| Parameter | Value |
|---|---|
| GTIN | 4046356041164 |
| Orderkey | 2703994 |
| Catalog page | Page 128 (C-6-2017) |
| Depth (Note) | 71.5 mm |
| Packing unit | 1 pc |
| Width (Note) | 80 mm |
| (Interfaces) | max. 244 Byte (Output) |
| Height (Note) | 119.8 mm |
| Country of origin | DE (Germany) |
| (Digital outputs) | Shock in acc. with EN 60068-2-27/IEC 60068-2-27 Operation: 25g, 11 ms duration, semi-sinusoidal shock impulse |
| Custom tariff number | 85176200 |
| (Ambient conditions) | Failure of the actuator supply Yes |
| Designation (General) | Inline local bus |
| No. of channels (General) | 2 |
| Note on dimensions (Note) | Specfications with connectors |
| Dimensional drawing (Note) | |
| Connection method (General) | Inline data jumper |
| (Standards and Regulations) | No hazardous substances above threshold values |
| Output name (Digital inputs) | Digital outputs |
| Transmission speed (General) | 500 kbps / 2 Mbps (automatic detection, no combined system) |
| Input name (Inline potentials) | Digital inputs |
| Transmission physics (General) | Ethernet in RJ45 twisted pair |
| Filter time (Inline potentials) | 3 ms |
| Net weight (Ambient conditions) | 335.7 g |
| Output voltage (Digital inputs) | 24 V DC -1 V (At nominal current) |
| Degree of protection (Dimensions) | IP20 |
| Input voltage (Inline potentials) | 24 V DC |
| Connection method (Digital inputs) | Inline connector |
| Mechanical tests (Digital outputs) | Vibration resistance in acc. with EN 60068-2-6/IEC 60068-2-6 5g |
| Mounting type (Ambient conditions) | DIN rail mounting |
| Number of outputs (Digital inputs) | 4 |
| Protection class (Digital outputs) | III, IEC 61140, EN 61140, VDE 0140-1 |
| (System limits of the bus coupler) | max. 0.91 A DC (from UBK) |
| Amount of process data (Interfaces) | max. 488 Byte (max. 244 bytes IN - max. 244 bytes OUT) |
| Nominal load, lamp (Digital inputs) | 12 W |
| Type of protection (Digital inputs) | Short-circuit and overload protection |
| Nominal load, ohmic (Digital inputs) | 12 W |
| Number of inputs (Inline potentials) | 8 |
| Weight per Piece (excluding packing) | 335.700 g |
| Air pressure (operation) (Dimensions) | 70 kPa ... 106 kPa (up to 3000 m above sea level) |
| Connection method (Inline potentials) | Inline connector |
| (Power supply for module electronics) | max. 8 A DC |
| China RoHS (Standards and Regulations) | Environmentally friendly use period: unlimited = EFUP-e |
| Connection technology (Digital inputs) | 2, 3-wire |
| Type of protection (Inline potentials) | Reverse polarity protection |
| Nominal output voltage (Digital inputs) | 24 V DC |
| Nominal load, inductive (Digital inputs) | 12 VA (1.2 H, 48 Ω) |
| Number of supported devices (Interfaces) | max. 63 (per station) |
| Connection technology (Inline potentials) | 2, 3-wire |
| Diagnostics messages (Ambient conditions) | Short-circuit / overload of the digital outputs Yes |
| Typical response time (Inline potentials) | approx. 500 µs |
| Ambient temperature (operation) (Dimensions) | -25 °C ... 55 °C (observe derating) |
| Description of the input (Inline potentials) | EN 61131-2 type 1 |
| Air pressure (storage/transport) (Dimensions) | 70 kPa ... 106 kPa (up to 3000 m above sea level) |
| Permissible humidity (operation) (Dimensions) | 10 % ... 95 % (according to DIN EN 61131-2) |
| Utilization restriction (Key Commercial Data) | EMC: class A product, see manufacturer's declaration in the download area |
| Designation (System limits of the bus coupler) | Bus coupler supply UBC; Communications power UL(7.5 V) and the analog supply UANA(24 V) are generated from the bus coupler supply. |
| Nominal input current at UIN (Inline potentials) | typ. 3 mA |
| Designation (Power supply for module electronics) | Segment circuit supply (US) |
| Supply current (System limits of the bus coupler) | 138 mA |
| Supply voltage (System limits of the bus coupler) | 24 V DC (via Inline connector) |
| Input voltage range "0" signal (Inline potentials) | -30 V DC ... 5 V DC |
| Input voltage range "1" signal (Inline potentials) | 15 V DC ... 30 V DC |
| Maximum output current per module (Digital inputs) | 2 A |
| Note on weight specifications (Ambient conditions) | with connectors |
| Maximum output current per channel (Digital inputs) | 500 mA |
| Ambient temperature (storage/transport) (Dimensions) | -40 °C ... 85 °C |
| Connection method (System limits of the bus coupler) | Spring-cage connection |
| Power dissipation (System limits of the bus coupler) | typ. 3 W (entire device) |
| Supply voltage (Power supply for module electronics) | 24 V DC |
| Number of devices with parameter channel (Interfaces) | max. 16 |
| Permissible humidity (storage/transport) (Dimensions) | 10 % ... 95 % (according to DIN EN 61131-2) |
| Typical input current per channel (Inline potentials) | typ. 3 mA |
| Current consumption (System limits of the bus coupler) | typ. 138 mA (from UBK) |
| Delay at signal change from 0 to 1 (Inline potentials) | 5 ms |
| Delay at signal change from 1 to 0 (Inline potentials) | 5 ms |
| Power consumption (Power supply for module electronics) | typ. 3 W (entire device) |
| Power supply unit (Power supply for module electronics) | max. 8 A DC (Sum of UM+ US; 4 A, maximum, when used in potentially explosive areas.) |
| Supply voltage range (System limits of the bus coupler) | 19.2 V DC ... 30 V DC (including all tolerances, including ripple) |
| Current consumption (Power supply for module electronics) | 3 mA (without actuators) |
| Supply voltage range (Power supply for module electronics) | 19.2 V DC ... 30 V DC (including all tolerances, including ripple) |
| Number of local bus devices that can be connected (Interfaces) | max. 61 (on board I/Os are two devices) |
| Maximum output current per module / terminal block (Digital inputs) | 2 A |
| Number of supported branch terminals with remote bus branch (Interfaces) | 0 |
Technical specifications and performance data
Installation and operation guide