| Parameter | Value |
|---|---|
| GTIN | 4046356495677 |
| Orderkey | 2700174 |
| Catalog page | Page 188 (C-6-2017) |
| Depth (Note) | 57 mm |
| Packing unit | 1 pc |
| Width (Note) | 156 mm |
| Height (Note) | 141 mm |
| (Analog outputs) | max. 950 mA |
| (Encoder inputs) | Shock in acc. with EN 60068-2-27/IEC 60068-2-27 25g |
| Country of origin | DE (Germany) |
| Custom tariff number | 85389091 |
| (Ambient conditions) | Undervoltage Power supply for sensors Message in the diagnostics register |
| Designation (General) | Sercos |
| Input name (Interfaces) | Digital inputs |
| No. of channels (General) | 2 |
| Note on dimensions (Note) | Specfications with connectors |
| Dimensional drawing (Note) | |
| Connection method (General) | RJ45 socket |
| (Standards and Regulations) | No hazardous substances above threshold values |
| Designation (Analog outputs) | Feed-in of the actuator supply UA2 |
| Output name (Digital inputs) | Digital outputs |
| Transmission speed (General) | 100 Mbps |
| Number of inputs (Interfaces) | 8 |
| Connection method (Interfaces) | Spring-cage connection |
| Input name (Inline potentials) | Encoder input, 2 square-wave signals with 90 degree offset |
| Transmission physics (General) | Copper |
| Net weight (Ambient conditions) | 405 g |
| Noise emission (Encoder inputs) | Industrial environment |
| Output voltage (Digital inputs) | 24 V DC |
| Supply voltage (Analog outputs) | 24 V DC |
| Type of protection (Interfaces) | Short-circuit protection, overload protection of the sensor supply |
| D/A resolution (Digital outputs) | 10 bit |
| Input voltage range (Interfaces) | -30 V DC ... 30 V DC |
| Degree of protection (Dimensions) | IP20 |
| Mechanical tests (Encoder inputs) | Vibration resistance in acc. with EN 60068-2-6/IEC 60068-2-6 5g |
| Connection method (Digital inputs) | Spring-cage connection |
| Connection technology (Interfaces) | 2, 3-wire |
| Mounting type (Ambient conditions) | NS 35/7,5 |
| Number of outputs (Digital inputs) | 4 |
| Power supply unit (Analog outputs) | max. 8 A |
| Input frequency (Inline potentials) | to 300 kHz |
| Nominal load, lamp (Digital inputs) | 12 W |
| Number of outputs (Digital outputs) | 2 |
| Type of protection (Digital inputs) | Short-circuit and overload protection |
| Current consumption (Analog outputs) | max. 2 A |
| Nominal load, ohmic (Digital inputs) | 12 W (48 Ω) |
| Number of inputs (Inline potentials) | 2 |
| Type of protection (Digital outputs) | Short-circuit/overload protection |
| Weight per Piece (excluding packing) | 405.000 g |
| Air pressure (operation) (Dimensions) | 80 kPa ... 108 kPa (up to 2000 m above sea level) |
| Supply voltage range (Analog outputs) | 19.2 V DC ... 30 V DC (including all tolerances, including ripple) |
| China RoHS (Standards and Regulations) | Environmentally friendly use period: unlimited = EFUP-e |
| Connection technology (Digital inputs) | 2-wire |
| Connection technology (Digital outputs) | 2-wire |
| Voltage output signal (Digital outputs) | -10 V ... 10 V |
| Nominal load, inductive (Digital inputs) | 12 VA (1.2 H, 50 Ω) |
| Diagnostics messages (Ambient conditions) | Short-circuit / overload of the digital outputs Message in the diagnostics register |
| Encoder supply current (Inline potentials) | 250 mA (Short-circuit and overload protection) |
| Encoder supply voltage (Inline potentials) | 24 V |
| Input voltage range "0" signal (Interfaces) | -30 V DC ... 5 V DC |
| Input voltage range "1" signal (Interfaces) | 15 V DC ... 30 V DC |
| Ambient temperature (operation) (Dimensions) | -25 °C ... 60 °C |
| Description of the input (Inline potentials) | Position detection with incremental signal from rotary/linear encoder |
| Air pressure (storage/transport) (Dimensions) | 66 kPa ... 108 kPa (up to 3500 m above sea level) |
| Permissible humidity (operation) (Dimensions) | max. 85 % (non-condensing) |
| Utilization restriction (Key Commercial Data) | 1 |
| Note on weight specifications (Ambient conditions) | with connectors |
| Maximum output current per channel (Digital inputs) | 500 mA |
| Ambient temperature (storage/transport) (Dimensions) | -25 °C ... 85 °C |
| Maximum output current per module / terminal block (Digital inputs) | 2 A |
Technical specifications and performance data
Installation and operation guide