Service time: Monday to Friday 9:00-18:00
FLM DIO 8/4 M8 - FLM DIO 8/4 M8 2773351 PHOENIX CONTACT Distributed I/O device
In Stock Hot Product

FLM DIO 8/4 M8

FLM DIO 8/4 M8 2773351 PHOENIX CONTACT Distributed I/O device

$0.00USD
4079 in stock
Key Specifications
GTIN:4046356181686
Orderkey:2773351
Catalog page:Page 217 (C-6-2017)
Depth (Note):26.5 mm
Supplier Information
Products: 0
Usually ships within 2-3 business days
Quality Guaranteed
Fast Shipping
Technical Support

Technical Specifications

ParameterValue
GTIN4046356181686
Orderkey2773351
Catalog pagePage 217 (C-6-2017)
Depth (Note)26.5 mm
Packing unit1 pc
Width (Note)29.8 mm
Height (Note)143 mm
Caption (Note)Side view (dimensions in mm)
Country of originDE (Germany)
Custom tariff number85389091
Designation (General)Fieldline local bus
Designation (Interfaces)UL
Drill hole spacing (Note)133 mm
Note on dimensions (Note)Length details incl. fixing clips
Dimensional drawing (Note)
Connection method (General)M8 connector
Supply current (Interfaces)3 A
Supply voltage (Interfaces)24 V DC
(Standards and Regulations)For details about hazardous substances go to tab “Downloads”, Category “Manufacturer's declaration”
Output name (Digital inputs)Digital outputs
Transmission speed (General)500 kbps
Number of positions (General)4
Connection method (Interfaces)M8 connector
Test section (Digital outputs)To I/O 500 V AC
Net weight (Ambient conditions)144 g
Output voltage (Digital inputs)24 V DC
Number of positions (Interfaces)4
Degree of protection (Dimensions)IP65/IP67
Input name (Fieldline potentials)Digital inputs
Supply voltage range (Interfaces)18 V DC ... 30 V DC (including ripple)
Connection method (Digital inputs)M8 connector
Filter time (Fieldline potentials)3 ms
Mounting type (Ambient conditions)Wall mounting
Number of outputs (Digital inputs)4 (Can also be used as an input)
Type of protection (Digital inputs)Short-circuit protection
Input voltage (Fieldline potentials)24 V DC
Weight per Piece (excluding packing)144.000 g
Air pressure (operation) (Dimensions)80 kPa ... 106 kPa (up to 2000 m above sea level)
China RoHS (Standards and Regulations)Environmentally Friendly Use Period = 50
Connection technology (Digital inputs)2, 3-wire
Designation connection point (General)Copper cable
Number of inputs (Fieldline potentials)8 (4 fixed, 4 freely selectable)
Protection class (Electrical isolation)III, IEC 61140, EN 61140, VDE 0140-1
Connection method (Fieldline potentials)M8 connector
Ambient temperature (operation) (Dimensions)-25 °C ... 60 °C
Connection technology (Fieldline potentials)2, 3-wire
Air pressure (storage/transport) (Dimensions)70 kPa ... 106 kPa (up to 3000 m above sea level)
Permissible humidity (operation) (Dimensions)5 % ... 95 %
Utilization restriction (Key Commercial Data)1
Description of the input (Fieldline potentials)IEC 61131-2 type 1
Maximum output current per channel (Digital inputs)500 mA
Ambient temperature (storage/transport) (Dimensions)-25 °C ... 85 °C
Input voltage range "0" signal (Fieldline potentials)-30 V DC ... 5 V DC
Input voltage range "1" signal (Fieldline potentials)13 V DC ... 30 V DC
Permissible humidity (storage/transport) (Dimensions)10 % ... 95 %
Connection in acc. with standard (Electrical isolation)CUL
Voltage supply UL (Power supply for module electronics)24 V DC

Product Description

The space-saving local bus system is specially designed for use in the immediate vicinity of the process. Functions: 4 digital inputs, 4 digital inputs or outputs max. 500 mA, exact diagnostics per ch
Key Features
  • Industrial grade quality
  • RoHS compliant
  • CE certified
  • 1-year warranty

Product Documents

Datasheet

Technical specifications and performance data

User Manual

Installation and operation guide

Top