| Parameter | Value |
|---|---|
| GTIN | 4046356481281 |
| Note | Made to Order (non-returnable) |
| Orderkey | 2800125 |
| (General) | 60 Hz |
| Catalog page | Page 20 (TT-2011) |
| Packing unit | 1 pc |
| Country of origin | DE (Germany) |
| EN type (General) | T1 |
| Custom tariff number | 85363030 |
| (Ambient conditions) | EN 61643-11 |
| UT(TOV-safe) (General) | 1200 V AC (200 ms / N-PE) |
| UT(TOV-proof) (General) | 335 V (5 sec /L-N) |
| Type (Ambient conditions) | DIN rail module, one-piece |
| Color (Ambient conditions) | black |
| Response time tA (General) | ≤ 100 ns |
| Depth (Key Commercial Data) | 65.7 mm |
| Width (Key Commercial Data) | 70.4 mm |
| Height (Key Commercial Data) | 95 mm |
| Nominal frequency fN (General) | 50 Hz |
| Residual current IPE (General) | ≤ 0.1 mA |
| Response time tA(L-N) (General) | ≤ 100 ns |
| Response time tA(N-PE) (General) | ≤ 100 ns |
| (Connection, protective circuit) | DIN EN 61643-11/A11 2007 |
| Degree of protection (Dimensions) | IP20 |
| IEC test classification (General) | I |
| Screw thread (Protective circuit) | M5 |
| Mounting type (Ambient conditions) | DIN rail: 35 mm |
| Weight per Piece (excluding packing) | 707.900 g |
| Housing material (Ambient conditions) | PA-GF |
| Stripping length (Protective circuit) | 14.5 mm |
| Connection method (Protective circuit) | Screw connection |
| Horizontal pitch (Key Commercial Data) | 4 Div. |
| Standby power consumption PC (General) | ≤ 26 mVA |
| Tightening torque (Protective circuit) | 4.5 Nm |
| Direction of action (Ambient conditions) | 3L-N & N-PE |
| Number of positions (Ambient conditions) | 4 |
| Connection method IN (Protective circuit) | Biconnect screw terminal block |
| Connection method OUT (Protective circuit) | Biconnect screw terminal block |
| Connection technology (Protective circuit) | Biconnect terminal block |
| Voltage protection level Up(L-N) (General) | ≤ 2 kV |
| Voltage protection level Up(N-PE) (General) | ≤ 2 kV |
| Ambient temperature (operation) (Dimensions) | -40 °C ... 85 °C |
| IEC power supply system (Ambient conditions) | TT |
| Max. backup fuse with branch wiring (General) | 400 A (NH-gL) |
| Permissible humidity (operation) (Dimensions) | ≤ 95 % |
| Nominal discharge current In(8/20) µs (General) | |
| Maximum continuous operating voltage UC (General) | 260 V AC |
| Follow current interrupt rating Ifi(L-N) (General) | 3 kA |
| Surge protection fault message (Ambient conditions) | optical |
| Conductor cross section AWG max. (Protective circuit) | 2 |
| Conductor cross section AWG min. (Protective circuit) | 20 |
| Follow current quenching capacity Ifi(N-PE) (General) | 100 A |
| Maximum continuous operating voltage UC(L-N) (General) | 260 V AC |
| Nominal discharge current In(8/20) µs (L-N) (General) | 35 kA |
| Standards/regulations (Connection, protective circuit) | IEC 61643-1 2005 |
| Conductor cross section solid max. (Protective circuit) | 35 mm² |
| Conductor cross section solid min. (Protective circuit) | 0.5 mm² |
| Maximum continuous operating voltage UC(N-PE) (General) | 260 V AC |
| Nominal discharge current In(8/20) µs (N-PE) (General) | 50 kA |
| Impulse discharge current (10/350) µs, charge (General) | 17.5 As |
| Conductor cross section flexible max. (Protective circuit) | 25 mm² |
| Conductor cross section flexible min. (Protective circuit) | 0.5 mm² |
| Flammability rating according to UL 94 (Ambient conditions) | V0 |
| Max. discharge current Imax(8/20) µs maximum (L-N) (General) | 35 kA |
| Max. discharge current Imax(8/20) µs maximum (N-PE) (General) | 50 kA |
| Impulse discharge current (10/350) µs, peak value limp (General) | 35 kA (L-N) |
| Impulse discharge current (10/350) µs, specific energy (General) | 306 kJ/Ω (L-N) |
| Standards for cearances and creepage distances (Ambient conditions) | EN 60664-1 |
| Front of wave sparkover voltage at 6 kV (1.2/50) µs (L-N) (General) | ≤ 2 kV |
| Front of wave sparkover voltage at 6 kV (1.2/50) µs (N-PE) (General) | ≤ 2 kV |
| Short-circuit withstand capability IPwith max. backup fuse (r.m.s.) (General) | 25 kA |
Technical specifications and performance data