| Parameter | Value |
|---|---|
| Reverse polarity protection | |
| Note | Confirmation 01: floating changeover contact |
| Depth | 114 mm |
| Width | 22.5 mm |
| Height | 107 mm |
| Altitude | ≤ 2000 m |
| Input name | Control input right/left |
| Certificate | UKCA-compliant |
| Cooling time | 20 min. (for auto reset) |
| Product type | Hybrid motor starters |
| Screw thread | M3 |
| Assembly note | can be aligned with spacing: see derating |
| Mounting type | DIN rail mounting |
| Product family | CONTACTRON |
| Status display | LED (yellow) |
| Leakage current | 0 mA |
| Mains frequency | 50/60 Hz |
| Article revision | 07 |
| Error indication | Red LED |
| Number of phases | 3 |
| Stripping length | 8 mm |
| Connection method | Screw connection |
| Mounting position | Vertical (horizontal DIN rail) |
| Tightening torque | 0.5 Nm ... 0.6 Nm |
| Load current range | 1.5 A ... 9 A (see to derating) |
| Motor starter type | Reversing starter |
| Protective circuit | Surge protection |
| Degree of pollution | 2 |
| Rated surge voltage | 6 kV |
| Switching frequency | ≤ 2 Hz (Load-dependent) |
| Switching threshold | 9.6 V (“0” signal) |
| Overvoltage category | III |
| Standards/regulations | IEC 60947-1 |
| Typical response time | < 35 ms |
| Typical turn-off time | < 40 ms |
| Contact switching type | 1 changeover contact |
| Operating voltage range | 42 V AC ... 550 V AC |
| Rated insulation voltage | 500 V |
| Triggering voltage range | 19.2 V DC ... 30 V DC |
| Maximum power dissipation | 14.6 W |
| Minimum power dissipation | 1.1 W |
| Operating voltage display | Green LED |
| Rated actuating current IC | 5 mA (Input type 1) |
| Rated actuating voltage UC | 24 V DC |
| Rated operating current Ie | 9 A (AC-51) |
| Rated operating voltage Ue | 500 V AC |
| Conductor cross section AWG | 24 ... 14 |
| Control supply voltage range | 19.2 V DC ... 30 V DC |
| Conductor cross section rigid | 0.2 mm² ... 2.5 mm² |
| Ambient temperature (operation) | -25 °C ... 70 °C (observe derating) |
| Rated control supply current IS | 40 mA |
| Conductor cross section flexible | 0.2 mm² ... 2.5 mm² |
| Flammability rating according to UL 94 | V0 (Housing) |
| Ambient temperature (storage/transport) | -40 °C ... 80 °C |
| Rated control circuit supply voltage US | 24 V DC |
| Trigger characteristic in acc. with IEC 60947-4-2 | Class 10A |
| Switching capacity in accordance with IEC 60947-5-1 | 3 A (230 V, AC15) |
| Insulation characteristics between the control input and control supply voltage, and auxiliary circuit to the main circuit | Safe isolation (IEC 60947-1) at operating voltage ≤ 300 V AC |
Technical specifications and performance data
Installation and operation guide