| Parameter | Value |
|---|---|
| () | II (2) D [Ex t] [Ex p] |
| GTIN | 4046356175753 |
| Note | Made to Order (non-returnable) |
| ATEX () | II (2) G [Ex e] [Ex d] [Ex px] |
| Orderkey | 2297497 |
| Catalog page | Page 14 (C-5-2017) |
| Depth (Note) | 114.5 mm |
| Packing unit | 1 pc |
| Width (Note) | 22.5 mm |
| Height (Note) | 99 mm |
| Indication () | Red LED |
| Input name () | Current measuring input L1/T1, L2/T2, L3/T3 |
| Designation () | Standards/regulations |
| Country of origin | DE (Germany) |
| Status display () | LED yellow right rotation (R), LED yellow left rotation (L), LED green data communication |
| Custom tariff number | 85371098 |
| Input voltage range () | 42 V AC ... 575 V AC |
| Screw thread (General) | M3 |
| Switching threshold () | 9.6 V DC (“0” signal) |
| Output name (Input data) | Acknowledging contacts O1-O4 |
| Standards/regulations () | DIN EN 50178 |
| Connection name (General) | Load circuit |
| Stripping length (General) | 8 mm |
| Connection method (General) | Screw connection |
| Degree of protection (Note) | IP20 |
| Measuring via (Output data) | External push-through current transformers connected upstream |
| (Standards and Regulations) | For details about hazardous substances go to tab “Downloads”, Category “Manufacturer's declaration” |
| Basic accuracy (Output data) | typ. 0.5 % |
| Mains frequency (Input data) | 50 Hz ... 60 Hz |
| Operating voltage display () | Green LED |
| Rated actuating current IC () | 3.3 mA |
| Rated actuating voltage UC () | 24 V DC |
| Residual voltage (Input data) | < 200 mV |
| Number of outputs (Input data) | 4 |
| Typical input current at UN () | 5 A (Secondary external converter) |
| Control supply voltage range () | 19.2 V DC ... 30 V DC |
| Operating mode (Power measurement) | 100% operating factor |
| Rated control supply current IS () | 25 mA |
| Nominal output voltage (Input data) | 24 V DC (semiconductor output) |
| Voltage range (Current measurement) | 0 V AC ... 350 V AC (Phase-to-neutral voltage) |
| Basic accuracy (Current measurement) | typ. 0.75 % |
| Continuous load current (Input data) | 500 mA |
| Weight per Piece (excluding packing) | 263.000 g |
| Conductor cross section AWG (General) | 24 ... 14 |
| Mounting position (Power measurement) | Vertical (horizontal DIN rail) |
| Surge voltage protection (Input data) | > 33 V DC |
| Voltage range with reference to US () | 0.8 ... 1.25 |
| Ambient temperature (operation) (Note) | -25 °C ... 70 °C |
| China RoHS (Standards and Regulations) | Environmentally Friendly Use Period = 50 |
| REACh SVHC (Standards and Regulations) | Lead 7439-92-1 |
| Conductor cross section solid (General) | 0.2 mm² ... 2.5 mm² |
| Assembly instructions (Power measurement) | In rows with zero spacing |
| Protective circuit/component (Input data) | Suppressor diode |
| Conductor cross section flexible (General) | 0.2 mm² ... 2.5 mm² |
| Rated control circuit supply voltage US () | 24 V DC |
| Test voltage input/output (Power measurement) | 8 kV |
| Utilization restriction (Key Commercial Data) | EMC: class A product, see manufacturer's declaration in the download area |
| Ambient temperature (storage/transport) (Note) | -25 °C ... 70 °C |
| Category acc. to EN ISO 13849 (Power measurement) | ≤ 1 (Safe shutdown) |
| Nominal output voltage range (factor) (Input data) | 0.8 ... 1.25 |
| Power range (Voltage measurement/phase-to-neutral voltage) | 4.5 kW (x amplitude transmission factor for current transformer) |
| Performance level according to ISO 13849 (Power measurement) | ≤ b (Safe shutdown) |
| Basic accuracy (Voltage measurement/phase-to-neutral voltage) | typ. 2 % |