| Parameter | Value |
|---|---|
| BACnet MS/TP (only at COM1 and COM2) | |
| RAM | 1024 Mbyte DDR3 SDRAM |
| Type | modular |
| Color | green (RAL 6021) |
| Depth | 71.5 mm |
| Width | 80 mm |
| Height | 119.8 mm |
| Processor | Arm®Cortex®-A8 1 GHz |
| Bus system | RJ45 |
| Web server | yes |
| Product type | Controller |
| Mounting type | DIN rail mounting |
| Product family | Inline-Controller |
| Program memory | 1 GByte (SRAM) |
| Realtime clock | Yes |
| Supply voltage | 24 V DC |
| No. of channels | 2 |
| Safety function | no |
| Article revision | 06 |
| Engineering tool | Emalytics |
| Connection method | Spring-cage connection |
| Transmission speed | 10/100 Mbps |
| Data storage system | 1.8 GByte (eMMC) |
| Diagnostics display | no |
| Note on application | Only for industrial use |
| Supported protocols | BACnet/IP |
| Degree of protection | IP20 |
| Number of interfaces | 4 |
| Supply voltage range | 19.2 V DC ... 30 V DC |
| Controller redundancy | no |
| GRP_Temperature class | T4 |
| Retentive data storage | 2 GByte (eMMC) |
| Air pressure (operation) | 70 kPa ... 106 kPa (up to 3000 m above sea level) |
| Max. current consumption | ≤ 1.5 A |
| Description realtime clock | integrated (rechargeable battery buffered) |
| Conductor cross section AWG | 28 ... 16 |
| Typical current consumption | ≤ 170 mA (at nominal voltage without local bus device) |
| Conductor cross section, rigid | 0.08 mm² ... 1.5 mm² |
| Ambient temperature (operation) | -25 °C ... 55 °C (observe derating) |
| Programming languages supported | Niagara Framework® |
| Air pressure (storage/transport) | 70 hPa ... 106 kPa (up to 3000 m above sea level) |
| Permissible humidity (operation) | 0 % ... 75 % (according to DIN EN 61131-2) |
| Conductor cross section, flexible | 0.08 mm² ... 1.5 mm² |
| Ambient temperature (storage/transport) | -25 °C ... 85 °C |
| Permissible humidity (storage/transport) | 0 % ... 75 % (according to DIN EN 61131-2) |
| Resistance to gases that may endanger the functions, in acc. with DIN 40046-36, DIN 40046-37 | Sulfur dioxide (SO2) 10 ±0.3 ppm (test duration: 10 days), hydrogen sulfide (H2S) 1 ±0.3 ppm (test duration: 4 days), both at 25°C and with 75% humidity |
Technical specifications and performance data