| Parameter | Value |
|---|---|
| typ. 78 mA | |
| Type | modular |
| Depth | 71.5 mm |
| Width | 24.3 mm |
| Height | 135.4 mm |
| Data bits | 5 ... 8 |
| Stop bits | 1 or 2 |
| Current draw | max. 90 mA (all connections of the serial interface are short-circuited) |
| Input buffer | 4 kByte |
| Product type | I/O component |
| ID code (hex) | DF |
| Mounting type | DIN rail mounting |
| Output buffer | 1 kByte |
| ID code (dec.) | 223 |
| Product family | Inline |
| Supply voltage | 7.5 V DC (via voltage jumper) |
| Connection name | Inline connector |
| Register length | 64 Byte |
| Pollution degree | 2 (IEC 60664-1, EN 60664-1) |
| Protection class | III (IEC 61140, EN 61140, VDE 0140-1) |
| Stripping length | 8 mm |
| Connection method | Inline data jumper |
| Length code (dec) | 31 |
| Length code (hex) | 1F |
| Power consumption | max. 1.3 W (at ULand UM, within the permissible operating temperature) |
| Scope of delivery | including Inline connectors and marking fields |
| Input address area | max. 62 Byte |
| Transmission speed | 2 Mbps |
| Dimensional drawing | |
| Note on application | Only for industrial use |
| Output address area | max. 62 Byte |
| Protocols supported | Transparent, end-to-end, XON/XOFF |
| Degree of protection | IP20 |
| Number of interfaces | 2 |
| Overvoltage category | II (IEC 60664-1, EN 60664-1) |
| Process data channel | 496 bit |
| Termination resistor | typ. 120 Ω (active, integrated) |
| Transmission physics | Copper |
| Required parameter data | 23 Byte |
| Air pressure (operation) | 70 kPa ... 106 kPa (up to 3000 m above sea level) |
| Conductor cross section AWG | 28 ... 16 |
| Required configuration data | 5 Byte |
| Conductor cross section rigid | 0.08 mm² ... 1.5 mm² |
| Note on the connection method | Use shielded cables. |
| Conductor cross section, rigid | 0.08 mm² ... 1.5 mm² |
| Ambient temperature (operation) | -25 °C ... 55 °C |
| Air pressure (storage/transport) | 70 kPa ... 106 kPa (up to 3000 m above sea level) |
| Conductor cross section flexible | 0.08 mm² ... 1.5 mm² |
| Permissible humidity (operation) | 10 % ... 95 % (non-condensing) |
| Conductor cross section, flexible | 0.08 mm² ... 1.5 mm² |
| Ambient temperature (storage/transport) | -25 °C ... 85 °C |
| Permissible humidity (storage/transport) | 10 % ... 95 % (non-condensing) |
| Test voltage: Serial interface/24 V supply UM | 500 V AC, 50 Hz, 1 min. |
| Maximum power dissipation for nominal condition | max. 1.3 W |
| Test voltage: Serial interface/functional ground | 500 V AC, 50 Hz, 1 min. |
| Test voltage: 24 V supply (UM)/functional ground | 500 V AC, 50 Hz, 1 min. |
| Test voltage: Serial interface/7.5 V supply (bus logic) | 500 V AC, 50 Hz, 1 min. |
| Test voltage: 7.5 V supply (bus logic)/functional ground | 500 V AC, 50 Hz, 1 min. |
Technical specifications and performance data