| Parameter | Value |
|---|---|
| GTIN | 4046356288026 |
| Orderkey | 2897402 |
| Catalog page | Page 165 (C-6-2017) |
| Depth (Note) | 71.5 mm |
| Packing unit | 1 pc |
| Width (Note) | 48.8 mm |
| (Interfaces) | max. 15 mA |
| Height (Note) | 119.8 mm |
| (Analog inputs) | I/O / functional earth ground 500 V AC 50 Hz 1 min. |
| Country of origin | DE (Germany) |
| (Inline potentials) | 0 Ω ... 30 kΩ |
| Custom tariff number | 85389091 |
| (Ambient conditions) | User error Error message in the process data |
| Designation (General) | Inline local bus |
| Designation (Interfaces) | Supply of analog modules (UANA) |
| No. of channels (General) | 2 |
| Note on dimensions (Note) | Housing dimensions |
| Dimensional drawing (Note) | |
| Connection method (General) | Inline data jumper |
| Supply voltage (Interfaces) | 24 V DC (via voltage jumper) |
| (Standards and Regulations) | No hazardous substances above threshold values |
| Test section (Analog inputs) | 7.5 V supply (bus logic), 24 V supply UANA/ I/O 500 V AC 50 Hz 1 min. |
| Transmission speed (General) | 500 kbps |
| Input name (Inline potentials) | Analog RTD inputs |
| Power consumption (Interfaces) | typ. 0.85 W (entire device) |
| Transmission physics (General) | Copper |
| Net weight (Ambient conditions) | 221.6 g |
| Current consumption (Interfaces) | typ. 6 mA |
| Data formats (Inline potentials) | IB IL, S7-compatible |
| Degree of protection (Dimensions) | IP20 |
| Supply voltage range (Interfaces) | 19.2 V DC ... 30 V DC (including all tolerances, including ripple) |
| Mounting type (Ambient conditions) | DIN rail |
| Resolution A/D (Inline potentials) | 24 bit |
| Operating mode (Ambient conditions) | Process data mode with 5 words/1 word PCP |
| Number of inputs (Inline potentials) | 8 (for resistance temperature detectors) |
| Weight per Piece (excluding packing) | 221.600 g |
| Air pressure (operation) (Dimensions) | 70 kPa ... 106 kPa (up to 3000 m above sea level) |
| Connection method (Inline potentials) | Spring-cage connection |
| Input filter time (Inline potentials) | 100 ms |
| China RoHS (Standards and Regulations) | Environmentally friendly use period: unlimited = EFUP-e |
| Measuring principle (Inline potentials) | Sigma/Delta process |
| Process data update (Inline potentials) | 1.8 s (Up to 3.3 s possible depending on operating mode) |
| Protection class (Electrical isolation) | III, IEC 61140, EN 61140, VDE 0140-1 |
| Connection technology (Inline potentials) | 4-wire |
| Diagnostics messages (Ambient conditions) | Failure of the internal I/O supply I/O error message sent to the bus coupler |
| Ambient temperature (operation) (Dimensions) | -25 °C ... 60 °C |
| Description of the input (Inline potentials) | Input for resistive temperature sensors |
| Air pressure (storage/transport) (Dimensions) | 70 kPa ... 106 kPa (up to 3000 m above sea level) |
| Permissible humidity (operation) (Dimensions) | 10 % ... 95 % (non-condensing) |
| Utilization restriction (Key Commercial Data) | 1 |
| Measured value representation (Inline potentials) | 16 bits (15 bits + sign bit) |
| Note on weight specifications (Ambient conditions) | with connectors |
| Ambient temperature (storage/transport) (Dimensions) | -25 °C ... 85 °C |
| Linear resistance measuring range (Inline potentials) | 0 Ω ... 500 Ω |
| Permissible humidity (storage/transport) (Dimensions) | 10 % ... 95 % (non-condensing) |
| Sensor types (RTD) that can be used (Inline potentials) | Pt, Ni, KTY, Cu sensors, linear resistors |
| Note regarding the connection technology (Inline potentials) | shielded |
Technical specifications and performance data
Installation and operation guide