| Parameter | Value |
|---|---|
| GTIN | 4017918956172 |
| Orderkey | 2819587 |
| (General) | Free fall in acc. with IEC 60068-2-32 1 m |
| Catalog page | Page 185 (C-6-2017) |
| Depth (Note) | 85 mm |
| Packing unit | 1 pc |
| Width (Note) | 97.6 mm |
| Height (Note) | 166 mm |
| (Digital inputs) | max. 150 mA |
| Country of origin | DE (Germany) |
| Custom tariff number | 85389091 |
| Designation (Interfaces) | Power supply |
| Noise emission (General) | Noise emission test of the housing EN 55011:1991 class A in accordance with EN 61000-6-4 |
| Dimensional drawing (Note) | |
| Mechanical tests (General) | Shock in acc. with EN 60068-2-27/IEC 60068-2-27 25g for 1 ms, three shocks in each direction |
| Protection class (General) | III, IEC 61140, EN 61140, VDE 0140-1 |
| (Standards and Regulations) | For details about hazardous substances go to tab “Downloads”, Category “Manufacturer's declaration” |
| Designation (Digital inputs) | Segment circuit supply (US) |
| Connection method (Interfaces) | 2-pos. COMBICON connector |
| Net weight (Inline potentials) | 880 g |
| Supply voltage (Digital inputs) | 24 V DC (nominal value) |
| Designation (Ambient conditions) | Startup and diagnostics |
| Degree of protection (Dimensions) | IP20 |
| Mounting type (Inline potentials) | DIN rail |
| Supply voltage range (Interfaces) | 12 V DC ... 48 V DC ±15 % (Surge voltage shutdown US> 60 V DC) |
| Current consumption (Digital inputs) | typ. 100 mA |
| Weight per Piece (excluding packing) | 880.000 g |
| Air pressure (operation) (Dimensions) | 80 kPa ... 106 kPa (up to 2000 m above sea level) |
| Input voltage (Motor starter, output) | 24 V DC |
| Supply voltage range (Digital inputs) | 19.2 V DC ... 30 V DC (including all tolerances, including ripple) |
| China RoHS (Standards and Regulations) | Environmentally Friendly Use Period = 50 |
| Connection method (Ambient conditions) | RS-232 |
| Transmission speed (Ambient conditions) | 500 kbps |
| Number of inputs (Motor starter, output) | 3 |
| Connection method (Motor starter, output) | MINI COMBICON |
| Max. current carrying capacity (Interfaces) | 10 A |
| Number of positions (Motor starter, output) | 3 |
| Ambient temperature (operation) (Dimensions) | -25 °C ... 55 °C |
| Number (Power supply for module electronics) | 1 |
| Air pressure (storage/transport) (Dimensions) | 70 kPa ... 106 kPa (up to 3000 m above sea level) |
| Connection technology (Motor starter, output) | 3-wire (Signal, Us, GND) |
| Permissible humidity (operation) (Dimensions) | 75 % ... 85 % (75% permanent, 85% occasionally) |
| Utilization restriction (Key Commercial Data) | 1 |
| Note on weight specifications (Inline potentials) | with connectors |
| Output name (Power supply for module electronics) | 1 permanently excited DC motor with or without brushgear |
| Ambient temperature (storage/transport) (Dimensions) | -25 °C ... 85 °C |
| Permissible humidity (storage/transport) (Dimensions) | 75 % ... 85 % (75% permanent, 85% occasionally) |
| Connection method (Power supply for module electronics) | 4-pos. COMBICON plug with shield clamp |
| Number of positions (Power supply for module electronics) | 4 |
| Nominal current range (Power supply for module electronics) | max. 10 A (Starting/continuous current) |
Technical specifications and performance data