| Parameter | Value |
|---|---|
| 2, 3-wire | |
| Depth | 71.5 mm |
| Width | 146.4 mm |
| Height | 140.5 mm |
| Input name | Digital inputs |
| Net weight | 394 g |
| Designation | INTERBUS |
| Output name | Digital outputs |
| Input voltage | 24 V DC |
| Mounting type | DIN rail |
| Output voltage | 24 V DC -1 V (At nominal current) |
| Supply voltage | 24 V DC (via Inline connector) |
| Fieldbus system | INTERBUS |
| Number of inputs | max. 16 (EN 61131-2 type 1) |
| Connection method | 2x 6-pos. Inline shield connectors |
| Number of outputs | 16 |
| Nominal load, lamp | 12 W |
| Power supply at UL | max. 2 A DC |
| Power supply at UM | max. 8 A DC (Sum of UM+ US) |
| Power supply at US | max. 8 A DC (Sum of UM+ US) |
| Protective circuit | Polarity reversal Suppressor diode |
| Transmission speed | 500 kBit/s |
| Current consumption | max. 1.25 A (with max. number of connected I/O terminal blocks (24 V DC supply)) |
| Nominal load, ohmic | 12 W |
| Degree of protection | IP20 |
| Power supply at UANA | max. 0.5 A DC (observe derating) |
| Supply voltage range | 19.2 V DC ... 30 V DC (including ripple) |
| Main circuit supply UM | 24 V DC -15 % / +20 % (acc. to EN 61131-2) |
| Nominal output voltage | 24 V DC |
| Communications power UL | 7.5 V DC ±5 % |
| I/O supply voltage UANA | 24 V DC -15 % / +20 % |
| Nominal load, inductive | 12 VA |
| Air pressure (operation) | 80 kPa ... 106 kPa (up to 3000 m above sea level) |
| Segment supply voltage US | 24 V DC -15 % / +20 % (acc. to EN 61131-2) |
| Note on weight specifications | with connectors |
| Input voltage range "1" signal | 15 V DC ... 30 V DC |
| Ambient temperature (operation) | -25 °C ... 55 °C |
| Air pressure (storage/transport) | 70 kPa ... 106 kPa (up to 3000 m above sea level) |
| Permissible humidity (operation) | 95 % (non-condensing) |
| Maximum output current per module | 8 A |
| Typical input current per channel | typ. 3 mA |
| Maximum output current per channel | 500 mA |
| Number of devices with parameter channel | 16 |
| Permissible humidity (storage/transport) | 95 % (non-condensing) |
| Number of local bus devices that can be connected | 63 (observe total permissible current consumption) |
| Number of supported branch terminals with remote bus branch | max. 15 |
Technical specifications and performance data