| Parameter | Value |
|---|---|
| Sensor supply failure yes | |
| Type | modular |
| Depth | 71.5 mm |
| Width | 80 mm |
| Height | 119.8 mm |
| Input name | Digital inputs |
| Output name | Digital outputs |
| Current draw | max. 0.98 A (with max. number of connected I/O terminal blocks) |
| Product type | I/O component |
| Signal delay | typ. 1.2 ms |
| ID code (hex) | none |
| Input voltage | 24 V DC |
| Mounting type | DIN rail mounting |
| Output voltage | 24 V DC -1 V (At nominal current) |
| Product family | Inline |
| Supply voltage | 24 V DC (via Inline connector) |
| Connection name | Inline connector |
| No. of channels | 12 |
| Register length | 16 bit |
| Article revision | 05 |
| Number of inputs | 8 |
| Protection class | III (IEC 61140, EN 61140, VDE 0140-1) |
| Stripping length | 8 mm |
| Connection method | RJ45 jack |
| Number of outputs | 4 |
| Scope of delivery | including Inline connectors and marking fields |
| Input address area | 8 bit |
| Nominal load, lamp | 12 W |
| Note on dimensions | Specfications with connectors |
| Protective circuit | Reverse polarity protection; Suppressor diode |
| Special properties | Extreme conditions version |
| Transmission speed | 10/100 Mbps |
| Dimensional drawing | |
| Nominal load, ohmic | 12 W |
| Note on application | Only for industrial use |
| Output address area | 4 bit |
| Degree of protection | IP20 |
| Diagnostics messages | Short-circuit or overload of the digital outputs yes |
| Number of interfaces | 2 |
| Supply voltage range | 19.2 V DC ... 30 V DC (including all tolerances, including ripple) |
| Transmission physics | Ethernet in RJ45 twisted pair |
| Connection technology | 3-conductor |
| Overcurrent shut-down | min. 0.7 A |
| Typical response time | approx. 500 µs |
| Behavior with overload | Auto restart |
| Nominal output voltage | 24 V DC |
| Nominal load, inductive | 12 VA (1.2 H, 48 Ω) |
| Air pressure (operation) | 70 kPa ... 106 kPa (up to 3000 m above sea level) |
| Description of the input | EN 61131-2 type 1 |
| Nominal input voltage UIN | 24 V DC |
| Conductor cross section AWG | 28 ... 16 |
| Number of supported devices | max. 63 (per station) |
| Nominal input current at UIN | typ. 3 mA |
| Conductor cross section rigid | 0.08 mm² ... 1.5 mm² |
| Note on the connection method | Auto negotiation and autocrossing |
| Behavior at voltage switch-off | The output follows the power supply without delay |
| Conductor cross section, rigid | 0.08 mm² ... 1.5 mm² |
| Input voltage range "0" signal | -30 V DC ... 5 V DC |
| Input voltage range "1" signal | 15 V DC ... 30 V DC |
| Ambient temperature (operation) | -25 °C ... 55 °C (Standard) |
| Air pressure (storage/transport) | 70 kPa ... 106 kPa (up to 3000 m above sea level) |
| Behavior with inductive overload | Output can be destroyed |
| Conductor cross section flexible | 0.08 mm² ... 1.5 mm² |
| Max. number of local bus devices | 61 (The on-board I/Os are two devices) |
| Output current when switched off | max. 10 µA (When not loaded, a voltage can be measured even at an output that is not set.) |
| Permissible humidity (operation) | 10 % ... 95 % (non-condensing) |
| Conductor cross section, flexible | 0.08 mm² ... 1.5 mm² |
| Maximum output current per module | max. 2 A |
| Typical input current per channel | typ. 3 mA |
| Delay at signal change from 0 to 1 | 1.2 ms |
| Delay at signal change from 1 to 0 | 1.2 ms |
| Ambient temperature (storage/transport) | -40 °C ... 85 °C |
| Number of devices with parameter channel | max. 16 |
| Permissible humidity (storage/transport) | 10 % ... 95 % (non-condensing) |
| Reverse voltage resistance to short pulses | Reverse voltage proof |
| Maximum power dissipation for nominal condition | 6.3 W |
| Number of local bus devices that can be connected | max. 61 (The on-board I/Os are two devices) |
| Number of supported branch terminals with remote bus branch | 0 |