| Parameter | Value |
|---|---|
| GTIN | 4017918977658 |
| Note | Made to Order (non-returnable) |
| Orderkey | 2861713 |
| Catalog page | Page 270 (AX-2009) |
| Packing unit | 1 pc |
| (Digital inputs) | 24 V supply (I/O) / functional earth ground 500 V AC 50 Hz 1 min. |
| Country of origin | DE (Germany) |
| Custom tariff number | 85389091 |
| Designation (General) | Inline local bus |
| Designation (Interfaces) | Segment circuit supply (US) |
| No. of channels (General) | 2 |
| Connection method (General) | Inline data jumper |
| Depth (Key Commercial Data) | 71.5 mm |
| Supply voltage (Interfaces) | 24 V DC (via voltage jumper) |
| Width (Key Commercial Data) | 12.2 mm |
| (Standards and Regulations) | No hazardous substances above threshold values |
| Height (Key Commercial Data) | 119.5 mm |
| Transmission speed (General) | 2 Mbps |
| Test section (Digital inputs) | 5 V supply, incoming remote bus/7.5 V supply (bus logics) 500 V AC 50 Hz 1 min. |
| Input name (Inline potentials) | Digital inputs |
| Net weight (Ambient conditions) | 53 g |
| Current consumption (Interfaces) | max. 0.5 A |
| Degree of protection (Dimensions) | IP20 |
| Input voltage (Inline potentials) | 24 V DC |
| Supply voltage range (Interfaces) | 19.2 V DC ... 30 V DC (including all tolerances, including ripple) |
| Mounting type (Ambient conditions) | DIN rail |
| Number of inputs (Inline potentials) | 2 |
| Weight per Piece (excluding packing) | 53.000 g |
| Air pressure (operation) (Dimensions) | 70 kPa ... 106 kPa (up to 3000 m above sea level) |
| Connection method (Inline potentials) | Spring-cage connection |
| China RoHS (Standards and Regulations) | Environmentally friendly use period: unlimited = EFUP-e |
| Type of protection (Inline potentials) | Short-circuit and overload protection |
| Protection class (Electrical isolation) | III, IEC 61140, EN 61140, VDE 0140-1 |
| Note on dimensions (Key Commercial Data) | Housing dimensions |
| Connection technology (Inline potentials) | 4-wire |
| Dimensional drawing (Key Commercial Data) | |
| Typical response time (Inline potentials) | < 1 ms |
| Ambient temperature (operation) (Dimensions) | -25 °C ... 55 °C |
| Description of the input (Inline potentials) | EN 61131-2 type 1 |
| Air pressure (storage/transport) (Dimensions) | 70 kPa ... 106 kPa (up to 3000 m above sea level) |
| Permissible humidity (operation) (Dimensions) | 10 % ... 95 % (according to DIN EN 61131-2) |
| Input voltage range "0" signal (Inline potentials) | -3 V DC ... 5 V DC |
| Input voltage range "1" signal (Inline potentials) | 15 V DC ... 30 V DC |
| Note on weight specifications (Ambient conditions) | with connector |
| Ambient temperature (storage/transport) (Dimensions) | -25 °C ... 85 °C |
| Permissible humidity (storage/transport) (Dimensions) | 10 % ... 95 % (according to DIN EN 61131-2) |