Key Specifications
GTIN:4046356771337
Orderkey:2903910
(UL data):Safe isolation (EN 50178) in the auxiliary circuit ≤ 300 V AC
Catalog page:Page 25 (C-5-2017)
Supplier Information
Products: 0
Usually ships within 2-3 business days
Quality Guaranteed
Fast Shipping
Technical Support

Technical Specifications

ParameterValue
GTIN4046356771337
Orderkey2903910
(UL data)Safe isolation (EN 50178) in the auxiliary circuit ≤ 300 V AC
Catalog pagePage 25 (C-5-2017)
Depth (Note)113.7 mm
Packing unit1 pc
Width (Note)22.5 mm
(Input data)2.4 A (AC-53a)
Height (Note)107.4 mm
(Device supply)19.2 V (“1” signal)
Country of originDE (Germany)
(Connection data 2)30 A (class CC or J, SCCR 100kA, #24 - 14 AWG max, solid and stranded)
Custom tariff number85371098
Insulation (UL data)Safe isolation (IEC 60947-1) in the auxiliary circuit ≤ 300 V AC
(Ambient conditions)Reverse polarity protection
Designation (UL data)Isolation characteristics between the control input and control supply voltage to auxiliary circuit
FLA (Connection data 2)2.4 A (500 V AC)
Output name (Input data)AC output
SCCR (Connection data 2)100 kA (500 V AC (fuse: 30 A class CC/30 A class J (high fault)))
(Approvals/conformities)For details about hazardous substances go to tab “Downloads”, Category “Manufacturer's declaration”
Connection name (General)Control circuits
Cooling time (Input data)20 min. (for auto reset)
(Output data load output)2 A (24 V, DC13)
Input name (Device supply)Control input right/left
Note (Key Commercial Data)If this device is to be used in combination with the CrossPowerSystem power distribution board, the device mount for the 16 A fuse (order designation: EM-CPS-DA-22,5F/16A; order number: 1002668) is required in order to attach the hybrid motor starter to the power distribution board.
Stripping length (General)10 mm
Connection method (General)Push-in connection
Leakage current (Input data)0 mA
Mains frequency (Input data)50/60 Hz
(Insulation characteristics)ISO 13849
Degree of pollution (UL data)2
Rated surge voltage (UL data)6 kV
Note (Output data load output)Confirmation: floating change-over contact, signal contact
Overvoltage category (UL data)III
Load current range (Input data)180 mA ... 2.4 A (see to derating)
Type of protection (Input data)Surge protection
Category code (Connection data 2)NLDX / NRNT
Degree of protection (Dimensions)IP20
Rated insulation voltage (UL data)500 V
Type of note (Key Commercial Data)Notes on operation
Type of protection (Device supply)Reverse polarity protection
China RoHS (Approvals/conformities)Environmentally Friendly Use Period = 50
Connection name (Connection data 1)Load circuit
Switching threshold (Device supply)9.6 V (“0” signal)
Operating voltage range (Input data)42 V AC ... 550 V AC
Stripping length (Connection data 1)10 mm
Weight per Piece (excluding packing)217.700 g
Conductor cross section AWG (General)24 ... 14
Connection method (Connection data 1)Push-in connection
Indication (Output data reply output)Red LED
Output name (Output data load output)Acknowledge output
Typical turn-off time (Device supply)< 30 ms
Contact type (Output data load output)1 PDT
Group installation (Connection data 2)20 A (class RK5, SCCR 5kA, #24 - 14 AWG max. solid and stranded)
Conductor cross section solid (General)0.2 mm² ... 2.5 mm²
Rated operating current Ie (Input data)2.4 A (AC-51)
Rated operating voltage Ue (Input data)500 V AC
Type of protection (Ambient conditions)Surge protection
Designation (Insulation characteristics)Standards/regulations
Mounting type (Output data reply output)DIN rail mounting
Triggering voltage range (Device supply)19.2 V DC ... 30 V DC
Operating mode (Output data reply output)100% operating factor
Status display (Output data reply output)Yellow LED
Conductor cross section flexible (General)0.2 mm² ... 2.5 mm²
Rated actuating current IC (Device supply)5 mA (Input type 1)
Rated actuating voltage UC (Device supply)24 V DC
UL certificate (Standards and Regulations)NLDX.E228652
Ambient temperature (operation) (Dimensions)-25 °C ... 70 °C (observe derating)
Mounting position (Output data reply output)vertical (horizontal DIN rail, motor output below)
Switching frequency (Output data reply output)≤ 2 Hz (Load-dependent)
Conductor cross section AWG (Connection data 1)24 ... 14
Assembly instructions (Output data reply output)alignable, for spacing see derating
Conductor cross section solid (Connection data 1)0.2 mm² ... 2.5 mm²
Control supply voltage range (Ambient conditions)19.2 V DC ... 30 V DC
Standards/regulations (Insulation characteristics)IEC 60947-1
Ambient temperature (storage/transport) (Dimensions)-40 °C ... 80 °C
Conductor cross section flexible (Connection data 1)0.2 mm² ... 2.5 mm²
Maximum power dissipation (Output data reply output)3.3 W
Minimum power dissipation (Output data reply output)1.1 W
Operating voltage display (Output data reply output)Green LED
Rated control supply current IS (Ambient conditions)40 mA
Rated control circuit supply voltage US (Ambient conditions)24 V DC
Trigger characteristic in acc. with IEC 60947-4-2 (Input data)Class 10A
Switching capacity according to IEC 60947-5-1 (Output data load output)3 A (230 V, AC15)

Product Description

Hybrid start controller for reversing 3~AC motors up to 500V AC and 2.4A output current, with 24V DC control voltage, adjustable overload disconnect and push-in connection.
Key Features
  • Industrial grade quality
  • RoHS compliant
  • CE certified
  • 1-year warranty