| Parameter | Value |
|---|---|
| GTIN | 4055626346137 |
| Orderkey | 2403696 |
| (Drawings) | |
| Catalog page | Page 104 (C-6-2019) |
| Depth (Note) | 71.5 mm |
| Packing unit | 1 |
| Width (Note) | 40 mm |
| (Interfaces) | max. 1012 Byte (Output) |
| Height (Note) | 119.4 mm |
| ETIM 5.0 (eCl@ss) | EC001604 |
| ETIM 6.0 (eCl@ss) | EC001604 |
| ETIM 7.0 (eCl@ss) | EC001604 |
| (Inline potentials) | Shock in acc. with EN 60068-2-27/IEC 60068-2-27 Operation: 25g, 11 ms duration, semi-sinusoidal shock impulse |
| Custom tariff number | 85176200 |
| (Ambient conditions) | Failure of the actuator supply Yes |
| Designation (General) | Inline local bus |
| No. of channels (General) | 2 |
| Note on dimensions (Note) | Housing dimensions |
| Color (Ambient conditions) | green |
| Dimensional drawing (Note) | |
| Connection method (General) | Inline data jumper |
| (Standards and Regulations) | For details about hazardous substances go to tab “Downloads”, Category “Manufacturer's declaration” |
| Transmission speed (General) | 500 kbps / 2 Mbps (automatic detection, no combined system) |
| eCl@ss 6.0 (Classifications) | 27242600 |
| eCl@ss 7.0 (Classifications) | 27242608 |
| eCl@ss 8.0 (Classifications) | 27242608 |
| eCl@ss 9.0 (Classifications) | 27242608 |
| Connection diagram (Drawings) | |
| Transmission physics (General) | Ethernet in RJ45 twisted pair |
| Net weight (Ambient conditions) | 168.5 g |
| Degree of protection (Dimensions) | IP20 |
| Mounting type (Ambient conditions) | DIN rail mounting |
| Utilization restriction (Drawings) | EMC: class A product, see manufacturer's declaration in the download area |
| (System limits of the bus coupler) | max. 0.91 A DC (from UBK) |
| Amount of process data (Interfaces) | max. 2024 Byte (max. 1012 Byte IN - max. 1012 Byte OUT) |
| Mechanical tests (Inline potentials) | Vibration resistance in acc. with EN 60068-2-6/IEC 60068-2-6 5g |
| Protection class (Inline potentials) | III (IEC 61140, EN 61140, VDE 0140-1) |
| Air pressure (operation) (Dimensions) | 70 kPa ... 106 kPa (up to 3000 m above sea level) |
| (Power supply for module electronics) | max. 0.91 A DC |
| China RoHS (Standards and Regulations) | Environmentally Friendly Use Period = 50 |
| REACh SVHC (Standards and Regulations) | |
| Number of supported devices (Interfaces) | max. 63 (per station) |
| Diagnostics messages (Ambient conditions) | Short-circuit / overload of the digital outputs Yes |
| Ambient temperature (operation) (Dimensions) | -25 °C ... 55 °C (observe derating) |
| Air pressure (storage/transport) (Dimensions) | 70 kPa ... 106 kPa (up to 3000 m above sea level) |
| Permissible humidity (operation) (Dimensions) | 10 % ... 95 % (according to DIN EN 61131-2) |
| Designation (System limits of the bus coupler) | Bus coupler supply UBC; Communications power UL(7.5 V) and the analog supply UANA(24 V) are generated from the bus coupler supply. |
| Designation (Power supply for module electronics) | Segment circuit supply (US) |
| Supply voltage (System limits of the bus coupler) | 24 V DC (via Inline connector) |
| Note on weight specifications (Ambient conditions) | with connectors |
| Ambient temperature (storage/transport) (Dimensions) | -40 °C ... 85 °C |
| Connection method (System limits of the bus coupler) | Spring-cage connection |
| Power dissipation (System limits of the bus coupler) | typ. 3 W (entire device) |
| Supply voltage (Power supply for module electronics) | 24 V DC |
| Number of devices with parameter channel (Interfaces) | max. 16 |
| Permissible humidity (storage/transport) (Dimensions) | 10 % ... 95 % (according to DIN EN 61131-2) |
| Current consumption (System limits of the bus coupler) | typ. 138 mA (from UBK) |
| Power consumption (Power supply for module electronics) | typ. 3 W (entire device) |
| Power supply unit (Power supply for module electronics) | max. 8 A DC (sum of UM+ US) |
| Supply voltage range (System limits of the bus coupler) | 19.2 V DC ... 30 V DC (including all tolerances, including ripple) |
| Current consumption (Power supply for module electronics) | typ. 51 mA (No local bus devices connected) |
| Supply voltage range (Power supply for module electronics) | 19.2 V DC ... 30 V DC (including all tolerances, including ripple) |
| Number of local bus devices that can be connected (Interfaces) | max. 63 |
| Number of supported branch terminals with remote bus branch (Interfaces) | 4 |