| Parameter | Value |
|---|---|
| Output stage cannot be controlled Error message in the diagnostic code (bus) and display via the LED ERR on the module | |
| Note | Notes on operation Line protection for the network supply line, max. 20 A. Observe derating of the POWER-COMBICON connector |
| Type | modular |
| Depth | 109 mm |
| Width | 63 mm |
| Height | 224 mm |
| Filter time | 0.2 ms |
| Current draw | max. 50 mA |
| Product type | I/O component |
| Assembly note | To safeguard sufficient ventilation, ensure that there is an installation clearance of a minimum of 50 cm both above and below. |
| ID code (hex) | BF |
| Mounting type | DIN rail mounting |
| ID code (dec.) | 191 |
| Operating mode | Process data mode with one byte |
| Product family | Inline |
| Supply voltage | 7.5 V DC (via voltage jumper) |
| Register length | 1 Byte |
| Number of inputs | 1 |
| Protection class | I (IEC 61140, EN 61140, VDE 0140-1) |
| Connection method | Inline data jumper |
| Length code (dec) | 129 |
| Length code (hex) | 81 |
| Mounting position | Panel mounting on horizontal DIN rail |
| Power consumption | max. 4.2 W (entire device) |
| Input address area | 1 Byte |
| Transmission speed | 500 kbps |
| Dimensional drawing | |
| Number of positions | 4 |
| Output address area | 1 Byte |
| Degree of protection | IP20 |
| Diagnostics messages | Overcurrent Error message in the diagnostic code (bus) and display via the LED ERR on the module |
| Number of interfaces | 2 |
| Process data channel | 8 bit |
| Supply voltage range | 19.2 V DC ... 28.8 V DC (including all tolerances, including ripple) |
| Transmission physics | Copper |
| Required parameter data | 5 Byte |
| Air pressure (operation) | 80 kPa ... 106 kPa (up to 2000 m above sea level) |
| Required configuration data | 5 Byte |
| Ambient temperature (operation) | -25 °C ... 55 °C |
| Air pressure (storage/transport) | 70 kPa ... 106 kPa (up to 3000 m above sea level) |
| Permissible humidity (operation) | 10 % ... 85 % (non-condensing) |
| Test voltage: Local bus/400 V level | 1.2 kV AC, 50 Hz, 1 min. |
| Ambient temperature (storage/transport) | -25 °C ... 85 °C |
| Permissible humidity (storage/transport) | 10 % ... 85 % (non-condensing) |
| Test voltage: Local bus/Brake control switch | 1.2 kV AC, 50 Hz, 1 min. |
| Test voltage: Supply voltage UL/ 400 V level | 1.2 kV AC, 50 Hz, 1 min. |
| Test voltage: Supply voltage US/ 400 V level | 1.2 kV AC, 50 Hz, 1 min. |
| Test voltage: Supply voltage UL/ brake control switch | 1.2 kV AC, 50 Hz, 1 min. |
| Test voltage: Supply voltage US/ brake control switch | 1.2 kV AC, 50 Hz, 1 min. |
Technical specifications and performance data
Installation and operation guide