| Parameter | Value |
|---|---|
| GTIN | 4046356466165 |
| Orderkey | 2316048 |
| (General) | 32 V DC (IIB) |
| Catalog page | Page 425 (C-8-2015) |
| Depth (Note) | 70.4 mm |
| Packing unit | 1 pc |
| Width (Note) | 17.5 mm |
| Height (Note) | 99.1 mm |
| (Safety data) | FF-846 |
| Country of origin | US (United States) |
| ATEX (Safety data) | Sira 08ATEX4302X; II 3G Ex nA IIC T4 GcII 3G Ex ic IIC T4 Gc, FISCO icII 3G Ex nL IIC T4 Gc, FNICO |
| IECEx (Safety data) | IECEx SIR 08.0109X; Ex nA IIC T4 Gc;Ex ic IIC T4 Gc, FISCO ic; Ex nL IIC T4 Gc, FNICO |
| Shock (Safety data) | 15g, 11 ms |
| Custom tariff number | 85389099 |
| ATEX (Serial interface) | Sira 08ATEX4302X; II 3G Ex nA IIC T4 GcII 3G Ex ic IIC T4 Gc, FISCO icII 3G Ex nL IIC T4 Gc, FNICO |
| IECEx (Serial interface) | IECEx SIR 08.0109X; Ex nA IIC T4 Gc;Ex ic IIC T4 Gc, FISCO ic; Ex nL IIC T4 Gc, FNICO |
| Conformance (Safety data) | CE-compliant, additionally EN 61326 |
| Designation (Safety data) | Standards/regulations |
| Color (Ambient conditions) | green |
| Dimensional drawing (Note) | |
| Interface 1 (Power supply) | Foundation Fieldbus and PROFIBUS PA Segment |
| Type of test (Safety data) | Corrosive resistance in acc. to ANSI-ISA 71.04-1985 - Severity level G3 |
| (Standards and Regulations) | For details about hazardous substances go to tab “Downloads”, Category “Manufacturer's declaration” |
| CSA, USA/Canada (Safety data) | Class I, Division 2, Groups A,B,C,D; Ex nA IIC T4Class I, Zone 2, AEx nA IIC T4 |
| Supply voltage range (General) | 24 V DC ... 32 V DC |
| Net weight (Ambient conditions) | 102.7 g |
| Surge protection (Power supply) | Active if voltage exceeds 39 V (typ.) or 41 V (max.) |
| Conformance (Ambient conditions) | CE-compliant, additionally EN 61326 |
| Connection method (Power supply) | Pluggable COMBICON screw connection for each spur |
| Nominal supply voltage (General) | 24 V DC (IIC) |
| Degree of protection (Dimensions) | IP20 |
| Fieldbus Foundation (Safety data) | FF-846 |
| CSA, USA/Canada (Serial interface) | Class I, Division 2, Groups A,B,C,D; Ex nA IIC T4Class I, Zone 2, AEx nA IIC T4 |
| Max. current consumption (General) | 12 mA (with terminator) |
| Input voltage Ui (Serial interface) | 17.5 V (for FB-2SP in a FNICO/FISCO ic system) |
| Standards/regulations (Safety data) | Shock and vibration in acc. with EN 61131-2 and EN 50178 |
| Termination resistor (Power supply) | 100 Ω, external removable plug included |
| Vibration (operation) (Safety data) | 1g, 10 Hz ... 150 Hz |
| Weight per Piece (excluding packing) | 102.700 g |
| Typical current consumption (General) | 8 mA (without termination resistor) |
| China RoHS (Standards and Regulations) | Environmentally Friendly Use Period = 50 |
| Mounting position (Ambient conditions) | On horizontal DIN rail NS 35 in acc. with EN 60715 |
| Fieldbus Foundation (Ambient conditions) | FF-846 |
| Ambient temperature (operation) (Dimensions) | -40 °C ... 85 °C |
| Permissible humidity (operation) (Dimensions) | 10 % ... 95 % (non-condensing) |
| Utilization restriction (Key Commercial Data) | EMC: class A product, see manufacturer's declaration in the download area |
| Conductor cross section AWG max. (Power supply) | 12 |
| Conductor cross section AWG min. (Power supply) | 24 |
| Voltage drop trunk line / outputs (Power supply) | ≤ 0.2 V |
| Conductor cross section solid max. (Power supply) | 2.5 mm² |
| Conductor cross section solid min. (Power supply) | 0.2 mm² |
| Ambient temperature (storage/transport) (Dimensions) | -40 °C ... 85 °C |
| Conductor cross section flexible max. (Power supply) | 2.5 mm² |
| Conductor cross section flexible min. (Power supply) | 0.2 mm² |