| Parameter | Value |
|---|---|
| Note regarding axial connection technology:Only for stranded wires. The conductor cross sections stated refer to the geometric cross section of the cable used.Use of cables with a geometric cross section very different from that of the cable's nominal cross section should be checked before use.The wiring space of the axial screw method is designed for fine strand cables according to VDE 0295 class 5. Deviating cable structures (e.g. class 6 cables) should be checked before use.ConnectionBefore starting to connect, ensure that the tapered screw is turned back all the way (chamber is open). The cables must not be twisted. The cores should be slid to the limit stop in the contact chamber (until insulation touches contact). Hold cores in position and use socket wrench to tighten. The used core end should be cut off before connecting again. The connection screw may only be retightened once to prevent the strands from breaking. To prevent damage to the contact, the core / cable should be mechanically intercepted at an appropriate distance from the connection point (e.g. by using a plate cutout). DIN VDE 0100-520:2003-06 contains information on how to do this correctly. | |
| Width | 34.2 mm |
| Height | 40.6 mm |
| Length | 14.6 mm |
| Series | HC-M-02 |
| General | For HEAVYCON housing type B6 to B48, HC-M-MHR... hinged retaining frame required |
| Application | Power |
| Product type | Modular contact insert |
| Assembly note | - Connection of the wires using a 2 mm Allen wrench.- Housing height ≥ 52 mm.- Axial screw connection only for flexible wires.- Plug-in connections may only be operated only when there is no load/voltage. |
| Rated current | 40 A |
| Contact material | Copper alloy |
| Hexagonal socket | SW 2 |
| Contact numbering | 1 - 2 |
| Tightening torque | 1.5 Nm (2.5 mm² ... 4 mm²) |
| Connection profile | 2 |
| Degree of pollution | 3 |
| Dimensional drawing | |
| Number of positions | 2 |
| Rated surge voltage | 8 kV |
| Overvoltage category | III |
| Connection technology | Axial screw connection |
| Rated voltage (III/3) | 1000 V |
| Number of module slots | 1 |
| Conductor cross section | 2.5 mm² ... 8 mm² (The cross section specification refers to the geometric cross section of the cable used) |
| Contact carrier material | PC |
| Contact surface material | Ag |
| Insertion/withdrawal cycles | ≥ 500 |
| Connection cross section AWG | 12 ... 10 |
| Ambient temperature (operation) | -40 °C ... 125 °C |
| Connection in acc. with standard | IEC / EN |
| Flammability rating according to UL 94 | V0 |
| Stripping length of the individual wire | 8 mm +1 mm (for 6 mm²) |