| Parameter | Value |
|---|---|
| Surge protection | |
| Note | The meaning of the acknowledgement outputs can be freely parameterized, see user manual |
| Color | green (RAL 6021) |
| Depth | 120 mm |
| Width | 62 mm |
| Height | 107 mm |
| Interface | RS-232 |
| Input name | Device supply |
| Mains type | 3-phase |
| Power range | 0.1 kW ... 5 kW (x transformation ratio of external current transducers) |
| Product type | Electronic motor manager |
| Screw thread | M3 |
| Assembly note | Can be aligned with > 20 mm spacing |
| Current range | 0.25 A ... 5 A (x transformation ratio of external current transducers) |
| Measuring via | Current transformer for any conductor current |
| Voltage range | 0 V ... 318 V (Toward virtual star point) |
| Basic accuracy | ± 2 % (Of input value, type < ± 1 %, cosφ 0.7, tu 20 °C, I = 5 A) |
| Operating mode | 100% operating factor |
| Status display | LED (yellow) |
| Mains frequency | 50 Hz |
| Error indication | Red LED |
| Number of phases | 3 |
| Residual voltage | < 1 V |
| Stripping length | 8 mm |
| Connection method | Screw connection |
| Mounting position | Vertical (horizontal DIN rail) |
| Number of outputs | 4 |
| Quiescent current | 80 mA AC |
| Protective circuit | Reverse polarity protection; Series polarity protection diode |
| Transmission speed | 19200 bit (baud) |
| Current consumption | 80 mA |
| Input voltage range | 110 V AC ... 550 V AC (conductor voltage) |
| Degree of protection | IP20 |
| Standards/regulations | DIN EN 50178 |
| Typical response time | < 25 ms |
| Typical turn-off time | < 25 ms |
| Nominal output voltage | UVN- 1 V |
| Nominal supply voltage | 24 V DC |
| Continuous load current | 50 mA |
| Nominal input voltage UN | 24 V DC ±20 % |
| Operating voltage display | Green LED |
| Test voltage input/output | 2.5 kV |
| Conductor cross section AWG | 24 ... 10 |
| Typical input current at UN | 2 A |
| Conductor cross section rigid | 0.2 mm² ... 6 mm² |
| Ambient temperature (operation) | -20 °C ... 60 °C |
| Conductor cross section flexible | 0.2 mm² ... 4 mm² |
| Nominal output voltage range (factor) | 0.8 ... 1.2 |
| Input voltage range in reference to UN | 0.8 ... 1.2 |
| Reaction time in normal load operation | < 25 ms |
| Ambient temperature (storage/transport) | -20 °C ... 70 °C |
| Supply voltage range with reference to UVN | 0.8 ... 1.2 |
Technical specifications and performance data
Installation and operation guide