| Parameter | Value |
|---|---|
| GTIN | 4017918929077 |
| Orderkey | 2862398 |
| Catalog page | Page 188 (C-6-2017) |
| Depth (Note) | 57 mm |
| Packing unit | 1 pc |
| Width (Note) | 156 mm |
| Height (Note) | 141 mm |
| Caption (Note) | The figure shows the general dimensional drawing of the Inline Block IO product family |
| (Digital inputs) | PROFIBUS / FE 500 V AC 50 Hz 1 min. |
| Country of origin | DE (Germany) |
| Custom tariff number | 85389091 |
| Designation (General) | PROFIBUS DP |
| (Electrical isolation) | Shock in acc. with EN 60068-2-27/IEC 60068-2-27 25g |
| Input name (Interfaces) | Digital inputs |
| Note on dimensions (Note) | Specfications with connectors |
| Dimensional drawing (Note) | |
| Input voltage (Interfaces) | 24 V DC |
| Connection method (General) | D-SUB-9 female connector |
| (Standards and Regulations) | No hazardous substances above threshold values |
| Transmission speed (General) | 9.6 kbps ... 12 Mbps |
| Number of inputs (Interfaces) | 32 |
| Number of positions (General) | 9 |
| Test section (Digital inputs) | I/Os / PROFIBUS 500 V AC 50 Hz 1 min. |
| Connection method (Interfaces) | Spring-cage connection |
| Net weight (Ambient conditions) | 510 g |
| Type of protection (Interfaces) | Short-circuit protection, overload protection of the sensor supply |
| Degree of protection (Dimensions) | IP20 |
| Connection technology (Interfaces) | 3-wire |
| Mounting type (Ambient conditions) | NS 35/7,5 |
| Typical response time (Interfaces) | approx. 500 µs |
| Weight per Piece (excluding packing) | 510.000 g |
| Air pressure (operation) (Dimensions) | 80 kPa ... 108 kPa (up to 2000 m above sea level) |
| Description of the input (Interfaces) | EN 61131-2 type 1 |
| Noise emission (Electrical isolation) | Industrial environment |
| China RoHS (Standards and Regulations) | Environmentally friendly use period: unlimited = EFUP-e |
| Mechanical tests (Electrical isolation) | Vibration resistance in acc. with EN 60068-2-6/IEC 60068-2-6 5g |
| Nominal input current at UIN (Interfaces) | 5 mA |
| Input voltage range "0" signal (Interfaces) | -30 V DC ... 5 V DC |
| Input voltage range "1" signal (Interfaces) | 15 V DC ... 30 V DC |
| Ambient temperature (operation) (Dimensions) | -25 °C ... 60 °C |
| Air pressure (storage/transport) (Dimensions) | 66 kPa ... 108 kPa (up to 3500 m above sea level) |
| Permissible humidity (operation) (Dimensions) | 85 % (non-condensing) |
| Utilization restriction (Key Commercial Data) | 1 |
| Note on weight specifications (Ambient conditions) | with connectors |
| Ambient temperature (storage/transport) (Dimensions) | -25 °C ... 85 °C |
| Permissible humidity (storage/transport) (Dimensions) | 95 % (non-condensing) |
| Connection in acc. with standard (Electrical isolation) | CUL |