| Parameter | Value |
|---|---|
| Pack | 1 |
| Series | Surion - GPS2M - Magnetic protection (Ie max 63A) |
| Capacity | GPS2MH - High Breaking capacity |
| Rated current (A) | 50 A |
| ETIM 5.0 (DIMENSIONS) | EC000074 |
| ETIM 6.0 (DIMENSIONS) | EC000074 |
| Weight (SPECIFICATIONS) | 0.81 kg |
| Instantaneous short-circuit release (A) | 650 A |
| Rated power 3 phase motors at 400Vac Pn (kW) | 22 kW |
| Rated power 3 phase motors at 440Vac Pn (kW) | 25 kW |
| Rated power 3 phase motors at 500/525Vac Pn (kW) | 25/30 kW |
| Rated power 3 phase motors at 660/690Vac Pn (kW) | 37/40 kW |
| Rated service short-circuit breaking cap 400V Ics kA | 38 kA |
| Rated service short-circuit breaking cap 440V Ics kA | 25 kA |
| Rated service short-circuit breaking cap 600V Ics kA | 4 kA |
| Rated service short-circuit breaking cap 690V Ics kA | 4 kA |
| Rated ultimate short-circuit breaking cap 400V Icu kA | 50 kA |
| Rated ultimate short-circuit breaking cap 440V Icu kA | 35 kA |
| Rated ultimate short-circuit breaking cap 600V Icu kA | 5 kA |
| Rated ultimate short-circuit breaking cap 690V Icu kA | 5 kA |
| Rated service short-circuit breaking cap 220/230V Ics kA | 100 kA |
| Rated service short-circuit breaking cap 500/525V Ics kA | 8 kA |
| Rated ultimate short-circuit breaking cap 220/230V Icu kA | 100 kA |
| Rated ultimate short-circuit breaking cap 500/525V Icu kA | 10 kA |