

| Parameter | Value |
|---|---|
| GTIN | 4017918894160 |
| Orderkey | 2861218 |
| Catalog page | Page 246 (AX-2009) |
| Depth (Note) | 71.5 mm |
| Packing unit | 1 pc |
| Width (Note) | 85 mm |
| Height (Note) | 119.8 mm |
| Country of origin | DE (Germany) |
| Custom tariff number | 85389091 |
| Designation (General) | Inline local bus |
| No. of channels (General) | 2 |
| Dimensional drawing (Note) | |
| Connection method (General) | Inline data jumper |
| (Standards and Regulations) | No hazardous substances above threshold values |
| Transmission speed (General) | 500 kbps |
| Transmission physics (General) | FO |
| Net weight (Ambient conditions) | 220 g |
| Test section (Inline potentials) | 7.5 V communications power, 24 V analog supply, 24 V bus coupler supply/functional earth ground 500 V AC 50 Hz 1 min. |
| Degree of protection (Dimensions) | IP20 |
| Mounting type (Ambient conditions) | DIN rail |
| (System limits of the bus coupler) | Polarity reversal protection of the supply voltage |
| Weight per Piece (excluding packing) | 220.000 g |
| Air pressure (operation) (Dimensions) | 70 kPa ... 106 kPa (up to 3000 m above sea level) |
| China RoHS (Standards and Regulations) | Environmentally friendly use period: unlimited = EFUP-e |
| REACh SVHC (Standards and Regulations) | Lead 7439-92-1 |
| Protection class (Electrical isolation) | III, IEC 61140, EN 61140, VDE 0140-1 |
| Ambient temperature (operation) (Dimensions) | -25 °C ... 55 °C |
| Air pressure (storage/transport) (Dimensions) | 70 kPa ... 106 kPa (up to 3000 m above sea level) |
| Permissible humidity (operation) (Dimensions) | 10 % ... 95 % (non-condensing) |
| Utilization restriction (Key Commercial Data) | 1 |
| Designation (System limits of the bus coupler) | Service Entrance |
| Supply voltage (System limits of the bus coupler) | 24 V DC |
| Note on weight specifications (Ambient conditions) | with connector |
| Ambient temperature (storage/transport) (Dimensions) | -25 °C ... 85 °C |
| Power supply unit (System limits of the bus coupler) | max. 0.5 A DC |
| Number of devices with parameter channel (Interfaces) | max. 62 |
| Permissible humidity (storage/transport) (Dimensions) | 10 % ... 95 % (non-condensing) |
| Type of protection (System limits of the bus coupler) | Surge protection of the supply voltage |
| Current consumption (System limits of the bus coupler) | typ. 90 mA (without connected Inline I/O terminals) |
| Connection in acc. with standard (Electrical isolation) | CUL |
| Supply voltage range (System limits of the bus coupler) | 19.2 V DC ... 30 V DC (including all tolerances, including ripple) |
| Number of local bus devices that can be connected (Interfaces) | max. 63 |
| Number of supported branch terminals with remote bus branch (Interfaces) | max. 15 |
Technical specifications and performance data
Installation and operation guide