| Parameter | Value |
|---|---|
| max. 512 Bit (INTERBUS-Slave) | |
| Depth | 71.5 mm |
| Shock | 25g, Criterion 1, according to IEC 60068-2-27 |
| Width | 182 mm |
| Height | 140.5 mm |
| Weight | 440 g |
| Interface | INTERBUS local bus (master) |
| Input name | Digital inputs |
| Output name | Digital outputs |
| Update rate | min. 1 ms |
| Mass storage | 4 Mbyte |
| Specification | Version 1.1 |
| Program memory | typ. 2 Mbyte (170 K instructions (IL)) |
| Realtime clock | Integrated (battery backup) |
| Supply voltage | 24 V DC ±5 % |
| Device function | PROFINET-IO controller |
| Residual ripple | ± 5 % |
| Diagnostics tool | DIAG+ from version 1.14 |
| Number of inputs | 12 |
| Programming tool | PC WORX |
| Connection method | Inline data jumper |
| Number of outputs | 4 |
| Power dissipation | max. 6 W |
| Transmission speed | 500 kBaud / 2 MBaud (can be switched) |
| Diagnostics display | No |
| Degree of protection | IP20 |
| Supply voltage range | 20.4 V DC ... 30 V DC |
| Without analog input | yes |
| Controller redundancy | No |
| Vibration (operation) | 5g, accordance to IEC 60068-2-6 |
| Without analog output | yes |
| Without counter input | yes |
| Amount of process data | max. 8192 Bit (INTERBUS-Master) |
| Retentive mass storage | 96 kByte (NVRAM) |
| Number of control tasks | 16 |
| Air pressure (operation) | 70 kPa ... 106 kPa (up to 3000 m above sea level) |
| Description of the input | Eight fast inputs, interrupt input |
| Number of supported devices | max. 512 (in total, of which 254 are remote bus devices/bus segments) |
| Typical current consumption | 250 mA (no local bus device connected during idling, bus inactive) |
| Without pulse direction output | yes |
| Ambient temperature (operation) | -25 °C ... 55 °C |
| Air pressure (storage/transport) | 70 kPa ... 106 kPa (up to 3000 m above sea level) |
| Permissible humidity (operation) | 10 % ... 95 % (non-condensing) |
| Maximum output current per channel | 500 mA |
| Ambient temperature (storage/transport) | -25 °C ... 85 °C |
| Number of devices with parameter channel | max. 62 |
| Permissible humidity (storage/transport) | 10 % ... 95 % (non-condensing) |
| Number of local bus devices that can be connected | max. 63 (observe current consumption) |
| Number of supported branch terminals with remote bus branch | max. 15 |
Technical specifications and performance data