| Parameter | Value |
|---|---|
| AAI835 | |
| Fuse | 0.05 A TR5 (slow-blow) (F1 ... F16) |
| Note | Usable system cables: Phoenix Contact YUC40, Yokogawa KS1 |
| Depth | 49.7 mm |
| Pitch | 2.54 mm |
| Width | 91.6 mm |
| Height | 111.8 mm |
| Altitude | ≤ 2000 m |
| Insulation | Functional insulation |
| Certificate | UKCA-compliant |
| Product type | Interface module |
| Screw thread | M3 |
| Mounting type | DIN rail mounting |
| Operating mode | 100% operating factor |
| No. of channels | 8 |
| Article revision | 06 |
| Pollution degree | 2 |
| Stripping length | 8 mm |
| Connection method | Yokogawa KS-compatible |
| Mounting position | any |
| Suitable I/O card | AAI135 |
| Tightening torque | 0.5 Nm |
| Notes on operation | For proper use, the specifications of the installation directive (see Downloads) must be observed. For applications or use with third-party products, the specifications, and the safety and warning instructions of the respective third-party manufacturer must also be met. |
| Number of positions | 40 |
| Rated surge voltage | 0.5 kV (1.2/50 μs) |
| Current (per branch) | ≤ 0.05 A (TU= 23 °C) |
| Overvoltage category | II |
| Number of connections | 2 |
| Standards/regulations | EN IEC 60664-1 |
| Operating voltage (DC) | ≤ 30 V DC |
| Status display present | No |
| Rated insulation voltage | 50 V |
| Conductor cross section AWG | 24 ... 12 |
| Conductor cross section rigid | 0.2 mm² ... 4 mm² |
| Degree of protection (Module) | IP00 |
| Ambient temperature (operation) | -20 °C ... 50 °C |
| Conductor cross section flexible | 0.2 mm² ... 4 mm² |
| Ambient temperature (storage/transport) | -20 °C ... 70 °C |
| Degree of protection (Installation location) | ≤ IP54 |
| Conductor cross-section rigid (2 conductors with same cross section) | 0.2 mm² ... 1 mm² |
| Conductor cross section flexible (2 conductors with same cross section) | 0.2 mm² ... 1 mm² |
Technical specifications and performance data