| Parameter | Value |
|---|---|
| Surge protection | |
| Color | gray (RAL 7042) |
| Depth | 114.5 mm |
| Width | 12.5 mm |
| Height | 99 mm |
| Input name | Device supply |
| Insulation | Basic insulation |
| Certificate | UKCA-compliant |
| Load current | 6 A (see to derating) |
| Product type | Solid-state contactor |
| Screw thread | M3 |
| Assembly note | alignable, for spacing see derating |
| Mounting type | DIN rail mounting |
| Operating mode | 100% operating factor |
| Product family | CONTACTRON |
| Status display | LED (yellow) |
| Article revision | 08 |
| Number of phases | 1 |
| Pollution degree | 2 |
| Stripping length | 8 mm |
| Connection method | Screw connection |
| Mounting position | vertical (horizontal DIN rail, motor output below) |
| Quiescent current | approx. 7 mA (When switched off) |
| Tightening torque | 0.5 Nm ... 0.6 Nm |
| Protective circuit | Surge protection |
| Current consumption | 3 mA |
| Degree of protection | IP20 |
| Overvoltage category | III |
| Standards/regulations | EN 50178 |
| Typical response time | 200 µs |
| Operating voltage range | 10 V DC ... 30 V DC |
| Surge voltage protection | > 33 V DC |
| Triggering voltage range | 19.2 V DC ... 28.8 V DC |
| Operating voltage display | Green LED |
| Rated actuating current IC | 3 mA |
| Rated actuating voltage UC | 24 V DC |
| Rated operating voltage Ue | 24 V DC |
| Conductor cross section AWG | 26 ... 14 |
| Test voltage (Input/output) | 2.5 kVrms(50 Hz, 60 s) |
| Control supply voltage range | 10 V DC ... 30 V DC |
| Conductor cross section rigid | 0.14 mm² ... 2.5 mm² |
| Ambient temperature (operation) | -20 °C ... 60 °C |
| Rated control supply current IS | 7 mA |
| Conductor cross section flexible | 0.14 mm² ... 2.5 mm² |
| Switchover time RL/LL(turn-on time) | 80 ms |
| Current limitation at short-circuits | 20 A |
| Rated operating current (Load output) | 6 A |
| Ambient temperature (storage/transport) | -20 °C ... 80 °C |
| Rated control circuit supply voltage US | 24 V DC |