| Parameter | Value |
|---|---|
| 2000 m (Fiberglass 62.5/125) | |
| MTTF | 67.3 Years (MIL-HDBK-217F standard, temperature 25°C, operating cycle 100%) |
| Type | Block design |
| Depth | 70 mm |
| Width | 50 mm |
| Height | 120 mm |
| Wavelength | 1300 nm |
| Signal LEDs | Data receive, link status |
| Product type | Switch |
| Test section | 500 V DC 1 min. |
| Mounting type | DIN rail mounting |
| Noise emission | EN 61000-6-4 |
| Noise immunity | EN 61000-6-2:2005 |
| Product family | Unmanaged Switch SFN |
| Status display | LEDs: US, link and activity per port |
| Basic functions | Unmanaged switch / auto negotiation, complies with IEEE 802.3, store and forward switching mode |
| Connection name | Power supply |
| No. of channels | 7 (RJ45 ports) |
| Residual ripple | 3.6 VPP(within the permitted voltage range) |
| Housing material | Aluminum |
| Protection class | III (IEC 61140, EN 61140, VDE 0140-1) |
| Stripping length | 7 mm |
| Connection method | RJ45 |
| Local diagnostics | US Supply voltage Green LED |
| Transmission speed | 10/100 Mbps |
| Supply voltage (DC) | 24 V DC |
| Transmission length | 100 m (per segment) |
| Transmission medium | Copper |
| Additional functions | Autonegotiation |
| Degree of protection | IP20 |
| Supply voltage range | 9 V DC ... 32 V DC |
| Transmission physics | Ethernet in RJ45 twisted pair |
| Vibration (operation) | in acc. with IEC 60068-2-6: 5g, 150 Hz |
| Power supply connection | Via COMBICON, max. conductor cross section 2.5 mm² |
| Air pressure (operation) | 86 kPa ... 108 kPa (up to 1500 m above sea level) |
| Conductor cross section AWG | 24 ... 12 |
| Typical current consumption | 190 mA (at US= 24 V DC) |
| Electromagnetic compatibility | Conformance with EMC Directive 2004/108/EC |
| Note on the connection method | Auto negotiation and autocrossing |
| Conductor cross section, rigid | 0.2 mm² ... 2.5 mm² |
| Ambient temperature (operation) | 0 °C ... 60 °C |
| Conformance with EMC directives | IEC 61000-6-2 IEC 61000-4-2 (ESD) Criterion B |
| Air pressure (storage/transport) | 66 kPa ... 108 kPa (up to 3500 m above sea level) |
| Permissible humidity (operation) | 5 % ... 95 % (non-condensing) |
| Status and diagnostic indicators | LEDs: US, link and activity per port |
| Conductor cross section, flexible | 0.2 mm² ... 2.5 mm² |
| Ambient temperature (storage/transport) | -20 °C ... 70 °C |
| Permissible humidity (storage/transport) | 5 % ... 95 % (non-condensing) |
| Maximum power dissipation for nominal condition | 4.56 W |
| Free from substances that could impair the application of coating | In acc. with VW specification |
| Resistance to gases that may endanger the functions, in acc. with DIN 40046-36, DIN 40046-37 | Sulfur dioxide (SO2) 10 ±0.3 cm3/m3, hydrogen sulfide (H2S) 1 ±0.3 cm3/m3, at 25°C and 75% humidity and exposure of four days |
Technical specifications and performance data
Installation and operation guide