| Parameter | Value |
|---|---|
| GTIN | 4046356712361 |
| Orderkey | 2701141 |
| Catalog page | Page 81 (C-6-2017) |
| Depth (Note) | 71.5 mm |
| Packing unit | 1 pc |
| Width (Note) | 80 mm |
| Height (Note) | 119.8 mm |
| (Control system) | PC WORX EXPRESS |
| Country of origin | DE (Germany) |
| Shock (Dimensions) | 25g, Criterion 1, according to IEC 60068-2-27 |
| Custom tariff number | 85371091 |
| Shock (General data) | 25g, Criterion 1, according to IEC 60068-2-27 |
| (Ambient conditions) | PC WORX EXPRESS |
| Input name (PROFINET) | Digital inputs |
| Weight (Power supply) | 285 g |
| Output name (PROFINET) | Digital outputs |
| Number (Fieldbus function) | 1 |
| (IEC 61131 runtime system) | max. 16384 Bit (internal Modbus /TCP client) |
| Number of inputs (PROFINET) | 8 |
| (Standards and Regulations) | For details about hazardous substances go to tab “Downloads”, Category “Manufacturer's declaration” |
| Connection method (PROFINET) | Spring-cage connection |
| Number of outputs (PROFINET) | 4 |
| Supply voltage (Direct I/Os) | 24 V DC |
| Immunity to EF (General data) | Noise immunity test in accordance with EN 61000-6-2 Electromagnetic fields EN 61000-4-3/IEC 61000-4-3 Criterion A, Field intensity: 10 V/m |
| Interface (Fieldbus function) | Parameterization/operation/diagnostics |
| Mass storage (Control system) | 256 kByte |
| Processor (Mechanical design) | Altera Nios II 64 MHz |
| Residual ripple (Direct I/Os) | ± 5 % |
| Immunity to ESD (General data) | Noise immunity test in accordance with EN 61000-6-2 Electrostatic discharge (ESD) EN 61000-4-2/IEC 61000-4-2 Criterion B, 6 kV contact discharge, 8 kV air discharge |
| Safety function (Power supply) | No |
| Power dissipation (Direct I/Os) | max. 5 W |
| Program memory (Control system) | 256 kByte |
| Realtime clock (Control system) | Yes |
| Connection technology (PROFINET) | 2, 3, 4-wire |
| Immunity to burst (General data) | Noise immunity test in accordance with EN 61000-6-2 Fast transients (burst) EN 61000-4-4/IEC 61000-4-4 Criterion A, all interfaces 1 kVCriterion B, all interfaces 2 kV |
| Immunity to surge (General data) | Noise immunity test in accordance with EN 61000-6-2 Transient overvoltage (surge) EN 61000-4-5/IEC 61000-4-5 Criterion B, supply lines DC: 0.5 kV/0.5 kV (symmetrical/asymmetrical), fieldbus cable shield 1 kV |
| Degree of protection (Dimensions) | IP20 |
| Device function (Data interfaces) | PROFINET device |
| Engineering tool (Control system) | PC WORX |
| Diagnostics display (Power supply) | No |
| Supply voltage range (Direct I/Os) | 19.2 V DC ... 30 V DC |
| Vibration (operation) (Dimensions) | 5g |
| Description of the input (PROFINET) | EN 61131-2 type 1 NPN/PNP |
| Controller redundancy (Power supply) | No |
| Interference emission (General data) | Noise emission test as per EN 61000-6-4 EN 55011 Class A |
| Vibration (operation) (General data) | 5g |
| Weight per Piece (excluding packing) | 345.300 g |
| Air pressure (operation) (Dimensions) | 70 kPa ... 106 kPa (up to 3000 m above sea level) |
| Connection method (Fieldbus function) | 6-pos. MINI DIN socket (PS/2) |
| Diagnostics tool (Ambient conditions) | DIAG+ |
| Engineering tool (Ambient conditions) | PC WORX |
| China RoHS (Standards and Regulations) | Environmentally Friendly Use Period = 50 |
| Max. current consumption (Direct I/Os) | 870 mA (370 mA communications power + 500 mA analog voltage supply) |
| Transmission speed (Fieldbus function) | max. 115.2 kbps |
| Configuration tool (Ambient conditions) | Config+ Version 1.01 or later |
| Retentive mass storage (Control system) | 8 kByte (NVRAM) |
| Number of control tasks (Control system) | 8 |
| Typical current consumption (Direct I/Os) | 210 mA |
| Ambient temperature (operation) (Dimensions) | -40 °C ... 60 °C |
| Electromagnetic compatibility (General data) | Conformance with EMC Directive 2014/30/EU |
| Vibration (storage/transport) (General data) | 5g |
| Air pressure (storage/transport) (Dimensions) | 70 kPa ... 106 kPa (up to 3000 m above sea level) |
| Maximum output current per channel (PROFINET) | 500 mA |
| Permissible humidity (operation) (Dimensions) | 10 % ... 95 % (according to DIN EN 61131-2) |
| Utilization restriction (Key Commercial Data) | EMC: class A product, see manufacturer's declaration in the download area |
| Amount of process data (IEC 61131 runtime system) | max. 4096 Bit (INTERBUS) |
| Immunity to conducted interference (General data) | Noise immunity test in accordance with EN 61000-6-2 Conducted interference EN 61000-4-6/IEC 61000-4-6 Criterion A; Test voltage 10 V |
| Ambient temperature (storage/transport) (Dimensions) | -40 °C ... 85 °C |
| Programming languages supported (Ambient conditions) | Programming in acc. with IEC 61131-3 |
| Permissible humidity (storage/transport) (Dimensions) | 10 % ... 95 % (according to DIN EN 61131-2) |
| Number of supported devices (IEC 61131 runtime system) | max. 128 |
| Number of devices with parameter channel (IEC 61131 runtime system) | max. 16 |
| Number of local bus devices that can be connected (IEC 61131 runtime system) | max. 63 (observe current consumption) |
| Number of supported branch terminals with remote bus branch (IEC 61131 runtime system) | max. 3 |
Technical specifications and performance data