| Parameter | Value |
|---|---|
| I + II + III | |
| Note | 2011 |
| Type | DIN rail module, one-piece |
| Depth | 76.6 mm (incl. DIN rail 7.5 mm) |
| Width | 72 mm |
| Height | 89.8 mm |
| EN type | T1 + T2 + T3 |
| Altitude | ≤ 5000 m |
| Product type | Combination type |
| Screw thread | M5 |
| Mounting type | DIN rail: 35 mm |
| Material group | I |
| Open side panel | No |
| Horizontal pitch | 4 Div. |
| Housing material | PBT |
| Pollution degree | 2 |
| Response time tA | ≤ 100 ns |
| Stripping length | 18 mm |
| Connection method | Screw connection |
| Cross section AWG | (converted acc. to IEC) |
| Shock (operation) | 2g (Half-sine / 11 ms / 3x ±X, ±Y, ±Z) |
| Tightening torque | 3 Nm (2,5 mm² ... 16 mm²) |
| Mode of protection | L-N |
| Nominal voltage UN | 240/415 V AC (TN-S) |
| Dimensional drawing | |
| Insulating material | PBT |
| Combination wave UOC | 6 kV |
| Degree of protection | IP20 (Installed) |
| Nominal frequency fN | 50 Hz (60 Hz) |
| Overvoltage category | IV |
| Residual current IPE | ≤ 0.01 mA |
| CTI value of material | 600 |
| Rated load current IL | 80 A (< 55 °C) |
| Vibration (operation) | 0,5g (9 … 200 Hz / 2.5 h / X, Y, Z) |
| IEC power supply system | TN-S |
| IEC test classification | T1 + T2 + T3 |
| TOV behavior at UT(L-N) | 457 V AC (5 s / withstand mode) |
| Standards/specifications | IEC 61643-11 |
| TOV behavior at UT(N-PE) | 1200 V AC (200 ms / withstand mode) |
| Residual voltage Ures(L-N) | ≤ 1.5 kV (at In) |
| Conductor cross section AWG | 13 ... 2 |
| Residual voltage Ures(L-PE) | ≤ 1.7 kV (at In) |
| Residual voltage Ures(N-PE) | ≤ 1.5 kV (at In) |
| Conductor cross section rigid | 2.5 mm² ... 35 mm² |
| Maximum continuous voltage UC | 264 V AC |
| Surge protection fault message | optical |
| Ambient temperature (operation) | -40 °C ... 85 °C |
| Conductor cross section flexible | 2.5 mm² ... 25 mm² |
| Permissible humidity (operation) | 5 % ... 95 % |
| Voltage protection level Up(L-N) | ≤ 1.5 kV |
| Voltage protection level Up(L-PE) | ≤ 2.5 kV |
| Voltage protection level Up(N-PE) | ≤ 1.5 kV |
| Short-circuit current rating ISCCR | 25 kA |
| Max. backup fuse with branch wiring | 315 A (gG) |
| Flammability rating according to UL 94 | V-0 |
| Ambient temperature (storage/transport) | -40 °C ... 85 °C |
| Follow current interrupt rating Ifi(N-PE) | 100 A |
| Follow current quenching capacity Ifi(L-N) | 25 kA |
| Max. backup fuse with V-type through wiring | 80 A (gG) |
| Total discharge current Itotal(10/350) µs | 100 kA |
| Nominal discharge current In(8/20) µs (L-N) | 25 kA |
| Nominal discharge current In(8/20) µs (L-PE) | 25 kA |
| Nominal discharge current In(8/20) µs (N-PE) | 100 kA |
| Impulse discharge current (10/350) µs (L-PE), charge | 12.5 As |
| Impulse discharge current (10/350) µs (N-PE), charge | 50 As |
| Impulse discharge current (10/350) µs (L-N), charge | 12.5 As |
| Impulse discharge current (10/350) µs (L-N), specific energy | 156 kJ/Ω |
| Impulse discharge current (10/350) µs (N-PE), specific energy | 2500 kJ/Ω |
| Impulse discharge current (10/350) µs (L-PE), specific energy | 156 kJ/Ω |
| Impulse discharge current (10/350) µs (L-PE), peak current value Iimp | 25 kA |
| Impulse discharge current (10/350) µs (N-PE), peak current value Iimp | 100 kA |
| Impulse discharge current (10/350) µs (L-N), peak current value Iimp | 25 kA |
Technical specifications and performance data
Installation and operation guide