| Parameter | Value |
|---|---|
| GTIN | 4017918894504 |
| Orderkey | 2861661 |
| Catalog page | Page 159 (C-6-2017) |
| Depth (Note) | 71.5 mm |
| Packing unit | 1 pc |
| Width (Note) | 48.8 mm |
| (Interfaces) | max. 200 mA |
| Height (Note) | 136.8 mm |
| (Analog inputs) | I/O / functional earth ground 500 V AC 50 Hz 1 min. |
| Country of origin | DE (Germany) |
| (Inline potentials) | -40 mA ... 40 mA |
| Custom tariff number | 85389091 |
| Designation (General) | Inline local bus |
| Designation (Interfaces) | Main circuit supply (UM) |
| No. of channels (General) | 8 |
| Dimensional drawing (Note) | |
| Connection method (General) | Inline data jumper |
| Supply voltage (Interfaces) | 24 V DC (via voltage jumper) |
| (Standards and Regulations) | No hazardous substances above threshold values |
| Test section (Analog inputs) | 5 V supply, incoming remote bus/7.5 V supply (bus logics) 500 V AC 50 Hz 1 min. |
| Transmission speed (General) | 500 kbps |
| Input name (Inline potentials) | Analog inputs |
| Transmission physics (General) | Copper |
| Net weight (Ambient conditions) | 125 g |
| Current consumption (Interfaces) | 0 A |
| Data formats (Inline potentials) | IBS IL, IBS ST, IBS RT, standardized representation, PIO format |
| Degree of protection (Dimensions) | IP20 |
| Supply voltage range (Interfaces) | 19.2 V DC ... 30 V DC (including all tolerances, including ripple) |
| Mounting type (Ambient conditions) | DIN rail |
| Number of inputs (Inline potentials) | 8 |
| Weight per Piece (excluding packing) | 125.000 g |
| Air pressure (operation) (Dimensions) | 70 kPa ... 106 kPa (up to 3000 m above sea level) |
| Connection method (Inline potentials) | Inline shield connector |
| China RoHS (Standards and Regulations) | Environmentally friendly use period: unlimited = EFUP-e |
| REACh SVHC (Standards and Regulations) | Lead 7439-92-1 |
| A/D conversion time (Inline potentials) | approx. 10 µs |
| Measuring principle (Inline potentials) | Successive approximation |
| Protection class (Electrical isolation) | III, IEC 61140, EN 61140, VDE 0140-1 |
| Current input signal (Inline potentials) | 0 mA ... 20 mA |
| Connection technology (Inline potentials) | 2, 3-wire |
| Limit frequency (3 dB) (Inline potentials) | 3.5 kHz |
| Ambient temperature (operation) (Dimensions) | -25 °C ... 55 °C |
| Description of the input (Inline potentials) | Single-ended inputs, current |
| Air pressure (storage/transport) (Dimensions) | 70 kPa ... 106 kPa (up to 3000 m above sea level) |
| Measured value resolution (Inline potentials) | 16 bits (15 bits + sign bit) |
| Permissible humidity (operation) (Dimensions) | 10 % ... 95 % (according to DIN EN 61131-2) |
| Utilization restriction (Key Commercial Data) | 1 |
| Measured value representation (Inline potentials) | 16 bit two's complement |
| Input resistance current input (Inline potentials) | 25 Ω 0.01 % |
| Ambient temperature (storage/transport) (Dimensions) | -25 °C ... 85 °C |
| Permissible humidity (storage/transport) (Dimensions) | 10 % ... 95 % (according to DIN EN 61131-2) |
| Connection in acc. with standard (Electrical isolation) | CUL |
| Note regarding the connection technology (Inline potentials) | shielded |
Technical specifications and performance data