| Parameter | Value |
|---|---|
| GTIN | 4055626067070 |
| Orderkey | 2702236 |
| Catalog page | Page 521 (C-6-2017) |
| Packing unit | 1 pc |
| (Dimensions) | -40 °F ... 158 °F |
| Country of origin | DE (Germany) |
| Custom tariff number | 85176200 |
| ATEX (Serial interface) | II 3 G Ex nA IIC T4 Gc DEMKO 17 ATEX 1749X |
| IECEx (Serial interface) | IECEx ULD 17.0020X Ex nA IIC T4 Gc |
| Interface (Power supply) | Analog |
| MTBF (Ambient conditions) | 208 Years (Siemens model SN29500, temperature 40°C, env. factor 1.5 and stress factor 50%) |
| Color (Ambient conditions) | gray |
| Interface 1 (Power supply) | HART FSK |
| Depth (Key Commercial Data) | 114.5 mm |
| No. of ports (Power supply) | 8 |
| Width (Key Commercial Data) | 45 mm |
| (Standards and Regulations) | For details about hazardous substances go to tab “Downloads”, Category “Manufacturer's declaration” |
| Height (Key Commercial Data) | 99 mm |
| Conformance (Serial interface) | CE-compliant |
| Supply voltage range (General) | 19.2 V DC ... 30 V DC (supplied from the bus) |
| Net weight (Ambient conditions) | 342.4 g |
| Conformance (Ambient conditions) | CE-compliant |
| Connection method (Power supply) | Screw connection |
| Degree of protection (Dimensions) | IP20 |
| UL, USA/Canada (Serial interface) | Class I, Div. 2, Groups A, B, C, D |
| Max. current consumption (General) | 258 mA (at 24 V DC) |
| Noxious gas test (Serial interface) | ISA-S71.04-1985 G3 Harsh Group A |
| Weight per Piece (excluding packing) | 342.400 g |
| Maximum output current (Power supply) | 25 mA (per channel) |
| Typical current consumption (General) | 74 mA (24 V DC with no load) |
| China RoHS (Standards and Regulations) | Environmentally Friendly Use Period = 50 |
| Mounting position (Ambient conditions) | any |
| Dimensional drawing (Key Commercial Data) | |
| Assembly instructions (Ambient conditions) | on standard DIN rail NS 35 in accordance with EN 60715 |
| Ambient temperature (operation) (Dimensions) | -40 °C ... 70 °C |
| Electromagnetic compatibility (Serial interface) | Conformance with EMC Directive 2004/108/EC |
| Electromagnetic compatibility (Ambient conditions) | Conformance with EMC Directive 2004/108/EC |
| Ambient temperature (storage/transport) (Dimensions) | -40 °C ... 85 °C |
| Test voltage data interface/power supply (Ambient conditions) | 500 V AC |