Service time: Monday to Friday 9:00-18:00
ELR H5-I-SC-230AC/500AC-2 - ELR H5-I-SC-230AC/500AC-2 2900575 PHOENIX CONTACT Hybrid motor starter
In Stock Hot Product

ELR H5-I-SC-230AC/500AC-2

ELR H5-I-SC-230AC/500AC-2 2900575 PHOENIX CONTACT Hybrid motor starter

$0.00USD
4470 in stock
Key Specifications
GTIN:4046356528177
Orderkey:2900575
(UL data):Safe isolation (EN 50178) in the auxiliary circuit ≤ 300 V AC
Catalog page:Page 25 (C-5-2017)
Supplier Information
Products: 0
Usually ships within 2-3 business days
Quality Guaranteed
Fast Shipping
Technical Support

Technical Specifications

ParameterValue
GTIN4046356528177
Orderkey2900575
(UL data)Safe isolation (EN 50178) in the auxiliary circuit ≤ 300 V AC
Catalog pagePage 25 (C-5-2017)
Packing unit1 pc
(Input data)2.4 A (AC-53a)
(Device supply)85 V AC (“1” signal)
Torque (General)0.5 Nm ... 0.6 Nm
Country of originDE (Germany)
(Connection data 2)30 A (class CC or J, SCCR 100kA, #24 - 14 AWG max, solid and stranded)
Custom tariff number85371098
Insulation (UL data)Safe isolation (IEC 60947-1) in the auxiliary circuit ≤ 300 V AC
Designation (UL data)Isolation characteristics between the control input and control supply voltage to auxiliary circuit
Screw thread (General)M3
FLA (Connection data 2)2.4 A (500 V AC)
Output name (Input data)AC output
SCCR (Connection data 2)100 kA (500 V AC (fuse: 30 A class CC/30 A class J (high fault)))
(Approvals/conformities)For details about hazardous substances go to tab “Downloads”, Category “Manufacturer's declaration”
Connection name (General)Control circuits
Cooling time (Input data)20 min. (for auto reset)
(Output data load output)2 A (24 V, DC13)
Input name (Device supply)Control input right/left
Stripping length (General)8 mm
Torque (Connection data 1)0.5 Nm ... 0.6 Nm
Connection method (General)Screw connection
Depth (Key Commercial Data)113.7 mm
Width (Key Commercial Data)22.5 mm
Height (Key Commercial Data)106.6 mm
Leakage current (Input data)0 mA
Mains frequency (Input data)50/60 Hz
(Insulation characteristics)ISO 13849
Degree of pollution (UL data)2
Rated surge voltage (UL data)4 kV
Note (Output data load output)Confirmation: floating change-over contact, signal contact
Overvoltage category (UL data)III
Load current range (Input data)180 mA ... 2.4 A (see to derating)
Mains frequency (Device supply)50/60 Hz
Type of protection (Input data)Surge protection
Screw thread (Connection data 1)M3
Category code (Connection data 2)NLDX / NRNT
Degree of protection (Dimensions)IP20
Rated insulation voltage (UL data)500 V
China RoHS (Approvals/conformities)Environmentally Friendly Use Period = 50
Connection name (Connection data 1)Load circuit
REACh SVHC (Approvals/conformities)Lead 7439-92-1
Switching threshold (Device supply)44 V AC (“0” signal)
Mains frequency (Ambient conditions)50/60 Hz
Operating voltage range (Input data)42 V AC ... 550 V AC
Stripping length (Connection data 1)8 mm
Weight per Piece (excluding packing)216.110 g
Conductor cross section AWG (General)24 ... 14
Connection method (Connection data 1)Screw connection
Indication (Output data reply output)Red LED
Output name (Output data load output)Acknowledge output
Typical turn-off time (Device supply)< 70 ms
Contact type (Output data load output)1 PDT
Group installation (Connection data 2)20 A (class RK5, SCCR 5kA, #24 - 14 AWG max. solid and stranded)
Conductor cross section solid (General)0.2 mm² ... 2.5 mm²
Rated operating current Ie (Input data)2.4 A (AC-51)
Rated operating voltage Ue (Input data)500 V AC
Type of protection (Ambient conditions)Surge protection
Designation (Insulation characteristics)Standards/regulations
Mounting type (Output data reply output)DIN rail mounting
Triggering voltage range (Device supply)85 V AC ... 253 V AC
Operating mode (Output data reply output)100% operating factor
Status display (Output data reply output)Yellow LED
Conductor cross section flexible (General)0.2 mm² ... 2.5 mm²
Rated actuating current IC (Device supply)7 mA (Input type 1)
Rated actuating voltage UC (Device supply)230 V AC
UL certificate (Standards and Regulations)NLDX.E228652
Ambient temperature (operation) (Dimensions)-25 °C ... 70 °C (observe derating)
Mounting position (Output data reply output)vertical (horizontal DIN rail, motor output below)
Switching frequency (Output data reply output)≤ 2 Hz (Load-dependent)
Conductor cross section AWG (Connection data 1)24 ... 14
Assembly instructions (Output data reply output)alignable, for spacing see derating
Conductor cross section solid (Connection data 1)0.2 mm² ... 2.5 mm²
Control supply voltage range (Ambient conditions)85 V AC ... 253 V AC
Standards/regulations (Insulation characteristics)IEC 60947-1
Ambient temperature (storage/transport) (Dimensions)-40 °C ... 80 °C
Conductor cross section flexible (Connection data 1)0.2 mm² ... 2.5 mm²
Maximum power dissipation (Output data reply output)4.7 W
Minimum power dissipation (Output data reply output)2.6 W
Operating voltage display (Output data reply output)Green LED
Rated control supply current IS (Ambient conditions)4 mA
Rated control circuit supply voltage US (Ambient conditions)230 V AC
Trigger characteristic in acc. with IEC 60947-4-2 (Input data)Class 10A
Switching capacity according to IEC 60947-5-1 (Output data load output)3 A (230 V, AC15)

Product Description

Hybrid start controller for reversing motors from 3~ AC up to 550 V AC, with 230 V AC input, 2.4 A output current and adjustable overload disconnect.
Key Features
  • Industrial grade quality
  • RoHS compliant
  • CE certified
  • 1-year warranty

Product Documents

Datasheet

Technical specifications and performance data

User Manual

Installation and operation guide

Top