| Parameter | Value |
|---|---|
| Surge protection | |
| Color | green (RAL 6021) |
| Depth | 102 mm |
| Width | 10 mm |
| Height | 75 mm |
| EMC note | EMC: class A product, see manufacturer's declaration in the download area |
| Insulation | Basic insulation |
| Application | Output function |
| Product type | Solid-state relay module |
| Screw thread | M3 |
| Assembly note | in rows with zero spacing |
| Mounting type | DIN rail mounting |
| Operating mode | 100% operating factor |
| Output circuit | 2-conductor, floating |
| Status display | LED (yellow) |
| Article revision | 10 |
| Pollution degree | 2 |
| Stripping length | 8 mm |
| Connection method | Screw connection |
| Mounting position | any |
| Protective circuit | Reverse polarity protection; Polarity protection diode |
| Input voltage range | 176 V DC ... 264 V DC |
| Degree of protection | IP20 |
| Output voltage range | 4 V DC ... 48 V DC |
| Overvoltage category | III |
| Standards/regulations | IEC 60664 |
| Typical response time | 20 µs |
| Typical turn-off time | 100 µs |
| Contact switching type | 1 N/O contact |
| Output nominal voltage | 48 V DC |
| Transmission frequency | 500 Hz |
| Design of digital output | electronic |
| Nominal input voltage UN | 220 V DC |
| Conductor cross section AWG | 24 ... 12 |
| Limiting continuous current | 100 mA |
| Test voltage (Input/output) | 3.5 kV AC (Input/output) |
| Typical input current at UN | 4 mA |
| Date of last data management | 24.05.2023 |
| Conductor cross section rigid | 0.2 mm² ... 4 mm² |
| Ambient temperature (operation) | -20 °C ... 60 °C |
| Conductor cross section flexible | 0.2 mm² ... 2.5 mm² |
| Flammability rating according to UL 94 | V0 |
| Input voltage range in reference to UN | 0.8 ... 1.2 |
| Ambient temperature (storage/transport) | -20 °C ... 70 °C |
| Voltage drop at max. limiting continuous current | 0.9 V |
| Switching threshold "0" signal in reference to UN | ≤ 0.4 |
| Switching threshold "1" signal in reference to UN | ≥ 0.8 |