| Parameter | Value |
|---|---|
| Type | modular |
| Depth | 71.5 mm |
| Width | 12.2 mm |
| Height | 135 mm |
| Current draw | typ. 29 mA |
| Product type | I/O component |
| ID code (hex) | 04 |
| Mounting type | DIN rail mounting |
| ID code (dec.) | 04 |
| Product family | Inline |
| Supply voltage | 24 V DC (via voltage jumper) |
| Connection name | Inline connector |
| Register length | 0 bit |
| Article revision | 07 |
| Protection class | III (IEC 61140, EN 61140, VDE 0140-1) |
| Stripping length | 8 mm |
| Connection method | Inline data jumper |
| Length code (dec) | 0 |
| Length code (hex) | 0 |
| Scope of delivery | including Inline connector and labeling field |
| Input address area | 0 Byte |
| Special properties | with remote bus branch |
| Transmission speed | 2 Mbps |
| Dimensional drawing | |
| Note on application | Only for industrial use |
| Output address area | 0 Byte |
| Degree of protection | IP20 |
| Process data channel | 0 bit |
| Supply voltage range | 19.2 V DC ... 30 V DC (including all tolerances, including ripple) |
| Transmission physics | RS-485 |
| Required parameter data | 0 Byte |
| Air pressure (operation) | 70 kPa ... 106 kPa (up to 3000 m above sea level) |
| Conductor cross section AWG | 28 ... 16 |
| Required configuration data | 0 Byte |
| Conductor cross section rigid | 0.08 mm² ... 1.5 mm² |
| Conductor cross section, rigid | 0.08 mm² ... 1.5 mm² |
| Ambient temperature (operation) | -25 °C ... 55 °C |
| Air pressure (storage/transport) | 70 kPa ... 106 kPa (up to 3000 m above sea level) |
| Conductor cross section flexible | 0.08 mm² ... 1.5 mm² |
| Permissible humidity (operation) | 10 % ... 95 % (according to DIN EN 61131-2) |
| Conductor cross section, flexible | 0.08 mm² ... 1.5 mm² |
| Ambient temperature (storage/transport) | -25 °C ... 85 °C |
| Permissible humidity (storage/transport) | 10 % ... 95 % (according to DIN EN 61131-2) |
| Maximum power dissipation for nominal condition | 0.7 W |
| Number of local bus devices that can be connected | max. 63 (Consider the logic current consumed by the devices; the branch terminal does not count as an Inline station device.) |
| Test voltage: 5 V supply incoming remote bus / functional ground | 500 V AC, 50 Hz, 1 min. |
| Test voltage: 5 V supply outgoing remote bus, electrically isolated from functional ground | 500 V AC, 50 Hz, 1 min. |
| Test voltage: 24 V main supply, 24 V segment supply, electrically isolated from the functional ground | 500 V AC, 50 Hz, 1 min. |
| Test voltage: 5 V supply, incoming remote bus, electrically isolated from 5 V supply, outgoing remote bus | 500 V AC, 50 Hz, 1 min. |
| Test voltage: 5 V supply, outgoing remote bus, electrically isolated from 5 V supply, incoming remote bus | 500 V AC, 50 Hz, 1 min. |
| Test voltage: 24 V main supply, 24 V segment supply, electrically isolated from 5 V supply, incoming remote bus | 500 V AC, 50 Hz, 1 min. |
| Test voltage: 24 V main supply, 24 V segment supply, electrically isolated from 5 V supply, outgoing remote bus | 500 V AC, 50 Hz, 1 min. |
| Test voltage: 5 V supply, incoming remote bus, electrically isolated from 24 V main supply, 24 V segment supply | 500 V AC, 50 Hz, 1 min. |
| Test voltage: 5 V supply, outgoing remote bus, electrically isolated from 24 V main supply, 24 V segment supply | 500 V AC, 50 Hz, 1 min. |
| Test voltage: 7.5 V logics supply, 24 V analog supply, 24 V bus terminal module supply, 5 V logics supply branch terminal block, electrically isolated from 5 V supply incoming remote bus | 500 V AC, 50 Hz, 1 min. |
| Test voltage: 7.5 V logics supply, 24 V analog supply, 24 V bus terminal module supply, 5 V logics supply branch terminal block, electrically isolated from 5 V supply outgoing remote bus | 500 V AC, 50 Hz, 1 min. |
| Test voltage: 5 V supply, incoming remote bus, electrically isolated from 7.5 V logics supply, 24 V analog supply, 24 V bus terminal module supply, 5 V logics supply branch terminal block | 500 V AC, 50 Hz, 1 min. |
| Test voltage: 5 V supply, outgoing remote bus, electrically isolated from 7.5 V logics supply, 24 V analog supply, 24 V bus terminal module supply, 5 V logics supply branch terminal block | 500 V AC, 50 Hz, 1 min. |
| Test voltage: 7.5 V communications power, 24 V analog supply, 24 V bus terminal module supply, 5 V communications power, bus branch terminal electrically isolated from functional ground | 500 V AC, 50 Hz, 1 min. |
| Test voltage: 24 V main supply, 24 V segment supply, electrically isolated from 7.5 V logics supply, 24 V analog supply, 24 V bus terminal module supply, 5 V logics supply branch terminal block | 500 V AC, 50 Hz, 1 min. |
| Test voltage: 7.5 V logics supply, 24 V analog supply, 24 V bus terminal module supply, 5 V logics supply branch terminal block, electrically isolated from 24 V main supply, 24 V segment supply | 500 V AC, 50 Hz, 1 min. |
Technical specifications and performance data