| Parameter | Value |
|---|---|
| Reverse polarity protection | |
| FLA | 2.4 A (500 V AC) |
| Note | Confirmation: floating change-over contact, signal contact |
| SCCR | 100 kA (500 V AC (fuse: 30 A class CC/30 A class J (high fault))) |
| Depth | 114 mm |
| Width | 22.5 mm |
| Height | 107.5 mm |
| Altitude | ≤ 2000 m |
| Input name | Control input right/left |
| Certificate | UKCA-compliant |
| Cooling time | 20 min. (for auto reset) |
| Product type | Hybrid motor starters |
| Assembly note | alignable, for spacing see derating |
| Category code | NLDX |
| Mounting type | DIN rail mounting |
| Identification | II (2) G [Ex e] [Ex d] [Ex px] |
| Operating mode | 100% operating factor |
| Product family | CONTACTRON |
| Status display | LED (yellow) |
| Leakage current | 0 mA |
| Mains frequency | 50/60 Hz |
| Switching level | < 5 V DC (For EMERGENCY STOP) |
| Article revision | 05 |
| Error indication | Red LED |
| Number of phases | 3 |
| Stripping length | 10 mm |
| Connection method | Push-in connection |
| Coordination type | 1 |
| Mounting position | vertical (horizontal DIN rail, motor output below) |
| Group installation | 20 A (class RK5, SCCR 5kA, #24 - 14 AWG max. solid and stranded) |
| Load current range | 180 mA ... 2.4 A (see to derating) |
| Motor starter type | Reversing starter |
| Protective circuit | Surge protection |
| Degree of pollution | 2 |
| Rated surge voltage | 6 kV |
| Switching frequency | ≤ 2 Hz (Load-dependent) |
| Switching threshold | 9.6 V (“0” signal) |
| Degree of protection | IP20 |
| Overvoltage category | III |
| Standards/regulations | IEC 60947-1 |
| Typical turn-off time | < 30 ms |
| Contact switching type | 1 changeover contact |
| Operating voltage range | 42 V AC ... 550 V AC |
| Rated insulation voltage | 500 V |
| Triggering voltage range | 19.2 V DC ... 30 V DC |
| Maximum power dissipation | 3.3 W |
| Minimum power dissipation | 1.1 W |
| Operating voltage display | Green LED |
| Rated actuating current IC | 5 mA (Input type 1) |
| Rated actuating voltage UC | 24 V DC |
| Rated operating current Ie | 2.4 A (AC-51) |
| Rated operating voltage Ue | 500 V AC |
| Conductor cross section AWG | 24 ... 14 |
| Control supply voltage range | 19.2 V DC ... 30 V DC |
| Conductor cross section rigid | 0.2 mm² ... 2.5 mm² |
| Ambient temperature (operation) | -25 °C ... 70 °C (observe derating) |
| Rated control supply current IS | 40 mA |
| Conductor cross section flexible | 0.2 mm² ... 2.5 mm² |
| Flammability rating according to UL 94 | V0 (Housing) |
| Ambient temperature (storage/transport) | -40 °C ... 80 °C |
| Rated control circuit supply voltage US | 24 V DC |
| Maximum power dissipation for nominal condition | 2.2 W |
| Trigger characteristic in acc. with IEC 60947-4-2 | Class 10A |
| Switching capacity in accordance with IEC 60947-5-1 | 3 A (230 V, AC15) |
| Isolation characteristics between the control input and control supply voltage to auxiliary circuit | Safe isolation (IEC 60947-1) in the auxiliary circuit ≤ 300 V AC |
| Insulation characteristics between the control input and control supply voltage, and auxiliary circuit to the main circuit | Safe isolation (IEC 60947-1) at operating voltage ≤ 300 V AC |
Technical specifications and performance data
Installation and operation guide