| Parameter | Value |
|---|---|
| li: Switched-mode beginning with the pulse | |
| Color | gray (RAL 7042) |
| Depth | 65.5 mm |
| Width | 17.5 mm |
| Height | 89.5 mm |
| Function | lp: Switched-mode beginning with the pause |
| Insulation | Basic insulation |
| Certificate | CE-compliant |
| Output fuse | 5 A (fast-blow) |
| Product type | Timer relay |
| Assembly note | on standard DIN rail NS 35 in accordance with EN 60715 |
| Mounting type | DIN rail mounting |
| Recovery time | 500 ms |
| Basic accuracy | ± 1 % (of scale end value) |
| Climatic class | 3K3 (in acc. with EN 60721) |
| Noise emission | EN 61000-6-4 |
| Noise immunity | EN 61000-6-2 |
| Operating mode | 100% operating factor |
| Status display | Green LED (POWER) |
| Connection name | Non-floating, terminals A1-B1 |
| Repeat accuracy | ≤ 0.5 % ±5 ms |
| Article revision | 00 |
| Pollution degree | 2 |
| Setting accuracy | ≤ 5 % (of scale end value) |
| Stripping length | 8 mm |
| Connection method | Push-in connection |
| Mounting position | any |
| Nominal frequency | 48 Hz ... 63 Hz |
| Setting range time | 50 ms ... 100 h (7 time end ranges) |
| Input voltage range | 24 V AC/DC ... 240 V AC/DC -10 % ... +15 % |
| Control pulse length | ≥ 50 ms (DC) |
| Overvoltage category | III |
| Low Voltage Directive | Conformance with Low Voltage Directive |
| Standards/regulations | EN 50178 |
| Contact switching type | 1 floating changeover contact |
| Mechanical service life | approx. 2x 107cycles |
| Service life electrical | approx. 2x 105cycles at ohmic load, 1000 VA |
| Rated insulation voltage | 300 V |
| Maximum switching voltage | 250 V AC (in acc. with IEC 60664-1) |
| Nominal power consumption | 2.5 VA (1 W) |
| Conductor cross section AWG | 26 ... 14 |
| Conductor cross section rigid | 0.14 mm² ... 2.5 mm² |
| Electromagnetic compatibility | Conformance with EMC directive |
| Degree of protection (Housing) | IP40 (Housing) |
| Ambient temperature (operation) | -25 °C ... 55 °C |
| Conductor cross section flexible | 0.14 mm² ... 2.5 mm² |
| Permissible humidity (operation) | 15 % ... 85 % |
| Temperature coefficient, typical | ≤ 0.01 %/K |
| Interrupting rating (ohmic load) max. | 750 VA (3 A/250 V AC, module aligned, ≤ 5 mm spacing) |
| Flammability rating according to UL 94 | V0 |
| Ambient temperature (storage/transport) | -25 °C ... 70 °C |
| Test voltage relay winding/relay contact | 4 kV |
| Degree of protection (Connection terminal blocks) | IP20 (Connection terminal blocks) |
Technical specifications and performance data