| Parameter | Value |
|---|---|
| GTIN | 4055626463391 |
| Orderkey | 2910588 |
| Packing unit | 1 pc |
| (Input data) | 40 W (230 V AC) |
| (Output data) | 88 % (230 V AC) |
| Country of origin | TH (Thailand) |
| Custom tariff number | 85044030 |
| (Ambient conditions) | typ. 16 ms (230 V AC) |
| Derating (Input data) | > 40 °C (1.67 % / °C, 115 V AC) |
| Efficiency (Output data) | 85 % (115 V AC) |
| Net weight (Output data) | 1.3 kg |
| Output power (Input data) | 480 W |
| (Connection data, output) | EN 61000-6-1 |
| Stripping length (General) | 7 mm |
| Connection method (General) | Screw connection |
| Depth (Key Commercial Data) | 128.5 mm |
| Width (Key Commercial Data) | 85.5 mm |
| Height (Key Commercial Data) | 123.6 mm |
| Residual ripple (Input data) | < 120 mVPP(-10 °C ... +70 °C) |
| Protection class (Output data) | I (with PE connection) |
| Input fuse (Ambient conditions) | 10 A (fast blow, internal) |
| Shock (Connection data, output) | IEC 60068-2-27, 27, half sinusoidal wave: 50g for 11 ms; 3x per direction, 9x overall |
| Degree of pollution (Dimensions) | 2 |
| Installation height (Dimensions) | ≤ 5000 m (> 2000 m, Derating: 10 %/1000 m) |
| Degree of protection (Dimensions) | IP20 |
| Max. capacitive load (Input data) | 8000 μF |
| Degree of protection (Output data) | IP20 |
| Typical response time (Input data) | 1000 ms |
| Nominal output voltage (Input data) | 24 V DC ±2 % |
| Mains buffering (Ambient conditions) | typ. 10 ms (115 V AC) |
| Weight per Piece (excluding packing) | 1,480.000 g |
| MTBF (Telcordia SR-332) (Output data) | > 700000 h |
| Active current limitation (Input data) | 109% - 130% of the max. output power (in the event of short circuit) |
| UL approvals (Connection data, output) | UL/C-UL listed UL 508 |
| AC frequency range (Ambient conditions) | 47 Hz ... 63 Hz |
| Operating voltage display (Output data) | Green LED |
| Type of protection (Ambient conditions) | Transient surge protection |
| Current consumption (Ambient conditions) | 5.4 A (115 V AC) |
| Input voltage range (Ambient conditions) | 85 V AC ... 264 V AC |
| Noise immunity (Connection data, output) | EN 61000-6-2 |
| Nominal output current (IN) (Input data) | 20 A |
| Inrush surge current (Ambient conditions) | typ. 40 A (115 V AC) |
| Power loss nominal load max. (Input data) | 50 W (115 V AC) |
| Stripping length (Connection data, input) | 7 mm |
| Conductor cross section AWG max. (General) | 12 |
| Conductor cross section AWG min. (General) | 16 |
| Connection method (Connection data, input) | Screw connection |
| Insulation voltage input / PE (Output data) | 2 kV AC |
| Ambient temperature (operation) (Dimensions) | -20 °C ... 70 °C |
| Discharge current to PE (Ambient conditions) | < 1 mA (264 V AC) |
| Insulation voltage output / PE (Output data) | 0.5 kV AC |
| Insulation voltage input/output (Output data) | 3 kV AC |
| Low Voltage Directive (Connection data, output) | Conformance with Low Voltage Directive 2014/35/EC |
| Vibration (operation) (Connection data, output) | IEC 60068-2-6, sinusoidal waves: 10 Hz ... 500 Hz, 19,6 m/s² (2g peak), 10 min. per cycle, 60 min. in the X direction |
| Nominal input voltage range (Ambient conditions) | 100 V AC ... 240 V AC |
| Protective circuit/component (Ambient conditions) | Varistor |
| Ambient temperature (storage/transport) (Dimensions) | -40 °C ... 85 °C |
| Standard - Electrical safety (Connection data, output) | EN 60950-1 |
| Electromagnetic compatibility (Connection data, output) | Conformance with EMC Directive 2014/30/EU |
| Installation distances left/right (Key Commercial Data) | 10 mm |
| Installation distances top/bottom (Key Commercial Data) | 50 mm |
| Setting range of the output voltage (USet) (Input data) | 22 V DC ... 28 V DC (max. power ≤ 280 W) |
| Conductor cross section AWG max. (Connection data, input) | 12 |
| Conductor cross section AWG min. (Connection data, input) | 16 |
| Max. permissible relative humidity (operation) (Dimensions) | ≤ 95 % (at 25 °C, non-condensing) |
| Maximum power dissipation in no-load condition (Input data) | 5 W (115 V AC) |
| Standard – Safety extra-low voltage (Connection data, output) | EN 60950-1 (SELV) |
| Approval - requirement of the semiconductor industry with regard to mains voltage dips (Connection data, output) | SEMI F47 - 0706 (200 V AC) |
Technical specifications and performance data