| Parameter | Value |
|---|---|
| GTIN | 4046356783231 |
| Note | Made to Order (non-returnable) |
| Orderkey | 2316297 |
| Catalog page | Page 518 (C-6-2017) |
| Depth (Note) | 70.4 mm |
| Packing unit | 1 pc |
| Width (Note) | 17.7 mm |
| Height (Note) | 85 mm |
| (Safety data) | IEC 61158-2 |
| Country of origin | US (United States) |
| ATEX (Safety data) | Sira 13ATEX4148X; II 3G Ex nA IIC T4 Gc |
| IECEx (Safety data) | IECEx SIR 13.0059X; Ex nA IIC T4 Gc |
| Custom tariff number | 85389099 |
| ATEX (Serial interface) | Sira 13ATEX4148X; II 3G Ex nA IIC T4 Gc |
| IECEx (Serial interface) | IECEx SIR 13.0059X; Ex nA IIC T4 Gc |
| Conformance (Safety data) | IEC 61158-2 |
| Designation (Safety data) | Standards/regulations |
| Test result (Safety data) | 5g, 10 ... 150 Hz |
| Color (Ambient conditions) | green |
| Dimensional drawing (Note) | |
| Interface 1 (Power supply) | FOUNDATION Fieldbus |
| Type of test (Safety data) | Corrosive resistance in acc. to ANSI-ISA 71.04-1985 - Severity level G3 |
| (Standards and Regulations) | For details about hazardous substances go to tab “Downloads”, Category “Manufacturer's declaration” |
| CSA, USA/Canada (Safety data) | Class I, Div. 2, Groups A,B,C,D; Ex nA IIC T4_GcClass I, Zone 2, AEx nA IIC T4_Gc |
| Output current (Power supply) | 29 mA |
| Supply voltage range (General) | 9 V DC ... 32 V DC |
| Net weight (Ambient conditions) | 97.1 g |
| Conformance (Ambient conditions) | IEC 61158-2 |
| Connection method (Power supply) | TBUS |
| Degree of protection (Dimensions) | IP20 |
| Fieldbus Foundation (Safety data) | FF-830 |
| CSA, USA/Canada (Serial interface) | Class I, Div. 2, Groups A,B,C,D; Ex nA IIC T4_GcClass I, Zone 2, AEx nA IIC T4_Gc |
| Max. current consumption (General) | 29 mA |
| Standards/regulations (Safety data) | Shock and vibration in acc. with EN 61131-2 and EN 50178 |
| Weight per Piece (excluding packing) | 97.100 g |
| Maximum output current (Power supply) | 29 mA |
| Output nominal voltage (Power supply) | ≤ 32 V |
| Typical current consumption (General) | 27 mA |
| China RoHS (Standards and Regulations) | Environmentally Friendly Use Period = 50 |
| Mounting position (Ambient conditions) | Any orientation on DIN rail, NS 35, in acc. with EN 60715 |
| Fieldbus Foundation (Ambient conditions) | FF-830 |
| Ambient temperature (operation) (Dimensions) | -40 °C ... 85 °C |
| Utilization restriction (Key Commercial Data) | EMC: class A product, see manufacturer's declaration in the download area |
| Ambient temperature (storage/transport) (Dimensions) | -40 °C ... 85 °C |
| Flammability rating according to UL 94 (Safety data) | V0 |
Technical specifications and performance data
Installation and operation guide