characteristic data) | CE-compliant |
| Designation (Safety-related characteristic data) | Air clearances and creepage distances between the power circuits |
| Diagnostic supply voltage UD (Ambient conditions) | 24 V DC -20 % / +25 % (at pin 04) |
| Output fuse (Relay outputs: enabling current path) | 150 mA Fast-blow |
| Output name (Relay outputs: enabling current path) | Confirmation current path |
| Contact type (Relay outputs: enabling current path) | 1 confirmation current path |
| Min. degree of protection of inst. location (Times) | IP54 |
| Ambient temperature (storage/transport) (Dimensions) | -40 °C ... 85 °C |
| Rated control supply current IS (Ambient conditions) | typ. 25 mA |
| Inrush current (Relay outputs: enabling current path) | min. 1 mA |
| Contact material (Relay outputs: enabling current path) | AgCuNi, + Au |
| Degree of pollution (Safety-related characteristic data) | 2 |
| Number of outputs (Relay outputs: enabling current path) | 1 (undelayed) |
| Switching voltage (Relay outputs: enabling current path) | min. 19.2 V DC |
| Output description (Relay outputs: enabling current path) | Safety-related N/C contacts |
| Overvoltage category (Safety-related characteristic data) | III |
| Switching capacity (Relay outputs: enabling current path) | min. 20 mW |
| Max. permissible humidity (storage/transport) (Dimensions) | 75 % (on average, 85% infrequently, non-condensing) |
| Standards/regulations (Safety-related characteristic data) | DIN EN 50178, EN 60079-15 |
| Vibration (operation) (Safety-related characteristic data) | 10 Hz ...150 Hz, 2g |
| Max. permissible relative humidity (operation) (Dimensions) | 75 % (on average, 85% infrequently, non-condensing) |
| Rated control circuit supply voltage US (Ambient conditions) | 24 V DC -20 % / +25 % |
| Switching capacity according to IEC 60947-5-1 (Power supply) | 3 A (24 V (DC13)) |
| Rated insulation voltage (Safety-related characteristic data) | 250 V AC |
| Safety Integrity Level Claim Limit (SIL CL) (Connection data) | 3 |
| Limiting continuous current (Relay outputs: enabling current path) | 100 mA |
| Rated surge voltage/insulation (Safety-related characteristic data) | Basic insulation 4 kV between all current paths and housing |
| Recovery time (Relay outputs: return current/signaling current path) | 500 ms |
| Typical pickup time at US (Relay outputs: return current/signaling current path) | 150 ms (when controlled via pins 05/06) |
| Typical release time at US (Relay outputs: return current/signaling current path) | 30 ms (when controlled via pins 05/06) |
Technical specifications and performance data
Installation and operation guide